AUTOMATION
CONTROLS

Search
Discontinued
Products



QM4H Digital Timers(DIN 48) (Discontinued Products)

Rating/ Performance

Item/Type QM4H-S QM4H-G
Rating Rated operating voltage 12 to 48 V AC/DC and 100 to 240 V AC/DC
Rated power consumption 12 to 48 V
AC/DC
During time delay 12 V DC, 48 V DC: Max. 1.5W
12 V AC, 48 V AC: Max. 3.0 VA
During time delay 12 V DC, 48 V DC: Max. 1.0W
12 V AC, 48 V AC: Max. 2.0 VA
After time delay 12 V DC, 48 V DC: Max. 2.5W
12 V AC, 48 V AC: Max. 5.0 VA
After time delay 12 V DC, 48 V DC: Max. 1.5W
12 V AC, 48 V AC: Max. 3.5 VA
100 to 240 V
AC/DC
During time delay 100 V DC, 240 V DC: Max. 1.5W
100 V AC, 240 V AC: Max. 3.0 VA
During time delay 100 V DC, 240 V DC: Max. 1.0W
100 V AC, 240 V AC: Max. 2.5 VA
After time delay 100 V DC, 240 V DC: Max. 2.0W
100 V AC, 240 V AC: Max. 4.0 VA
After time delay 100 V DC, 240 V DC: Max. 1.8W
100 V AC, 240 V AC: Max. 3.2 VA
Rated frequency 50/60 Hz common (at AC)
Rated control capacity 5 A, 250V AC (resistive load)
Time range 0.01s to 9990h, Selection of 8 range: 0.01s/0.1s/1s/0.1min/1min/0.1h/1h/10h
Operation mode Power ON delay Power ON delay (with reset and stop terminals)
Min. input signal width - 20ms (Reset and Stop inputs)*4
Time accuracy*1 Operating time fluctuation ±(0.01%+0.05s) in case of power on start
±(0.005%+0.03s) in case of input reset start*2
[Operating voltage: 85 to 110% V
Temperature: -10 to +55°C/ +14 to 131°F (20°C 68°F)
Stopped time: 0.1 sec to 1 hour]
Temperature error
Setting error
Voltage error
Contact Contact arrangement T.D. mode: Time delay 2C
INST. mode: Time delay 1C and Instantaneous 1C (Use MODE switch on front)
Time delay 1C
Contact material Silver alloy
Life*3 Mechanical (contact) Min. 107
Electrical (contact) Min. 105 (at rated control vltage)
Electrical Allowable operating voltage range 85 to 110% of rated operating voltage
Breakdown voltage
(Initial value)
Between live and dead metal parts, between input and output,
between contact sets, between contacts
Min. 100 MΩ (at 500 V DC megger)
Insulation resistance
(Initial value)
Between live and dead metal parts: 2, 000 Vrms for 1 min
Between input and output: 2, 000 Vrms for 1 min
Between contact sets: 2, 000 Vrms for 1 min
Between contacts: 1, 000 Vrms for 1 min
Reset time Max. 0.1s
Mechanical Vibration resistance Functional 10 to 55 Hz: 1 cycle/min. single amplitude of 0.25 mm .010 inch (10 min on 3 axes)
Destructive 10 to 55 Hz: 1 cycle/min. single amplitude of 0.375 mm .015 inch (1h on 3 axes)
Shock resistance Functional 98 m/s2 (4 times on 3 axes)
Destructive 980 m/s2 (5 times on 3 axes)
Operating conditions Ambient temperature -10 °C to 55°C/ +14°F to +131°F
Ambient humidity Min. 35 to 85% RH (non-condensing)
Air pressure 860 to 1060 hPa
Others Mass (Weight) Approx. 130 g 4.59 oz Approx. 120 g 4.23 oz
Available standards UL, c-UL, CE
Operating display LED (red), During time delay: blinking, After time delay: OFF

*1Unspecified measuring conditions are rated operating voltage (in case of DC type, ripple rate of 5% or less), ambient temp. 20℃ 68℉, and stop time 1 second.
*2Reset start applies to QM4H-G type.
*3Excluding switches
*4Note that if the QM4H-G type is set to zero “0” and a STOP signal is input, output will begin when the power is turned on.
*5The protective structure on the AQM4801 is IP50, and IP64 for the AQM4803.

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region




Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)