Business > Industrial Devices > Automation Controls Top > AKS1202
*Photo may vary from actual product.
Product Number | AKS1202 |
Part Number | AKS1202 |
Product | KS1 Signal Converter |
Product name | KS1 Signal Converter(Discontinued) |
Item | Specifications |
---|---|
Product Number | AKS1202 |
Part Number | AKS1202 |
Item | Specifications |
---|---|
Rated voltage | 24 V DC |
Operating voltage range | 90 to 110 %V of rated voltage (21.6 to 26.4 V DC) |
Inrush current | 12 A or less |
Current consumption | 200 mA or less |
Allowed momentary power off time | 10 ms |
Fuse | Built-in type |
Terminal screw | M2 |
Ambient temperature | 0 to 55 degrees |
Storage temperature | -20 to +75 degrees |
Ambient humidity | 30 to 85 % RH (at 20 degrees , non-condensing) |
Breakdown voltage(initial) | 500 V AC 1 minute, RS485 terminals ⇔ Combined power and ground terminals |
Insulation resistance(initial) | 100 Mohm or higher (500 V DC using an insulation resistance meter), RS485 terminals ⇔ Combined power and ground terminals |
Vibration resistance | 10 to 55 Hz, 1 cycle / min.: double amplitude of 0.75 mm, 1 hour on 3 axes |
Shock resistance | 294 m / s2 or more, 5 times on 3 axes |
Dimensions | 25 x 60 x 90 |
Weight | Approx. 80 g |
Item | Specifications |
---|---|
Ethernet | Interface: IEEE802.3u, 10BASE-T / 100BASE-TX Connector shape: RJ45 Transmission specifications (Transmission speed): 10 Mbps / 100 Mbps Transmission specifications (Transmission method): Base band Transmission specifications (Max. segment length): 100 m Communication cable: Category 5 UTP cable Protocol: Modbus TCP(RTU, ASCII), TCP / IP Functions: Auto negotiation function, MDI / MDI-X, Auto crossover function |
RS232C | Interface: RS-232C (non-insulated) Conversion COM port: COM1 (Note) Communication style: 1: 1 communication Number of connection units: 1 unit Communication method: Full duplex system Synchronous system: Synchronous communication method Transmission distance: 15 m 49 ft Transmission speed: 2,400 / 4,800 / 9,600 / 19,200 / 38,400 / 57,600 / 115,200 bps Connection connector quantity: Max. 3 COM receive time out: Setting range 10 ms to 300 s Non-transmission connection cut-off time: Setting range: 0 to 1800 s (Setting value of 0 is not cut off) Transmission format (Data length): 8 bit fixed Transmission format (Parity): Odd / even / none Transmission format (Stop bit): 1 bit / 2 bit Transmission format (End code): CR / CR+LF / None Serial ⇔ Ethernet conversion format: Command response format (Note) COM1 and COM2 can be used simultaneously. |
RS485 | Interface: RS-485 (insulated) Conversion COM port: COM2 (Note 1) Communication style: 1: N communication Number of connection units: Max. 99 units Communication method: Half-duplex operation Synchronous system: Synchronous communication method Transmission distance:Max. 1,200 m 3,937 ft (Note 2)(Note 3) Transmission speed: 2,400 / 4,800 / 9,600 / 19,200 / 38,400 / 57,600 / 115,200 bps Connection connector quantity: Max. 3 COM reception time-out: Setting range 10 ms to 300 s Non-transmission connection cut-off time: Setting range: 0 to 1800 s (Setting value of 0 is not cut off) Transmission format (Data length): 8 bit fixed Transmission format (Parity): Odd / even / none Transmission format (Stop bit): 1 bit / 2 bit Transmission format (End code): CR / CR+LF / None Serial ⇔ Ethernet conversion format: Command response format (Note 1) COM1 and COM2 can be used simultaneously. (Note 2) When connecting a commercially available device, please confirm operation using the actual device. In some case, the number of stations, transmission distance, and communication speed vary depending on the connected device. (Note 3) The values for the transmission distance, communication speed and number of stations should be within the values noted in the graph. |
Product Number | AFP0803 |
Part Number | AFP0803 |
Product name | Mounting plate |
Product Number | AFP0804 |
Part Number | AFP0804 |
Product name | Mounting plate |
Product Number | AFP0811 |
Part Number | AFP0811 |
Product name | Mounting plate |
Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)