Type | NPN output | PNP output | |||
---|---|---|---|---|---|
Model No. (Note 2) |
Front sensing | GX-F6A(I) | GX-F6B(I) | GX-F6A(I)-P | GX-F6B(I)-P |
Top sensing | GX-H6A(I) | GX-H6B(I) | GX-H6A(I)-P | GX-H6B(I)-P | |
CE marking directive compliance | EMC Directive, RoHS Directive | ||||
Max. operation distance (Note 3) |
1.6 mm 0.063 in ± 8 % | ||||
Stable sensing range (Note 3) |
0 to 1.3 mm 0 to 0.051 in | ||||
Standard sensing object | Iron sheet 12 x 12 x t 1 mm 0.472 x 0.472 x t 0.039 in | ||||
Hysteresis | 20 % or less of operation distance (with standard sensing object) |
||||
Repeatability | Along sensing axis, perpendicular to sensing axis: 0.04 mm 0.002 in or less | ||||
Supply voltage | 12 to 24 V DC+10/-15% Ripple P-P 10 % or less | ||||
Current consumption | 15 mA or less | ||||
Output | NPN open-collector transistor - Maximum sink current: 100 mA - Applied voltage: 30 V DC or less (between output and 0 V) - Residual voltage: 2 V or less (at 100 mA sink current) |
PNP open-collector transistor - Maximum source current: 100 mA - Applied voltage: 30 V DC or less(between output and +V) - Residual voltage: 2 V or less (at 100 mA source current) |
|||
Utilization category |
DC-12 or DC-13 | ||||
Output operation | Normally open | Normally closed | Normally open | Normally closed | |
Max. response frequency | 400 Hz | ||||
Operation indicator | Orange LED (lights up when the output is ON) |
||||
Pollution degree | 3 (Industrial environment) | ||||
Protection | IP68 (IEC), IP68G (Note 4, 5) | ||||
Ambient temperature | -25 to +70 ℃ -13 to +158 ℉, Storage: -40 to +85 ℃ -40 to +185 ℉ | ||||
Ambient humidity | 35 to 85 % RH, Storage: 35 to 95 % RH | ||||
Voltage withstandability | 1,000 V AC for one min. between all supply terminals connected together and enclosure | ||||
Insulation resistance | 50 MΩ, or more, with 500 V DC megger between all supply terminals connected together and enclosure | ||||
Vibration resistance | 10 to 500 Hz frequency, 3 mm 0.118 in double amplitude (Max. 20 G) in X, Y and Z directions for two hours each | ||||
Shock resistance | 10,000 m/s2 acceleration (1,000 G approx.) in X, Y and Z directions three times each | ||||
Sensing range variation |
Temperature characteristics |
Over ambient temperature range -25 to +70 ℃ -13 to +158℉: Within ±8 % of sensing range at +23℃ +73 ℉. | |||
Voltage characteristics |
Within ±2 % for +10/-15 % fluctuation of the supply voltage | ||||
Material | Enclosure: PBT, Indicator part: Polyester | ||||
Cable | 0.15 mm2 3-core oil, heat and cold resistant cabtyre cable, 1 m 3.281 ft long | ||||
Cable extension | Extension up to total 100 m 328.084 ft is possible with 0.3 mm2, or more, cable. | ||||
Net weight | 15 g approx. |
Notes:
1) | Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +23 ℃ +73 ℉. |
---|---|
2) | "I" in the model No. indicates a different frequency type. |
3) | The maximum operation distance stands for the maximum distance for which the sensor can detect the standard sensing object. The stable sensing range stands for the sensing range for which the sensor can stably detect the standard sensing object even if there is an ambient temperature drift and/or supply voltage fluctuation. |
4) | Panasonic Industrial Devices SUNX's IP68 test method (1)Immerse at 0 m below 0 ℃ +32 ℉ water surface and leave for 30 min. Then, immerse at 0 m below +70 ℃ +158 ℉ water surface and leave for 30 min. (2)Regard the heat shock test in (1) as one cycle and perform 20 cycles. (3)Leave in water at a depth of 1 m 3.281 ft in water for 500 hours. (4)After tests (1) to (3) , insulation resistance, voltage withstandability, current consumption, and sensing ranges must meet the standard values. |
