AUTOMATION
CONTROLS

Search
Discontinued
Products



Communication Unit for CC-Link IE Field / CC-Link

Specifications

■SC-GU3-□

■SC-HG1-□

Communication unit for CC-Link IE Field

Model No. SC-GU3-04
Applicable regulations CE Marking (EMC Directive (Note 1), RoHS Directive), UKCA Marking (EMC Regulations (Note 1), RoHS Regulations)
Compatible sensor units Sensor amplifiers (NPN output type) that can connect to the SC‑71 cascading connector unit (optional)
Number of units connectable Maximum of 16 units can be connected to one SC-GU3-04 unit
(Max. 12 units when FX500 / LS-500 series is connected)
Supply voltage 24 V DC +10-15 % Ripple P-P 10 % or less
Current consumption 200 mA or less (excluding connected sensor amplifiers)
Allowable passing current 2A or less (Note 2)
Communication method CC-Link IE Field
Remote station type Remote device station
Transmission line types Line, star (mixing of line and star types is possible), ring
Network No. setting 1 to 239 (decimal) [1 to EF (hex)] (0 and 240 or higher result in an error) (Note 3)
Station No. setting 1 to 120 (decimal) (0 and 121 or higher result in an error)
Communication speed 1 Gbps
Maximum overall cable distance 100 m 328.084 ft
Ambient temperature -10 to +50 ℃ +14 to +122 ℉
(8 to 16 units connected: -10 to +45 ℃ +14 to +113 ℉)
(No dew condensation or icing allowed)
Storage: -20 to +70 ℃ -4 to +158 ℉
Ambient humidity 35 to 85 % RH, Storage: 35 to 85 % RH
Material Enclosure: Polycarbonate
Net weight 100 g approx.

Notes:

1) Ground the shield wire of the Ethernet cable at a higher-level device in order to comply with the EMC Directives / EMC Regulations. This product is not provided with a grounding terminal.
For details, refer to the CC-Link IE Field Network Cable Installation Manual published by the CC-Link Partner Association.
2) Take care that the total consumption current of connected sensor amplifiers and other devices does not exceed the allowable passing current.
3) For the Network No. setting of this product, set a value converted to hexadecimal.

Return to top

Communication unit for CC-Link SC-GU3-01

Item SC-GU3-01
Applicable regulations CE Marking (EMC Directive, RoHS Directive), UKCA Marking (EMC Regulations, RoHS Regulations)
Number of connectable units Maximum of 16 units per SC-GU3-01 unit (Max. 12 units when FX-500 / LS-500 series are connected)
Supply voltage 24 V DC +10-15% Ripple P-P 10 % or less
Current consumption 120 mA or less (without connected sensor amplifiers)
Allowable passing current Wire-saving connector 2 A (Note 1), supply connector 6 A (Note 2)
Communication method CC-Link Ver.1.10
Number of occupied station Switchable 1 or 4 station
Baud rate 10 Mbps 5 Mbps 2.5 Mbps 625 kbps 156 kbps
Total extension length 100 m 328.084 ft 150 m 492.126 ft 200 m 656.168 ft 600 m 1968.504 ft 1,200 m 3937.008 ft
Communication cable Specified cable (twist pair cable with shield) (Note 3)
Station No. setting 1 to 64 (0 and 65 or more: Error)
Remote station type Remote device station
Ambient temperature –10 to +55 ℃ +14 to +131 ℉ (No dew condensation or icing allowed),
(If 4 to 7 units are connected in cascade: –10 to +50 ℃ +14 to +122 ℉,
if 8 to 16 units are connected in cascade: –10 to +45 ℃ +14 to +113 ℉)
Storage: –20 to +70 ℃ –4 to +158 ℉
Ambient humidity 35 to 85 % RH, Storage: 35 to 85 % RH
Material Enclosure: Polycarbonate
Weight Net weight: 80 g approx., Gross weight: 120 g approx.

