Product Number AKW263100A
Part Number AKW263100A
Product KW2M Eco-Power Meter
Details Main unit
Product name KW2M Eco-Power Meter(Discontinued)
  • Substitute -
  • Sub Prod No. -
  • Sub Part No. -
  • Remark Sorry, no suggested alternative products.

Spec Detail As of September 29, 2023

Item Specifications
Product Number AKW263100A
Part Number AKW263100A

General specifications

Item Specifications
Supply voltage range 100 to 240V AC
Rated frequency 50/60 Hz
Nominal power consumption 15VA approx. (240V AC at 25 ℃ +77 ℉)
Inrush current 30A or less (240V AC/DC at 25 ℃ +77 ℉)
Allowable momentary power-off time 10 ms
Ambient temperature Operation: at -10 to +50 ℃ 14 to 122 ℉
Storage: at -25 to +70 ℃ -13 to 158 ℉
Ambient humidity 30 to 85% RH (at 20℃ 68℉) with non-condensing
Breakdown voltage(initial) Between the isolated circuits: 2,000 V/1 min
・ Enclosure - All terminals
・ Between primary and secondary insulated circuits (Double insulation is supported)
(1) Power supply terminals - other terminals
(2) Voltage input terminal - other terminals
Insulation resistance(initial) Between the isolated circuits: 100 MΩ or more
Vibration resistance 10 to 150Hz (7.5 minutes/cycle), Single amplitude: 0.75 mm 0.030 in (1 h on 3 axes)
10 to 55Hz (1 minute/cycle), Single amplitude: 0.375 mm 0.015 in (1 h on 3 axes)
Shock resistance Min. 294 m/s2 (5 times on 3 axes)
Display method Black-and-white LCD with backlight (graphic form)
Display updating time cycle 500, 1000, 2000, 3000 ms (set with setting mode)
Power failure memory method Internal memory
Sea level altitude Under 2,000 m 6,562 ft
Overvoltage category III
Pollution degree 2
Dimensions W/H/D 85 x 140 x 65 mm 3.346 x 5.512 x 2.559 in
Weight Approx. 450 g

Communication specifications(RS485)

Item Specifications
Interface Conforming to RS485
Communication method Half-duplex
Synchronous system Synchronous communication method
Isolation status Isolated with the internal circuits
Protocol MEWTOCOL, MODBUS (RTU)(select with setting mode)
Number of connected unit 99 units (max.)
(Note) For RS485 converter on the computer side, we recommend SI-35 and SI-35USB (from LINE EYE Co.,Ltd.) . When using SI-35, SI-35USB or PLC from our company (which can be connected up to 99 units), up to 99 can be connected. In case using this system with the other devices, up to 31 can be connected.
Transmission distance 1,200 m 3,937 ft
(Note) Please check with the actual devices when some commercial devices with RS485 interface are connected. The number of connected devices, transmission distance, and transmission speed may be different according to using transmission line.
Transmission speed 115200, 57600, 38400, 19200, 9600, 4800, 2400 bps (select with setting mode)
Transmission format : Data length 8 bit (fixed)
Transmission format : Parity Not available / Odd number / Even number (select with setting mode)
Transmission format : Stop bit 1 bit, 2 bit (select with setting mode)

Communication specifications(Ethernet)

Item Specifications
Number of communication ports 2
Interface IEEE802.3u, 100BASE-TX / 10BASE-T
Connector type RJ45
Transmission specifications : Transmission speed 100 Mbps / 10 Mbps
Transmission specifications : Transmission method Base band
Transmission specifications : Max. segment length 100 m 328 ft
Communication cable UTP (category 5)
Protocol (DNS, DHCP) TCP/IP, UDP/IP
Web server Setting, Monitoring measured values
Function Auto-negotiation function(Note) , MDI/MDI-X auto-crossover function
(Note) Speed change is automatically performed by an auto-negotiation function.
Dedicated communication MEWTOCOL,MODBUS(TCP)(2 session for each)

Output specifications

Item Specifications
Output points Two channels
(Note) Non-insulated between channels
Insulation method PhotoMOS relay
Output type 1a
Output capacity 100 mA, 30 V AC/DC
Output mode ・ Pulse by integral power
・ Output by alarm or events (set with setting mode)
Pulse Output by integral power : Pulse width 1 ms to 100 ms (set with setting mode)
Pulse Output by integral power : Pulse output unit 0.001 kWh / 0.01 kWh / 0.1 kWh / 1 kWh / 10 kWh / 100 kWh
Alarm output / Event output : Type Stand-by alarm/ Under voltage alarm/ Over voltage alarm/ Power interruption alarm/ Under current alarm/ Over current alarm/ Active power alarm/ Reactive power alarm/ Apparent power alarm/ PF alarm/ Over frequency alarm/ Under frequency alarm/ Voltage harmonics alarm/ Current harmonics alarm/ Voltage THD alarm/ Current THD alarm/ Unbalanced voltage alarm/ Unbalanced current alarm/ Power demand alarm/ Current demand alarm/ Counter output/ Level output (external control)
Alarm output / Event output : Alarm reset Self-reset (according to the setting) / Manual-reset
Protection element Varistor
(Note) Varistor is mounted internal as a protection element. Install a protective device in case of using at the place where it effects by surge.
Alarm output [OUT1][OUT2] : Display Lighting alarm mark
Alarm output [OUT1][OUT2] : Output signal Normal: OFF
Alarm: ON
Alarm output [OUT1][OUT2] : Output capacity 100 mA, 30 V AC/DC

Input specifications

Item Specifications
Input points 1 channel
Insulation method Input dedicated insulation (insulated with other funct ion terminals)
Input method Connection point / non-voltage a contact or open collector (operated by internal power source)
Input signal Non-voltage input
・ Impedance during short-circuit: 1 kΩ or less (short- circuit current, approx. 10 mA or less)
・ Residual voltage during short-circuit: 3 V or less
・ Impedance while open: 100 kΩ or more
Input mode Pulse input or external device output signal clock synchronization
Maximum counting speed 2000 Hz / 30 Hz
Minimum input signal width 0.25 ms (2000 Hz selected) / 16.7 ms (30 Hz selected)
ON: OFF ratio = 1: 1
Pre-scale setting : Decimal point Up to three decimal points can be selected
Pre-scale setting : Range 0.001 to 100.000 (set with setting mode)
Output mode (during pulse output selection) HOLD
Protection element Zener diode
Pulse input : Pulse input 1,000 to 99,000 pulse/kWh Arbitrary setting (External pulse converter required)
Pulse input : Pulse rate 0.001 to 100000 kWh/pulse
Pulse input : Pulse input condition (2000 Hz) Pulse width: 0.25 ms or more
Pulse interval: 0.5 ms or more (OFF time 0.25 ms or more)
Pulse input : Pulse input condition (30 Hz) Pulse width: 16.7 ms or more
Pulse interval: 33.4 ms or more (OFF time 16.7 ms or more)
Pulse input : Operation voltage / current 5 V DC 10 mA

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region



Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)