5) | If using the sensor in an environment where cutting oil droplets splatter, the sensor may be deteriorated due to added substances in the oil. Please check the resistivity of the sensor against the cutting oil you are using beforehand. |
Type | NPN output | PNP output | |||
---|---|---|---|---|---|
Model No. (Note 2) |
Front sensing | GX-F8A(I) | GX-F8B(I) | GX-F8A(I)-P | GX-F8B(I)-P |
Top sensing | GX-H8A(I) | GX-H8B(I) | GX-H8A(I)-P | GX-H8B(I)-P | |
CE marking directive compliance | EMC Directive, RoHS Directive | ||||
Max. operation distance (Note 3) |
2.5 mm 0.098 in ± 8 % | ||||
Stable sensing range (Note 3) |
0 to 2.1 mm 0 to 0.083 in | ||||
Standard sensing object | Iron sheet 15 x 15 x t 1 mm 0.591 x 0.591 x t 0.039 in | ||||
Hysteresis | 20 % or less of operation distance (with standard sensing object) |
||||
Repeatability | Along sensing axis, perpendicular to sensing axis: 0.04 mm 0.002 in or less | ||||
Supply voltage | 12 to 24 V DC+10/-15% Ripple P-P 10 % or less | ||||
Current consumption | 15 mA or less | ||||
Output | NPN open-collector transistor - Maximum sink current: 100 mA - Applied voltage: 30 V DC or less (between output and 0 V) - Residual voltage: 2 V or less (at 100 mA sink current) |
PNP open-collector transistor - Maximum source current: 100 mA - Applied voltage: 30 V DC or less(between output and +V) - Residual voltage: 2 V or less (at 100 mA source current) |
|||
Utilization category |
DC-12 or DC-13 | ||||
Output operation | Normally open | Normally closed | Normally open | Normally closed | |
Max. response frequency | 500 Hz | ||||
Operation indicator | Orange LED (lights up when the output is ON) |
||||
Pollution degree | 3 (Industrial environment) | ||||
Protection | IP68 (IEC), IP68G (Note 4, 5) | ||||
Ambient temperature | -25 to +70 ℃ -13 to +158 ℉, Storage: -40 to +85 ℃ -40 to +185 ℉ | ||||
Ambient humidity | 35 to 85 % RH, Storage: 35 to 95 % RH | ||||
Voltage withstandability | 1,000 V AC for one min. between all supply terminals connected together and enclosure | ||||
Insulation resistance | 50 MΩ, or more, with 500 V DC megger between all supply terminals connected together and enclosure | ||||
Vibration resistance | 10 to 500 Hz frequency, 3 mm 0.118 in double amplitude (Max. 20 G) in X, Y and Z directions for two hours each | ||||
Shock resistance | 10,000 m/s2 acceleration (1,000 G approx.) in X, Y and Z directions three times each | ||||
Sensing range variation |
Temperature characteristics |
Over ambient temperature range -25 to +70 ℃ -13 to +158℉: Within ±8 % of sensing range at +23℃ +73 ℉. | |||
Voltage characteristics |
Within ±2 % for +10/-15 % fluctuation of the supply voltage | ||||
Material | Enclosure: PBT, Indicator part: Polyester | ||||
Cable | 0.15 mm2 3-core oil, heat and cold resistant cabtyre cable, 1 m 3.281 ft long | ||||
Cable extension | Extension up to total 100 m 328.084 ft is possible with 0.3 mm2, or more, cable. | ||||
Net weight | Front sensing type: 15 g approx., Top sensing type: 20 g approx.. |
Notes:
1) | Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +23 ℃ +73 ℉. |
---|---|
2) | "I" in the model No. indicates a different frequency type. |
3) | The maximum operation distance stands for the maximum distance for which the sensor can detect the standard sensing object. The stable sensing range stands for the sensing range for which the sensor can stably detect the standard sensing object even if there is an ambient temperature drift and/or supply voltage fluctuation. |
4) | Panasonic Industrial Devices SUNX's IP68 test method (1)Immerse at 0 m below 0 ℃ +32 ℉ water surface and leave for 30 min. Then, immerse at 0 m below +70 ℃ +158 ℉ water surface and leave for 30 min. (2)Regard the heat shock test in (1) as one cycle and perform 20 cycles. (3)Leave in water at a depth of 1 m 3.281 ft in water for 500 hours. (4)After tests (1) to (3) , insulation resistance, voltage withstandability, current consumption, and sensing ranges must meet the standard values. |