Notes:

1) Be sure to check that total current consumption of sensor amplifiers connected in cascade does not exceed allowable passing current.
2) In case of supplying power to other devices, be sure to set the current less than allowable passing current.
3) Use only a special-use communication cable that is approved by the CC-Link Partner Association.

End unit

Item SC-GU3-EU
CE marking directive compliance EMC Directive, RoHS Directive
Number of connectable units 1 unit for 1 communication unit
Supply voltage 11 to 25 V DC Ripple P-P 10 % or less
Current consumption 25 mA or less
Power indicator Green LED (lights up when the power is ON)
Ambient temperature –10 to +55 ℃ +14 to +131 ℉ (No dew condensation or icing allowed),
(If 4 to 7 units are connected in cascade: –10 to +50 ℃ +14 to +122 ℉,
if 8 to 16 units are connected in cascade: –10 to +45 ℃ +14 to +113 ℉)
Storage: –20 to +70 ℃ –4 to +158 ℉
Ambient humidity 35 to 85 % RH, Storage: 35 to 85 % RH
Material Enclosure: Polycarbonate
Weight Net weight: 20 g approx., Gross weight: 20 g approx.

Cascading connector unit

Item SC-71
Number of connectable units Max. 16 units per 1 communication unit
Ambient temperature –10 to +55 ℃ +14 to +131 ℉ (No dew condensation or icing allowed),
(If 4 to 7 units are connected in cascade: –10 to +50 ℃ +14 to +122 ℉,
if 8 to 16 units are connected in cascade: –10 to +45 ℃ +14 to +113 ℉)
Storage: –20 to +70 ℃ –4 to +158 ℉
Ambient humidity 35 to 85 % RH, Storage: 35 to 85 % RH
Material Enclosure: Polycarbonate, Metal plate: Aluminum
Weight Net weight: 10 g approx., Gross weight: 25 g approx.

e-CON 1-channel connector input extension unit

Item SC-E1
Supply voltage 12 to 24V DC ±10%
Current consumption 20 mA or less (with all indicators on) (Note 1)
Number of signals 1 input
Input Connectable devices: NPN open-collector transistor output type (Input 1) sensor, DC 2-wire output type (Input 2) sensor (Note 2), switches, and other devices
Current supply for input device: 100 mA or less
Input impedance: 17 kΩ approx. (Input 1) or 3.2 kΩ approx. (Input 2)
Output NPN open-collector transistor
• Maximum sink current: 50 mA
• Applied voltage: 30 V DC or less (between output and 0 V)
• Residual voltage: 1.5 V or less (with sink current of 50 mA)
Power indicator Green LED (Lights up when the power is ON)
Input indicator Green LED (Lights up when input is being received by unit)
Ambient temperature –10 to +55 ℃ +14 to +131 ℉ (No dew condensation or icing allowed), (If 4 to 7 units are connected in cascade: –10 to +50 ℃ +14 to +122 ℉, if 8 to 16 units are connected in cascade: –10 to +45 ℃ +14 to +113 ℉) Storage: –20 to +70 ℃ –4 to +158 ℉
Ambient humidity 35 to 85% RH
Storage:35 to 85% RH
Material Enclosure: Flame-resistant PBT
Connector: Polyester
Weight Net weight: 15g approx., Gross weight: 40g approx.
Accessory Connector (e-CON): 1pc.

Notes:

1) Does not include current consumption or input current for connected input devices.
2) Conditions of connectable DC 2-wire type input device
・Leak current: 1 mA or less (when the power is OFF),
Offset voltage: 3 V or less (when the power is ON)
・ Product whose load current range includes 5 to 8 mA

