Business > Industrial Devices > Automation Controls Top > FA Sensors & Components > Measurement Sensors > Measurement Sensors > Communication Unit for Digital Displacement Sensors SC-HG1 > Specifications
Model No. | SC-HG1-ETC | |
---|---|---|
Applicable regulations | CE Marking (EMC Directive, RoHS Directive), UKCA Marking (EMC Regulations, RoHS Regulations) | |
Compatible controllers | HG-SC□, HG-TC□ | |
Maximum number of connectable controllers |
Maximum of 15 controllers (one master, 14 slaves) per SC-HG1-ETC unit | |
Supply voltage (Note 2) | 24 V DC ±10 %, including ripple 0.5 V (P-P) | |
Current consumption | 100 mA or less | |
Communication protocol | EtherCAT | |
Compliance | IEEE 802.3u (100BASE-TX) | |
Communication speed | 100 Mbps (100BASE-TX) | |
Communication connector | RJ-45×2 | |
Node-to-node distance | 100 m 328.084 ft or less | |
Supported functions | Process data object communication (cyclic communication) Mailbox communication (message communication) CoE Explicit Device Identification Station Alias |
|
Pollution degree | 2 | |
Operating altitude (Note 3) | 2,000 m 6,561.68 ft or less | |
Environmental resistance |
Ambient temperature |
-10 to +45 ℃ +14 to +113 ℉ (No dew condensation or icing allowed), Storage: -20 to +60 ℃ -4 to +140 ℉ |
Ambient humidity |
35 to 85 % RH, Storage: 35 to 85 % RH | |
Voltage withstandability |
1,000 V AC for one min. between all supply terminals connected together and enclosure | |
Insulation resistance |
20 MΩ or higher, using 250 V DC megger between all supply terminals connected together and enclosure | |
Vibration resistance |
10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude (10 to 58Hz), maximum acceleration 49 m/s2 (58 to 150 Hz) in X, Y and Z directions for two hours each |
|
Shock resistance |
98 m/s2 (10 G approx.) acceleration in X, Y, and Z directions five times each | |
Grounding method | Casing: Floating type | |
Material | Enclosure : Polycarbonate | |
Communication cable | Category 5e (shielded twisted pair cable recommended) | |
Weight | Net weight: 90 g approx. Gross weight: 150 g appox. |
Notes:
1) | Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +20 ℃ +68 ℉. |
---|---|
2) | Power is supplied from a connected controller / master controller. |
3) | Do not use or store in an environment that has been pressurized to an air pressure higher than the atmospheric pressure at 0 m. |
Model No. | SC-HG1-CEF | |
---|---|---|
Applicable regulations | CE Marking (EMC Directive, RoHS Directive), UKCA Marking (EMC Regulations, RoHS Regulations) | |
Compatible controllers | HG-SC□, HG-TC□ | |
Maximum number of connectable controllers | Maximum of 15 controllers (one master, 14 slaves) per SC‑HG1‑CEF unit | |
Supply voltage(Note 2) | 24V DC ±10%, including 0.5V ripple (P-P) | |
Current consumption | 200 mA or less | |
Communication method | CC-Link IE Field | |
Remote station type | Remote device station | |
Network No. setting | 1 to 239 (decimal) [1 to EF (hex)] (0 and 240 or more: Error)(Note 3) | |
Cyclic transmission (Maximum number of links per station) |
RX/RY:128 points each (128 bits), 16 bytes, RWr/RWw: 64 points each (64 words), 128 bytes |
|
Transient transmission | Server function only, data size 1024 bytes | |
Station No. setting | 1 to 120 (decimal) (0 and 121 or more: Error) | |
Communication speed | 1 Gbps | |
Transmission line type | Line, star, (mixing of line and star types is possible), ring | |
Maximum transmission distance | 100 m 328.084 ft | |
Maximum number of units connectable | 121 units (1 master station, 120 slave stations) | |