5) | If using the sensor in an environment where cutting oil droplets splatter, the sensor may be deteriorated due to added substances in the oil. Please check the resistivity of the sensor against the cutting oil you are using beforehand. |
Type | NPN output | PNP output | |||
---|---|---|---|---|---|
Model No. (Note 2) |
Front sensing | GX-F12A(I) | GX-F12B(I) | GX-F12A(I)-P | GX-F12B(I)-P |
Top sensing | GX-H12A(I) | GX-H12B(I) | GX-H12A(I)-P | GX-H12B(I)-P | |
CE marking directive compliance | EMC Directive, RoHS Directive | ||||
Max. operation distance (Note 3) |
4.0 mm 0.157 in ± 8 % | ||||
Stable sensing range (Note 3) |
0 to 3.3 mm 0 to 0.130 in | ||||
Standard sensing object | Iron sheet 20 x 20 x t 1 mm 0.787 x 0.787 x t 0.039 in | ||||
Hysteresis | 20 % or less of operation distance (with standard sensing object) |
||||
Repeatability | Along sensing axis, perpendicular to sensing axis: 0.04 mm 0.002 in or less | ||||
Supply voltage | 12 to 24 V DC+10/-15% Ripple P-P 10 % or less | ||||
Current consumption | 15 mA or less | ||||
Output | NPN open-collector transistor - Maximum sink current: 100 mA - Applied voltage: 30 V DC or less (between output and 0 V) - Residual voltage: 2 V or less (at 100 mA sink current) |
PNP open-collector transistor - Maximum source current: 100 mA - Applied voltage: 30 V DC or less(between output and +V) - Residual voltage: 2 V or less (at 100 mA source current) |
|||
Utilization category |
DC-12 or DC-13 | ||||
Output operation | Normally open | Normally closed | Normally open | Normally closed | |
Max. response frequency | 500 Hz | ||||
Operation indicator | Orange LED (lights up when the output is ON) |
||||
Pollution degree | 3 (Industrial environment) | ||||
Protection | IP68 (IEC), IP68G (Note 4, 5) | ||||
Ambient temperature | -25 to +70 ℃ -13 to +158 ℉, Storage: -40 to +85 ℃ -40 to +185 ℉ | ||||
Ambient humidity | 35 to 85 % RH, Storage: 35 to 95 % RH | ||||
Voltage withstandability | 1,000 V AC for one min. between all supply terminals connected together and enclosure | ||||
Insulation resistance | 50 MΩ, or more, with 500 V DC megger between all supply terminals connected together and enclosure | ||||
Vibration resistance | 10 to 500 Hz frequency, 3 mm 0.118 in double amplitude (Max. 20 G) in X, Y and Z directions for two hours each | ||||
Shock resistance | 10,000 m/s2 acceleration (1,000 G approx.) in X, Y and Z directions three times each | ||||
Sensing range variation |
Temperature characteristics |
Over ambient temperature range -25 to +70 ℃ -13 to +158℉: Within ±8 % of sensing range at +23℃ +73 ℉. | |||
Voltage characteristics |
Within ±2 % for +10/-15 % fluctuation of the supply voltage | ||||
Material | Enclosure: PBT, Indicator part: Polyester | ||||
Cable | 0.15 mm2 3-core oil, heat and cold resistant cabtyre cable, 1 m 3.281 ft long | ||||
Cable extension | Extension up to total 100 m 328.084 ft is possible with 0.3 mm2, or more, cable. | ||||
Net weight | Front sensing type: 20 g approx., Top sensing type: 20 g approx.. |
Notes:
1) | Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +23 ℃ +73 ℉. |
---|---|
2) | "I" in the model No. indicates a different frequency type. |
3) | The maximum operation distance stands for the maximum distance for which the sensor can detect the standard sensing object. The stable sensing range stands for the sensing range for which the sensor can stably detect the standard sensing object even if there is an ambient temperature drift and/or supply voltage fluctuation. |