e-CON 8-channel connector input extension unit

Item SC-E81
Supply voltage 12 to 24V DC ±10%
Current consumption 60 mA or less (with all indicators on) (Note 1)
Number of signals 8 inputs (Note 2)
Input Connectable devices: NPN transistor / open-collector output type sensors, switches, and other devices
Current supply for input devices: 800 mA or less (total for 8 inputs)
Input impedance: Approx. 17 kΩapprox
Output NPN open-collector transistor
• Maximum sink current: 50 mA
• Applied voltage: 30 V DC or less (between output and 0 V)
• Residual voltage: 1.5 V or less (with sink current of 50 mA)
Power indicator Green LED (lights up when the power is ON)
Input indicator 8 green LEDs (light up when input is received from the corresponding channel)
Ambient temperature –10 to +55 ℃ +14 to +131 ℉ (No dew condensation or icing allowed),
(If 4 to 7 units are connected in cascade: –10 to +50 ℃ +14 to +122 ℉,
if 8 to 9 units are connected in cascade: –10 to +45 ℃ +14 to +113 ℉)
Storage: –20 to +70 ℃ –4 to +158 ℉
Ambient humidity 35 to 85% RH
Storage: 35 to 85% RH
Material Enclosure: Polycarbonate 
Connector: Polyester
Weight Net weight: 40g approx., Gross weight: 85g approx.

Notes:

1) Does not include current consumption or input current for connected input devices.
2) Uses eight channels of signaling, regardless of the number of connected input devices.

e-CON 8-channel connector input extension unit (without an input signal indicator)

Item SC-E82
Supply voltage 5 to 24 V DC ±10%
Current consumption 7mA or less
Number of signals 8 inputs (Note 1)
Input Connectable devices: NPN open-collector transistor output type
sensors, switches, and other devices (Note 2)
Current supply for input devices: 800 mA or less (total for 8 inputs)
Power indicator Green LED (Lights up when the power is ON)
Ambient temperature –10 to +55 ℃ +14 to +131 ℉ (No dew condensation or icing allowed),
(If 4 to 7 units are connected in cascade: –10 to +50 ℃ +14 to +122 ℉,
if 8 to 9 units are connected in cascade: –10 to +45 ℃ +14 to +113 ℉)
Storage: –20 to +70 ℃ –4 to +158 ℉
Ambient humidity 35 to 85% RH
Storage: 35 to 85% RH
Material Enclosure: Polycarbonate
Connector: Polyester
Weight Net weight: 40g approx.
Gross weight: 85g approx.

Notes:

1) Uses eight channels of signaling, regardless of the number of connected input devices.
2) When using in combination with the SC-MIL, it can use as a commercially available device including a DC 2-wire type sensor or output. Refer to the SC series for the SC-MIL.

Analog voltage input unit
Analog current input unit

Item Analog voltage input unit Analog current input unit
SC-A01 SC-A02
Supply voltage 12 to 24V DC±10%, Ripple P-P 10% or less
Current consumption 25 mA or less (with all indicators on and 24 V applied) (Note 1)
Analog input Voltage: 1 to 5 V DC (input impedance: approx. 200 kΩ) Current: 4 to 20 mA DC (input impedance: approx. 250 kΩ)
Communication data
(Note 2)
Analogue ⇔ Communication data
・Communication data: 0 to 4,000 digits (within range of 1 to 5 V)
・Zero point: Within 0 digit ±0.5% F.S. (within the range of 1 to 5V)
・Span: Within 4,000 digits ±0.5% F.S.
・Linearity: Within ±0.5% F.S.
Analogu ⇔ Communication data
・Communication data: 0 to 4,000 digits (within range of 4 to 20 mA)
・Zero point: Within 0 digit ±0.5% F.S.
・Span: Within 4,000 digits ±0.5% F.S.
・Linearity: Within ±0.5% F.S.
Input Connectable devices: NPN open-collector transistor output type
Current supply for input devices: 100 mA or less
Input impedance: 17 kΩ approx.
Operating voltage: On voltage of 17 V or more (between input and +V, 24 V applied)
Off voltage of 4 V or less (between input and +V, 24 V applied)
Output NPN open-collector transistor
• Maximum sink current: 50 mA or less (when expanding to 5 units or more, 25 mA)
• Applied voltage: 30 V DC or less (between output and 0 V)
• Residual voltage: 1.5 V or less (with sink current of 50 mA)
Power indicator Green LED (lights up when the power is ON)
Input indicator Green LED (lights up when input is being received by unit)
Ambient temperature –10 to +55 ℃ +14 to +131 ℉ (No dew condensation or icing allowed),
(If 4 to 7 units are connected in cascade: –10 to +50 ℃ +14 to +122 ℉,
if 8 to 16 units are connected in cascade: –10 to +45 ℃ +14 to +113 ℉)
Storage: –20 to +70 ℃ –4 to +158 ℉
Ambient humidity 35 to 85% RH, Storage: 35 to 85% RH
Material Case: Flame-resistant PBT, Connector: Polyester
Weight Net weight: 15 g approx., Gross weight: 40 g approx.
Accessory Connector (e-CON): 1