Cascade connection levels | Maximum 20 | |
Pollution degree | 2 | |
Operating altitude | 2,000 m 6561.68 ft or less(Note 4) | |
Environmental resistance |
Protection | IP40 (IEC) |
Ambient temperature | -10 to +45 ℃ +14 to +113 ℉ (No dew condensation or icing allowed) Storage: -20 to +60 ℃ -4 to +140 ℉ |
|
Ambient humidity | 35 to 85 % RH, Storage: 35 to 85 % RH | |
Voltage withstandability |
1,000 V AC for one min. between all supply terminals connected together and enclosure |
|
Insulation resistance |
20 MΩ or more, with 250 V DC megger between all supply terminals connected together and enclosure |
|
Vibration resistance | 10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude (10 to 58Hz), maximum acceleration 49 m/s2 (58 to 150 Hz) in X, Y and Z directions for two hours each | |
Shock resistance | 98 m/s2 acceleration (10 G approx.) in X, Y and Z directions five times each |
|
Material | Enclosure: Polycarbonate | |
Communication cable | Ethernet cable that satisfies 1000BASE-T standard Category 5e or higher (Double-shielded / STP, straight cable)(Note 5) |
|
Weight | Net weight: 100 g approx., Gross weight: 150 g approx. |
Notes:
1) | Where measurement conditions have not been specified precisely, the conditions used were ambient temperature +20 ℃ +68 ℉. |
---|---|
2) | Power is supplied from a connected controller / master controller. |
3) | For the network number setting on this product, convert the network number to hex and set the hex value. |
4) | Do not use or store in an environment that has been pressurized to an air pressure higher than the atmospheric pressure at 0 m. |
5) | Use CC-Link Partner Association recommended cable. |
Model No. | SC-HG1-C | |||||
---|---|---|---|---|---|---|
Applicable regulations | CE Marking (EMC Directive (Note 2), RoHS Directive), UKCA Marking (EMC Regulations (Note 2), RoHS Regulations) | |||||
Compatible controllers | HG-SC□, HG-TC□ | |||||
Maximum number of connectable controllers | Maximum of 15 controllers (one master, 14 slaves) per SC-HG1-C unit | |||||
Supply voltage (Note 3) | 24 V DC ±10 %, including 0.5 V ripple (P-P) | |||||
Current consumption | 80 mA or less | |||||
Communication method | Switchable CC-Link Ver.1.10 or 2.00 | |||||
Remote station type | Remote device station | |||||
Number of occupied station | CC-Link Ver.1.10: 4 stations, CC-Link Ver.2.00: Switchable 2 or 4 stations | |||||
Station No. setting | 1 to 64 (0 and 65 or more: Error) | |||||
Communication speed | 10 Mbps | 5 Mbps | 2.5 Mbps | 625 kbps | 156 kbps | |
Maximum transmission distance |
100 m 328.084 ft |
160 m 524.934 ft |
400 m 1,312.336 ft |
900 m 2,952.756 ft |
1,200 m 3,937.008 ft |
|
Pollution degree | 2 | |||||
Operating altitude | 2,000 m 6561.68 ft or less (Note 4) | |||||
Environmental resistance |
Protection | IP40 (IEC) | ||||
Ambient temperature | -10 to +45 ℃ +14 to +113 ℉ (No dew condensation or icing allowed), Storage: -20 to +60 ℃ -4 to +140 ℉ | |||||
Ambient humidity | 35 to 85 % RH, Storage: 35 to 85 % RH | |||||
Voltage withstandability | 1,000 V AC for one min. between all supply terminals connected together and enclosure | |||||
Insulation resistance | 20 MΩ or more, with 250 V DC megger between all supply terminals connected together and enclosure | |||||
Vibration resistance | 10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude (10 to 58 Hz), maximum acceleration 49 m/s2(58 to 150 Hz) in X, Y and Z directions for two hours each | |||||
Shock resistance | 98 m/s2 acceleration (10 G approx.) in X, Y and Z directions five times each | |||||
