AUTOMATION
CONTROLS

Search
Discontinued
Products



FP-XH

Specifications

General specifications

AFPXHC14□ / AFPXHC30□ / AFPXHC60□

Item Specifications
Operating ambient temperature 0 to +55 ℃ +32 to +131 ℉
Storage ambient temperature -40 to +70 ℃ -40 to +158 ℉
Operating ambient humidity 10 to 95 % RH (at +25 ℃ +77 ℉, non-condensing)
Storage ambient humidity 10 to 95 % RH (at +25 ℃ +77 ℉, non-condensing)
Breakdown
voltage
(Note)
    AC power supply DC power supply
Relay output Between power supply terminal and earth terminal 1,500 V AC for 1 minute 500 V AC for 1 minute
Between power supply terminal and service power supply terminal 1,500 V AC for 1 minute -
Between input terminal and earth terminal 1,500 V AC for 1 minute 500 V AC for 1 minute
Between output terminal and earth terminal 1,500 V AC for 1 minute 1,500 V AC for 1 minute
Transistor
output
Between power supply terminal and earth terminal 1,500 V AC for 1 minute 500 V AC for 1 minute
Between power supply terminal and service power supply terminal 1,500 V AC for 1 minute -
Between input terminal and earth terminal 1,500 V AC for 1 minute 500 V AC for 1 minute
Between output terminal and earth terminal 500 V AC for 1 minute 500 V AC for 1 minute
Isolation
resistance
Between power supply terminal and earth terminal 100 MΩ or more
(500 V DC using an insulation resistance meter)
Between power supply terminal and service power supply terminal
Between input terminal and earth terminal
Between output terminal and earth terminal
Vibration
resistance
5 to 8.4 Hz, 3.5 mm 0.138 in single amplitude
8.4 to 150 Hz, Acceleration 9.8 m/s2
10 min. each in the X, Y and Z directions (1 octave/min)
Shock resistance 147 m/s2, 4 times each in the X, Y and Z directions
Noise resistance 1,000 V [P-P] with pulse widths of 50 ns and 1 μs
(using a noise simulator) (Power supply terminal)
Operating condition No corrosive gas and no excessive dust
Applicable standard
for EC directives
EMC directive: EN 61131-2
(directive concerning emission, immunity and low voltage)
Over-voltage category Category II
Level of contamination 2

Note: Cut-off current 5 mA (Initial value at shipment)

Functional specifications

AFPXHC14□ / AFPXHC30□ / AFPXHC60□

Item Specifications
Programming method Relay symbol
Control method Cyclic operation
Program memory Built-in Flash ROM
Program capacity C14: 16 k steps, C30 / C60: 24 k / 32 k / 40 k steps
(switch-over) (Note 1)
Basic instructions Approx. 110
High-level instructions Approx. 220
Operation speed [Basic instruction (ST)]
Approx. 0.04 μs/step (under 7 k steps)
Approx. 0.7 μs/step (7 k steps or more)

[High-level instruction (F0MV)]
Approx. 0.22 μs/step (under 7 k steps)
Approx. 1.73 μs/step (7 k steps or more)
Operation
memory
Link
relay
External input (X) (Note 2) 1,760 points (X0 to X109F)
External output (Y) (Note 2) 1,760 points (Y0 to Y109F)
Internal relay (R) (Note 3) Default: 8,192 points (R0 to R511F)
FP-X compatible specifications: 4,096 points
Special internal relay (R) 240 points
Timer / Counter (T / C) (Note 4) 1,024 points (Initial settings Timer: 1,008 points, Counter: 16 points)
Link relay (L) 2,048 points (L0 to L127F)
Memory
area
Data register (DT) C14: 12 k words, C30 / C60: 64 k, 32 k, 12 k words
* For C30 / C60, DT capacity varies according to the program capacity
Special data register (DT) 500 words
Link data register (LD) 256 words (LD0 to LD255)
File register (FL) None
Index register (I) 14 words (I0 to ID)
Differential points Points for program capacity
Master control relay points (MCR) 256 points
Number of labels (JMP + LOOP) 256 points
Number of step ladders 1,000 steps
Number of subroutines 500 subroutines
Number of interrupt program Transistor output type: Input 8, Constant 1
Relay output type: Input 11 (for C30 / C60: 14), Constant 1
High-speed counter
(Note 5) (Note 6)
Control unit input [Transistor output type]
Single-phase 8 channels (100 kHz × 4, 10 kHz × 4) or 2-phase 4 channels (50 kHz × 2, 10 kHz × 2)