Note:

1) Does not include current consumption or input current for connected input devices.
2) The figure below illustrates the relationship between communication data and input voltage.

Models connectable to SC-GU3-□

Communication
compatibility
Type Model No.
Models that support optical
communications
Digital fiber sensor (Note) FX-501, FX-502, FX301, FX-305
Digital laser sensor LS-403, LS-501
Digital pressure sensor DPS-401, DPS-402
1ch connector input unit
(analog communication unit)
SC-A01, SC-A02
No optical communications Digital fiber sensor (Note) FX-551, FX-411, FX-412, FX-301(B/G/H), FX-301-HS
Manually Set Fiber Sensor FX-311(B/G)
Digital laser sensor LS-401
Compact inductive proximity sensor GA-311
1ch connector input unit SC-E1
8ch connector input unit SC-E81, SC-E82
Note: FX-301 fiber sensor products manufactured before June 2004 are not compatible with optical communication. Those produced from June 2004 are compatible with optical communication.
If "NAVI" is printed only on one side of the product, the unit is not compatible with optical communication. If "NAVI" is printed on both sides of the product, the unit is compatible with optical communication. Please check when using FX-301 fiber sensors.

When connecting ordinary photoelectronic / proximity sensors or analog sensors

By using the SC-E1, SC-E81 or SC-E82 e-CON-compatible connector input extension unit, ordinary photoelectronic / proximity sensors and analog sensors can be connected to the SC-GU3.
The SC-A01 and SC-A02 allow the connection of analog output devices. (1 to 5 V, 4 to 20 mA)

When connecting ordinary photoelectronic / proximity sensors or analog sensors


CC-Link IE Field Communication Unit for HG series SC-HG1-CEF

Model No. SC-HG1-CEF
Applicable regulations CE Marking (EMC Directive, RoHS Directive), UKCA Marking (EMC Regulations, RoHS Regulations)
Compatible controllers HG-SC□, HG-TC□
Maximum number of connectable controllers Maximum of 15 controllers (one master, 14 slaves) per SC‑HG1‑CEF unit
Supply voltage(Note 2) 24V DC ±10%, including 0.5V ripple (P-P)
Current consumption 200 mA or less
Communication method CC-Link IE Field
Remote station type Remote device station
Network No. setting 1 to 239 (decimal) [1 to EF (hex)] (0 and 240 or more: Error)(Note 3)
Cyclic transmission
(Maximum number of
links per station)
RX/RY:128 points each (128 bits), 16 bytes,
RWr/RWw: 64 points each (64 words), 128 bytes
Transient transmission Server function only, data size 1024 bytes
Station No. setting 1 to 120 (decimal) (0 and 121 or more: Error)
Communication speed 1 Gbps
Transmission line type Line, star, (mixing of line and star types is possible), ring
Maximum transmission distance 100 m 328.084 ft
Maximum number of units connectable 121 units (1 master station, 120 slave stations)
Cascade connection levels Maximum 20
Pollution degree 2
Operating altitude 2,000 m 6561.68 ft or less(Note 4)
Environmental
resistance
Protection IP40 (IEC)
Ambient temperature -10 to +45 ℃ +14 to +113 ℉ (No dew condensation or icing allowed)
Storage: -20 to +60 ℃ -4 to +140 ℉
Ambient humidity 35 to 85 % RH, Storage: 35 to 85 % RH
Voltage
withstandability
1,000 V AC for one min. between all supply terminals
connected together and enclosure
Insulation
resistance
20 MΩ or more, with 250 V DC megger between all supply
terminals connected together and enclosure
Vibration resistance 10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude (10 to 58Hz), maximum acceleration 49 m/s2 (58 to 150 Hz) in X, Y and Z directions for two hours each
Shock resistance 98 m/s2 acceleration (10 G approx.) in X, Y and Z directions
five times each
Material Enclosure: Polycarbonate
Communication cable Ethernet cable that satisfies 1000BASE-T standard Category
5e or higher (Double-shielded / STP, straight cable)(Note 5)
Weight Net weight: 100 g approx., Gross weight: 150 g approx.

