Type | Ralay output type | Transistor output type | |||
---|---|---|---|---|---|
Item | AC type | DC/AC type | DC/AC type | ||
Rating | Rated operating voltage | 100 to 240 V | 12 to 24 V DC/24 V AC | 12 to 24 V DC/24 V AC | |
Rated frequency | 50/60 Hz common | ||||
Rated power consumption | Max. 10 V A | Max. 3 W | |||
Rated control capacity | 5 A 250 V AC (resistive load) | 100 mA, 30 V DC | |||
Input mode | Addition (UP)/Subtraction (DOWN)/Direction (DIR)/Individuality (IND)/Phase (PHASE) 5 modes selectable by DIP switches |
||||
Max. counting speed | 30 Hz, 5 kHz (selectable by DIP switches) | ||||
Counting input (input 1, input 2) |
16.7 ms at 30 Hz/0.1 ms at 5 kHz ON time: OFF time = 1:1 | ||||
Reset input | Min. input signal width: 1 ms, 20 ms (selected by DIP switches) | ||||
Lock input | Min. input signal width: 20 ms | ||||
Input signal | Contact, Open collector input/DC two-wire system sensor Input impedance: 1 kΩ or less, Input residual voltage: 2 V or less, Open impedance: 100 kΩ or less, Max. energized voltage: 40 V DC |
||||
Output mode | HOLD-A, HOLD-B, HOLD-C, SHOT-A, SHOT-B, SHOT-C, SHOT-D, 7 modes selectable by DIP switches | ||||
One shot output time | 1 s, 0.5s, 0.2s, 0.1s, 0.05, 0.01s | ||||
Indication | 7-segment LCD, Counter value (backlight red LED), Setting value (backlight yellow LED) | ||||
Digit | 4-digit display type --999 to 9999 (0 to 9999 for setting) 6-digit display type --99999 to 999999 (0 to 999999 for setting) |
||||
Decimal point | Can be set to three digits | ||||
Pre-scaling | 0.001 to 9.999 (4-digit type), 0.001 to 99.999 (6-digit type) | ||||
Memory | EEP-ROM (Overwriting times: 105 ope. or more) | ||||
Power for senser | 12 V DC (±10%) 100 mA Max. | - | |||
Contact | Contact arrangement | 1 Form C | 1 Form A (Open collector) | ||
Initial contact resistance | 100 mΩ (at 1 A 6 V DC) | - | |||
Contact material | Ag alloy/Au flush | - | |||
Life | Mechanical (contact) |
2×107 ope. (Except for switch operation parts) | - | ||
Electrical (contact) |
105 ope. (At rated control voltage) | 107 ope. (At rated control voltage) | |||
Electrical | Operating voltage range | 85 to 264 V AC | 10.8 to 26.4 V DC, 20.4 to 26.4 V AC | ||
Initial withstand voltage | Between live and dead metal parts: 2,000 Vrms for 1 min (pin type) Between input and output: 2,000 Vrms for 1 min |
||||
Initial insulation resistance (At 500 V DC) |
Between live and dead metal parts: Min. 100 MΩ (pin type) Between input and output: Min. 100 MΩ |
||||
Temperature rise | Max. 65°C (under the flow of nominal operating current at nominal voltage) | ||||
Mechanical | Vibration resistance |
Functional | 10 to 55 Hz (1 cycle/min), single amplitude: 0.35 mm (10 min on 3 axes) | ||
Destructive | 10 to 55 Hz (1 cycle/min), single amplitude: 0.75 mm (1 h on 3 axes) | ||||
Shock resistance |
Functional | Min. 98 m/s2 (4 times on 3 axes) | |||
Destructive | Min. 294 m/s2 (5 times on 3 axes) | ||||
Operating conditions | Ambient temperature | --10°C to 55°C/ +14°F to +131°F | |||
Ambient humidity | Max. 85 % RH (non-condensing) | ||||
Air pressure | 860 to 1,060 h Pa | ||||
Connection | 11-pin/screw terminal | ||||
Protective construction | IP66 (front panel with a rubber gasket) |
Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]