Material | Enclosure: Polycarbonate | |||||
Communication cable | Specified cable (shielded twisted cable) (Note 5) | |||||
Weight | Net weight: 80 g approx., Gross weight: 130 g approx. |
Notes:
1) | Where measurement conditions have not been specified precisely, the conditions used were ambient temperature +20℃+68℉. |
---|---|
2) | If our product will be incorporated in a customer product that will comply with the EMC Directive / EMC Regulations , install our product in a conductive box in accordance with "PLC User's Manual [Published by Mitsubishi Electric Corporation]". |
3) | Power is supplied from a connected controller / master controller. |
4) | Do not use or store in an environment that has been pressurized to an air pressure higher than the atmospheric pressure at 0 m. |
5) | Use only a special-use communication cable that is approved by the CC-Link Partner Association. |
Model No. | SC-HG1-485 | |
---|---|---|
Applicable regulations | CE Marking (EMC Directive, RoHS Directive), UKCA Marking (EMC Regulations, RoHS Regulations) | |
Compatible controllers | HG-SC□, HG-TC□ | |
Supply voltage (Note 2) | 24 V DC ±10 %, Ripple P-P 10 % or less (Within specified power supply voltage range) | |
Current consumption | 40 mA or less | |
Communication method | Two-wire half duplex communication | |
Synchronization method | Start-stop synchronization | |
Communication protocol | MODBUS (RTU / ASCII) / MEWTOCOL-COM | |
Communication speed | 1.2 kbps / 2.4 kbps / 4.8 kbps / 9.6 kbps / 19.2 kbps / 38.4 kbps / 57.6 kbps / 115.2 kbps | |
Electrical characteristics | Complies with EIA RS-485 | |
Number of connectable units |
Host (RS-485) | 1 to 99 units when MODBUS (RTU/ASCII) is used, 1 to 64 units when MEWTOCOL-COM is used |
Controllers | Maximum of 15 controllers (one master, 14 slaves) per SC-HG1-485 unit | |
Stop bit length | 1 bit / 2 bits | |
Parity check | Even / Odd / None | |
Data bit length | 8 bits (RTU) / 7 bits (ASCII) | |
Pollution degree | 2 | |
Operating altitude | 2,000 m 6561.68 ft or less (Note 3) | |
Environmental resistance |
Protection | IP40 (IEC) |
Ambient temperature | -10 to +45 ℃ 14 to +113 ℉ (No dew condensation or icing allowed), Storage: -20 to +60 ℃ -4 to +140 ℉ | |
Ambient humidity | 35 to 85 % RH, Storage: 35 to 85 % RH | |
Voltage withstandability | 1,000 V AC for one min. between all supply terminals connected together and enclosure | |
Insulation resistance | 20 MΩ, or more, with 250 V DC megger between all supply terminals connected together and enclosure | |
Vibration resistance | 10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude (10 to 58Hz), maximum acceleration 49 m/s2 (58 to 150 Hz) in X, Y and Z directions for two hours each | |
Shock resistance | 98 m/s2 acceleration (10 G approx.) in X, Y and Z directions five times each | |
Material | Enclosure: Polycarbonate | |
Total extension distance | Communication cable: 1,200 m 3,937.008 ft or less between SC-HG1-485 (terminal) and PLC | |
Weight | Net weight: 75 g approx., Gross weight: 120 g approx. | |
Accessories | Termination resistor switching jumper pin: 1 pc. |
Notes:
1) | Where measurement conditions have not been specified precisely, the conditions used were ambient temperature +20℃ +68 ℉. |
---|---|
2 | Power is supplied from a connected controller / master controller. |
3 | Do not use or store in an environment that has been pressurized to an air pressure higher than the atmospheric pressure at 0 m. |
Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)