4) | Panasonic Industrial Devices SUNX's IP68 test method (1)Immerse at 0 m below 0 ℃ +32 ℉ water surface and leave for 30 min. Then, immerse at 0 m below +70 ℃ +158 ℉ water surface and leave for 30 min. (2)Regard the heat shock test in (1) as one cycle and perform 20 cycles. (3)Leave in water at a depth of 1 m 3.281 ft in water for 500 hours. (4)After tests (1) to (3) , insulation resistance, voltage withstandability, current consumption, and sensing ranges must meet the standard values. |
5) | If using the sensor in an environment where cutting oil droplets splatter, the sensor may be deteriorated due to added substances in the oil. Please check the resistivity of the sensor against the cutting oil you are using beforehand. |
Type | NPN output | ||||
---|---|---|---|---|---|
Long sensing range | |||||
Model No. (Note 2) |
Front sensing | GX-F15A(I) | GX-F15B(I) | GX-FL15A(I) | GX-FL15B(I) |
Top sensing | GX-H15A(I) | GX-H15B(I) | GX-HL15A(I) | GX-HL15B(I) | |
CE marking directive compliance | EMC Directive, RoHS Directive | ||||
Max. operation distance (Note 3) |
5.0 mm 0.197 in ± 8 % | 8.0 mm 0.315 in ± 8 % (Note 4) | |||
Stable sensing range (Note 3) |
0 to 4.2 mm 0 to 0.165 in | 0 to 6.7 mm 0 to 0.264 in (Note 4) | |||
Standard sensing object | Iron sheet 20 x 20 x t 1 mm 0.787 x 0.787 x t 0.039 in |
Iron sheet 30 x 30 x t 1 mm 1.181 x 1.181 x t 0.039 in |
|||
Hysteresis | 20 % or less of operation distance (with standard sensing object) | ||||
Repeatability | Along sensing axis, perpendicular to sensing axis: 0.04 mm 0.002 in or less | ||||
Supply voltage | 12 to 24 V DC+10/-15% Ripple P-P 10 % or less | ||||
Current consumption | 15 mA or less | ||||
Output | NPN open-collector transistor - Maximum sink current: 100 mA - Applied voltage: 30 V DC or less (between output and 0 V) - Residual voltage: 2 V or less (at 100 mA sink current) |
||||
Utilization category |
DC-12 or DC-13 | ||||
Output operation | Normally open | Normally closed | Normally open | Normally closed | |
Max. response frequency | 250 Hz | 150 Hz (Note 5) | |||
Operation indicator | Orange LED (lights up when the output is ON) | ||||
Pollution degree | 3 (Industrial environment) | ||||
Protection | IP68 (IEC), IP68G (Note 6, 7) | ||||
Ambient temperature | -25 to +70 ℃ -13 to +158 ℉, Storage: -40 to +85 ℃ -40 to +185 ℉ | ||||
Ambient humidity | 35 to 85 % RH, Storage: 35 to 95 % RH | ||||
Voltage withstandability | 1,000 V AC for one min. between all supply terminals connected together and enclosure | ||||
Insulation resistance | 50 MΩ, or more, with 500 V DC megger between all supply terminals connected together and enclosure | ||||
Vibration resistance | 10 to 500 Hz frequency, 3 mm 0.118 in double amplitude (Max. 20 G) in X, Y and Z directions for two hours each | ||||
Shock resistance | 10,000 m/s2 acceleration (1,000 G approx.) in X, Y and Z directions three times each | ||||
Sensing range variation |
Temperature characteristics |
Over ambient temperature range -25 to +70 ℃ -13 to +158℉: Within ±8 % of sensing range at +23℃ +73 ℉. | |||
Voltage characteristics |
Within ±2 % for +10/-15 % fluctuation of the supply voltage | ||||
Material | Enclosure: PBT, Indicator part: Polyester | ||||
Cable | 0.15 mm2 3-core oil, heat and cold resistant cabtyre cable, 1 m 3.281 ft long | ||||
Cable extension | Extension up to total 100 m 328.084 ft is possible with 0.3 mm2, or more, cable. | ||||
Net weight | 20 g approx. |
Type | PNP output | ||||
---|---|---|---|---|---|
Long sensing range | |||||
Model No. (Note 2) |
Front sensing | GX-F15A(I)-P | GX-F15B(I)-P | GX-FL15A(I)-P | GX-FL15B(I)-P |
Top sensing | GX-H15A(I)-P | GX-H15B(I)-P | GX-HL15A(I)-P | GX-HL15B(I)-P | |
CE marking directive compliance | EMC Directive, RoHS Directive | ||||
Max. operation distance (Note 3) |
5.0 mm 0.197 in ± 8 % | 8.0 mm 0.315 in ± 8 % (Note 4) | |||
Stable sensing range (Note 3) |
0 to 4.2 mm 0 to 0.165 in | 0 to 6.7 mm 0 to 0.264 in (Note 4) | |||
