FP0R

Cautions For Use

Limitation of combination

Limitation of combination of units
1.Up to 3 expansion or intelligent units can be connected to each base control unit. 2.There is no restriction on the type and the order in which expansion units are installed. 3.The relay output type and transistor type can be used in conjunction with each other.

Expansion method
No special expansion cables are required as the expansion unit employs a stacking system that uses expansion connectors and lock levers on the unit.

Controllable I/O points when expansion units are added

Type of control unit Control unit only When the expansion unit is the same output type as the control unit When the expansion unit is a transistor output type
C10 10 points Max. 58 points Max. 106 points
C14 14 points Max. 62 points Max. 110 points
C16 16 points Max. 112 points Max. 112 points
C32
T32
F32
32 points Max. 128 points Max. 128 points

Unit's current consumption table

Type of units Control unit Expansion unit Input circuit Output circuit
The current consumed by the control unit power supply connector. If expansion units or intelligent units are added, the current is increased by the value indicated below. The current consumed by the expansion unit power supply connector. If a unit is not listed below, it means that it has no power supply connector. The current consumed by the input circuits of the various units. The value indicates the current that flows into the input circuit. "n" indicates the number of points that are on. The current consumed by the output circuits of the various units. The value indicates the current used to drive the output circuit. "n" indicates the number of points that are on. The value does not include the load current value.
FP0R
control units
C10 100mA or less - 15.9mA -
C14 120 mA or less - 21.1mA -
C16 70mA or less - 21.1mA 20mA
C32
T32
F32
90mA or less - 42.2mA 40mA
FP0
expansion units
FP0-E8X 10mA or less - 34.4mA or less -
FP0-E8R 15mA or less 50mA or less 17.2mA or less -
FP0-E8YR 10mA or less 100mA or less - -
FP0-E8YT/P 15mA or less - - 24mA or less
FP0-E16X 20mA or less - 68.8mA or less -
FP0-E16R 20mA or less 100mA or less 34.4mA or less -
FP0-E16T/P 25mA or less - 34.4mA or less 24mA or less
FP0-E16YT/P 25mA or less - - 48mA or less
FP0-E32T/P 40mA or less - 68.8mA or less 48mA or less
FP0
intelligent unit
FP0-A21 20mA or less 100mA or less - -
FP0-A80 20mA or less 60mA or less - -
FP0-A04V 20mA or less 100mA or less - -
FP0-A04I 20mA or less 130mA or less - -
FP0-TC4
FP0-TC8
25mA or less - - -
FP0-IOL 30mA or less 40mA or less - -
FP0-CCLS 40mA or less 40mA or less - -

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region




Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)