PA-N Relays

PA-N Relays PC board socket/Self-clinching terminal socket

Dimensions

Standard type
terminal socket
Self clinching type
terminal socket
RoHS compliant

Types

Product name Type No. Part No. Standard packing
Inner carton Outer carton
PC board socket PA1a-PS APA831 50 pcs. 500 pcs.
Self-clinching terminal socket PA1a-PS-H APA832

Return to top

Rating

Item Specifications
Dielectric strength
(initial)
Between pin No. 2 and 5: 2,000 Vrms for 1 min (detection current: 10 mA)
Between pin No. 5 and 6: 2,000 Vrms for 1 min (detection current: 10 mA)
Insulation resistance
(initial)
Each between terminals: Min. 1,000 MΩ
(at 500 V DC, Measured portion is the same as the case of dielectric strength.)
Max. carrying current 3 A
Conditions for usage,
transport and storage
Ambient temperature: -40 to +70°C
Humidity: 5 to 85% RH (Avoid icing and condensation)

Return to top

Handling

■ Mounting method of relay

1) Match the direction of relay and socket.

2) Insert both ends of the relay securely all the way in until both hooks clear the ribs on the relay case.

■ Removing method of relay

1) Remove the relay, applying force in the direction shown below.

2) In case there is not enough space for finger to pick relay up, use screwdrivers in the way shown.

3) When using the removal key (APA801), remove the relay as shown in the figure.
You can purchase the removal key (APA801) as an accessories.

4) Exercise care when removing relays. If greater than necessary force is applied at the socket hooks, deformation may alter the dimensions so that the hook will no longer catch, and other damage may also occur.

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region




Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)