Standard sensing object | Iron sheet 20 x 20 x t 1 mm 0.787 x 0.787 x t 0.039 in |
Iron sheet 30 x 30 x t 1 mm 1.181 x 1.181 x t 0.039 in |
|||
Hysteresis | 20 % or less of operation distance (with standard sensing object) | ||||
Repeatability | Along sensing axis, perpendicular to sensing axis: 0.04 mm 0.002 in or less | ||||
Supply voltage | 12 to 24 V DC+10/-15% Ripple P-P 10 % or less | ||||
Current consumption | 15 mA or less | ||||
Output | PNP open-collector transistor - Maximum source current: 100 mA - Applied voltage: 30 V DC or less (between output and +V) - Residual voltage: 2 V or less (at 100 mA source current) |
||||
Utilization category |
DC-12 or DC-13 | ||||
Output operation | Normally open | Normally closed | Normally open | Normally closed | |
Max. response frequency | 250 Hz | 150 Hz (Note 5) | |||
Operation indicator | Orange LED (lights up when the output is ON) | ||||
Pollution degree | 3 (Industrial environment) | ||||
Protection | IP68 (IEC), IP68G (Note 6, 7) | ||||
Ambient temperature | -25 to +70 ℃ -13 to +158 ℉, Storage: -40 to +85 ℃ -40 to +185 ℉ | ||||
Ambient humidity | 35 to 85 % RH, Storage: 35 to 95 % RH | ||||
Voltage withstandability | 1,000 V AC for one min. between all supply terminals connected together and enclosure | ||||
Insulation resistance | 50 MΩ, or more, with 500 V DC megger between all supply terminals connected together and enclosure | ||||
Vibration resistance | 10 to 500 Hz frequency, 3 mm 0.118 in double amplitude (Max. 20 G) in X, Y and Z directions for two hours each | ||||
Shock resistance | 10,000 m/s2 acceleration (1,000 G approx.) in X, Y and Z directions three times each | ||||
Sensing range variation |
Temperature characteristics |
Over ambient temperature range -25 to +70 ℃ -13 to +158℉: Within ±8 % of sensing range at +23℃ +73 ℉. | |||
Voltage characteristics |
Within ±2 % for +10/-15 % fluctuation of the supply voltage | ||||
Material | Enclosure: PBT, Indicator part: Polyester | ||||
Cable | 0.15 mm2 3-core oil, heat and cold resistant cabtyre cable, 1 m 3.281 ft long | ||||
Cable extension | Extension up to total 100 m 328.084 ft is possible with 0.3 mm2, or more, cable. | ||||
Net weight | 20 g approx. |
Notes:
1) | Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +23 ℃ +73 ℉. |
---|---|
2) | "I" in the model No. indicates a different frequency type. |
3) | The maximum operation distance stands for the maximum distance for which the sensor can detect the standard sensing object. The stable sensing range stands for the sensing range for which the sensor can stably detect the standard sensing object even if there is an ambient temperature drift and/or supply voltage fluctuation. |
4) | This is the numerical value which the sensor mount onto an insulator. When mounted onto a steel or stainless steel plate, insert the optional aluminum sheet between the sensor and the plate. |
5) | This is the numerical value which the sensor mount onto an insulator. When mounted onto a metallic plate, max. response frequency will decrease. |
6) | Panasonic Industrial Devices SUNX's IP68 test method (1)Immerse at 0 m below 0 ℃ +32 ℉ water surface and leave for 30 min. Then, immerse at 0 m below +70 ℃ +158 ℉ water surface and leave for 30 min. (2)Regard the heat shock test in (1) as one cycle and perform 20 cycles. (3)Leave in water at a depth of 1 m 3.281 ft in water for 500 hours. (4)After tests (1) to (3) , insulation resistance, voltage withstandability, current consumption, and sensing ranges must meet the standard values. |
7) | If using the sensor in an environment where cutting oil droplets splatter, the sensor may be deteriorated due to added substances in the oil. Please check the resistivity of the sensor against the cutting oil you are using beforehand. |
Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)