[Relay output type]
Single-phase 8 channels (10 kHz × 8) or 2-phase 4 channels (10 kHz × 4)
Pulse I/O with cassette
installed
[Transistor output type]
Installation not possible

[Relay output type]
C14: Single-phase 2 channels (100 kHz × 2) or 2-phase 1 channel (50 kHz × 1)
C30 / C60: Single-phase 4 channels (100 kHz × 4) or 2-phase 2 channels (50 kHz × 2)
*with two cassettes installed
Pulse output / PWM output
(Note 5) (Note 6)
Control unit output [Transistor output type]
C14: 3 channels, C30: 4 channels, C60: 6 channels

[Pulse output]
each 100 kHz

[PWM output]
3 channels (C14), 4 channels (other than C14)
1 Hz to 70 kHz (Resolution of 1000)
70.001 kHz to 100 kHz (Resolution of 100)
Pulse I/O with cassette
installed
[Relay output type]
C14: 1 channel, C30 / C60: 2 channels
*with two cassettes installed

[Pulse output]
each 100 kHz

[PWM output]
1 channel (C14), 2 channels (other than C14)
*with two cassettes installed
1 Hz to 70 kHz (Resolution of 1000)
70.001 kHz to 100 kHz (Resolution of 100)
Pulse catch input
Interrupt input (Note 6)
[Transistor output type]
8 points (Control unit input: 8 points)

[Relay output type]
14 points (Control unit input: 8 points, Pulse I/O cassette : 3 points × 2)
Periodical interrupt (Note 6) 0.1 ms to 30 sec.
Potentiometer input 1 channel (0 to 4,000)
Input time constant processing Available
Clock / calendar Available (only when the master memory cassette AFPX-MRTC and battery are installed)
Flash ROM
backup
Backup by F12 / P13 instructions All area of Data register
Automatic backup when
power is off
Counter: 16 points, Internal relay: 128 points,
Data register: 315 words
Battery backup Memory set in hold area of system register
(only when battery is installed)
Battery lifetime 5 years or more in the actual use condition
(operating 8 hours a day) (Note 7)
Password Yes (Can be selected from 4 digits, 8 digits or 32 digits)
Self-diagnostic function Watchdog timer, program syntax check, etc.
PLC link function Max. 16 units, link relay: 1,024 points, link register: 128 words
(Data transfer, remote programming: Not available)
Rewriting in RUN mode Available (downloading in RUN mode, program rewriting in RUN mode)
(Max. 512 steps)

Notes:

1) When changing the system register No.0 (sequence program capacity), the data register (DT) capacity will also change.
2) The number of points in the table is the number of points of operation memory.
The number of points actually available to be used is determined by the hardware configuration.
3) Can be selected by the setting of the system register No. 1 (internal relay capacity).
To provide compatibility with the conventional FP-X series control unit, select 4,096 points.
4) The number of timer points can be changed by the setting of the system register No.5.
5) The maximum counting speed and maximum output frequency for the high-speed counter, pulse output and PWM output indicate the specifications for the voltage of 24 V DC and ambient temperature of +25 ℃ +77 ℉. The frequency may decrease depending on voltage, temperature or combination of functions used.
6) The inputs and outputs used for each function of the high-speed counter, pulse output, PWM output, pulse catch input or interrupt input cannot be allocated in duplication.
7) Battery lifetime values is calculated when the power is not completely turned on.
Since the actual value depends on conditions of use, in practice, the lifetime may be shorter.

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region




Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)