Notes:

1) Where measurement conditions have not been specified precisely, the conditions used
were ambient temperature +20 ℃ +68 ℉.
2) Power is supplied from a connected controller / master controller.
3) For the network number setting on this product, convert the network number to hex and
set the hex value.
4) Do not use or store in an environment that has been pressurized to an air pressure higher than the atmospheric pressure at 0 m.
5) Use CC-Link Partner Association recommended cable.

CC-Link Communication Unit for HG series SC-HG1-C

Model No. SC-HG1-C
Applicable regulations CE Marking (EMC Directive (Note 2), RoHS Directive), UKCA Marking (EMC Regulations (Note 2), RoHS Regulations)
Compatible controllers HG-SC□, HG-TC□
Maximum number of connectable controllers Maximum of 15 controllers (one master, 14 slaves) per SC-HG1-C unit
Supply voltage (Note 3) 24 V DC ±10 %, including 0.5 V ripple (P-P)
Current consumption 80 mA or less
Communication method Switchable CC-Link Ver.1.10 or 2.00
Remote station type Remote device station
Number of occupied station CC-Link Ver.1.10: 4 stations, CC-Link Ver.2.00: Switchable 2 or 4 stations
Station No. setting 1 to 64 (0 and 65 or more: Error)
Communication speed 10 Mbps 5 Mbps 2.5 Mbps 625 kbps 156 kbps
Maximum transmission
distance
100 m
328.084 ft
160 m
524.934 ft
400 m
1,312.336 ft
900 m
2,952.756 ft
1,200 m
3,937.008 ft
Pollution degree 2
Operating altitude 2,000 m 6561.68 ft or less (Note 4)
Environmental
resistance
Protection IP40 (IEC)
Ambient temperature -10 to +45 ℃ +14 to +113 ℉ (No dew condensation or icing allowed), Storage: -20 to +60 ℃ -4 to +140 ℉
Ambient humidity 35 to 85 % RH, Storage: 35 to 85 % RH
Voltage withstandability 1,000 V AC for one min. between all supply terminals connected together and enclosure
Insulation resistance 20 MΩ or more, with 250 V DC megger between all supply terminals connected together and enclosure
Vibration resistance 10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude (10 to 58 Hz), maximum acceleration 49 m/s2(58 to 150 Hz) in X, Y and Z directions for two hours each
Shock resistance 98 m/s2 acceleration (10 G approx.) in X, Y and Z directions five times each
Material Enclosure: Polycarbonate
Communication cable Specified cable (shielded twisted cable) (Note 5)
Weight Net weight: 80 g approx., Gross weight: 130 g approx.

Notes:

1) Where measurement conditions have not been specified precisely,
the conditions used were ambient temperature +20℃+68℉.
2) If our product will be incorporated in a customer product that will comply with the EMC Directive / EMC Regulations , install our product in a conductive box in accordance with "PLC User's Manual [Published by Mitsubishi Electric Corporation]".
3) Power is supplied from a connected controller / master controller.
4) Do not use or store in an environment that has been pressurized to an air pressure higher than the atmospheric pressure at 0 m.
5) Use only a special-use communication cable that is approved by the CC-Link Partner Association.

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region







BY PHONE

Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)