KT4H/B Temperature Controllers

Cautions For Use

Mounting

Please install vertically in order to satisfy the IP66 specification for dust and splash proofing.
The possible control panel plate thickness for installation is between 1 to 5 mm 0.039 to 0.197 in.

(1) Insert the unit from the front of the control panel.
(2) Push the mounting frame fully into contact with the paneland tighten the screws. (Screw tightening torque: 0.05 N·m to 0.06 N・m)

Part description

Note: Color selection is the same for each size.
(1)Action indicators (backlight: Orange)    
  ℉℃ Lights respectively when temperature unit/ is selected.
T/R Lights during serial communication (optional) TX output.
AT Flashes during auto-tuning or auto-reset.
OUT1 Lights when control output is ON or heating output (optional)
is ON.
For DC current output type, it flashes corresponding to the
manipulated variable in 0.25 second cycles.
OUT2 Lights when cooling output (optional) is ON.
EVT1 Lights when alarm output 1 is ON.
EVT2 Lights when alarm output 2 (optional) is ON or heater burnout
alarm output (optional) is ON.
LOCK Lights when lock 1, lock 2 or lock 3 is selected.
(2)MEMO display Indicates the set value memory number. (backlight: Green)
(3)PV display Indicates the process value (PV). (backlight: Red / Orange /
Green)
(4)SV display Indicates the set value (SV). (backlight: Green)
(5)Mode key Selects the setting mode and registers the set value.
(6)OUT/OFF key The control output ON / OFF or auto / manual control
function can be switched.
(7)Increase key Increases the numeric value.
(8)Decrease key Decreases the numeric value.
(9)Tool connector By connecting the dedicated cable, the following operations can be conducted from the external computer.
  • Reading and setting of SV, PID and various set values
  • Reading of PV and action status
  • Function change

Notes on site selection

This controller is intended to be used in the following environment (IEC 61010-1)

  • Overvoltage category II and Pollution degree 2

Mount the controller in a place with:

  • A minimum of dust, and an absence of corrosive gases
  • No flammable, explosive gases
  • Few mechanical vibrations or shocks
  • No exposure to direct sunlight, an ambient temperature of -10 to 55 ℃ 14 to 131 ℉ that does not change rapidly. (When installing inside a panel, make particular allowance for heat dissipation. Avoid installation in situations such as above equipment that generates heat.)
  • Locations in which temperature rapidly changes may cause condensation.
  • Locations or atmospheres in which benzine, thinners, alcohol, or other organic solvents are present, or in which ammonia, sodium hydroxide, or other strong alkaline substances may adhere.
  • Locations susceptible to direct impact or the transmission of vibrations, or where splashing with water is possible.
  • In the proximity of equipment in which large switching surges occur or near high-voltage cables, high-voltage equipment, power lines, power equipment, ham radio transmitters, or equipment containing these or similar devices.
  • An ambient non-condensing humidity of 35 to 85 % RH
  • No large capacity electromagnetic switches or cables through which large current is flowing
  • No water, oil or chemicals or where the vapors of these substances can come into direct contact with the controller

Notes on wiring

  • The terminal block of KT4R / KT8R / KT9R / KT4H / KT4B series are designed to be wired from the left side (The terminal of KT2 series are designed to be wired from the upper and lower direction). The lead wire must be inserted from the left side of the terminal, and fastened by the terminal screw. Use a wirepressed terminal with insulation sleeve that fits to the M3 screw.
Wire-pressed
terminal
Company name Type name Fastening
torque
Fork type NICHIFU Co., Ltd. 1.25Y-3 0.6 N•m
Max. 1.0 N•m.
J.S.T. Mfg. Co., Ltd. VD1.25-B3A
Round type NICHIFU Co., Ltd. 1.25-3
J.S.T. Mfg. Co., Ltd. V1.25-3

  • Terminal screw fastening torque is 0.6 N·m to 1.0 N·m (for KT4R / KT8R / KT9R / KT4H / KT4B series). For KT7 series by M3 screw is less than 0.5 N·m and by M2 screw is less than 0.25 N·m respectively.
  • Use a thermocouple and compensating lead wire according to the sensor input specification of the controller.
  • Use a 3-wire system of RTD according to the sensor input specification of the controller.
  • This controller has no built-in power switch, circuit breaker and fuse. Therefore, it is necessary to install them in the circuit near the external controller. (Recommended fuse: Time-lag fuse, rating voltage 250 V AC, rating current 2 A)
  • In the case of 24 V AC / DC power supply, do not confuse the polarity when it is DC.
  • With the relay contact output type, use the relay externally according to the capacity of the load to protect the built-in relay contact.
  • When wiring, keep input wire (Thermocouple, RTD, etc.) away from power source wire and load wire.
  • Turn the power supply to the instrument off before wiring or checking. Working or touching the terminal with the power switched on may result in electric shock which could cause severe injury or death.
  • Do not drop wire chips into the holes of vent when wiring.
  • To prevent the controller from harmful effects of unexpected high level noise, it is recommended that a surge absorber be installed between the electromagnetic switch coils.

Notes on mounting

  • Do not use excessive force while screwing in the mounting frame and mounting bracket of KT4R / KT8R / KT9R / KT4H / KT4B series.
    For KT8R / KT9R series, recommended torque is approximately 0.1 N·m.
    For KT4H / KT4B series, recommended torque is approximately 0.05 to 0.06 N·m.
    For KT4R series, recommended torque is approximately 0.15 N·m.
  • When mounting the KT7 series to the DIN rail, mount it in a lateral direction. Make sure a click is audible when fixed into place.

Optional heater burnout alarm output
(for KT7 / KT4H series)

  • This alarm output is not available for detecting heater current under phase control.
  • Use the current transformer (CT) provided, and pass one lead wire of the heater circuit into the hole of CT.
  • When wiring, keep CT wire away from power source wire and load wire to avoid external interference.
  • In three phase installations for KT4H series, ensure that R, S and T are each connected to a 2-line CT that connects with CT1 [(13) - (14)] and CT2 [(14) - (15)] terminals.

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region




Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)