AUTOMATION
CONTROLS

Search
Discontinued
Products



RX2-D300-C5 | Robust Photoelectric Sensor RX(Discontinued)


Robust Photoelectric Sensor RX(Discontinued)

*Photo may vary from actual product.



  • Discontinued
  • Last time buySeptember 30, 2020
Product Number RX2-D300-C5
Part Number RX2-D300-C5
Product Robust Photoelectric Sensor
Details DC 2-wire type Diffuse reflective
Product name Robust Photoelectric Sensor RX(Discontinued)
  • Substitute -
  • Sub Prod No. -
  • Sub Part No. -
  • Remark Sorry, no suggested alternative products.

Spec Detail As of September 30, 2020

Item Specifications
Product Number RX2-D300-C5
Part Number RX2-D300-C5
Regulatory compliance EMC Directive, RoHS Directive
Sensing range 300 mm 11.811 in
(Note) The sensing range and the hysteresis of the specified for white non-glossy paper (200 x 200 mm 7.874 x 7.874 in) as the object.
Sensing object Opaque, translucent or transparent object
(Note) Make sure to confirm detection with an actual sensor before use.
Hysteresis 15 % or less of operation distance
(Note) The sensing range and the hysteresis of the specified for white non-glossy paper (200 x 200 mm 7.874 x 7.874 in) as the object.
Repeatability(perpendicular to sensing axis) 0.5 mm 0.020 in or less
Supply voltage 12 to 24 V DC plus or minus 10 % Ripple P-P 10 % or less
Current consumption 1 mA or less
(Note) It is the leakage current when the output is in the OFF state.
Sensing output Non contact DC 2-wire type
- Load current: 5 to 100 mA
- Residual voltage: 4 V or less (Note)
(Note) When extending the cable, the residual voltage will be increased depending on the type of cable used. Verify the residual voltage when extending the cable.
Sensing output:Output operation Switchable either Light-ON or Dark-ON
Sensing output:Short-circuit protection Incorporated
Response time 3 ms or less
Operation indicator Red LED (lights up when the output is ON)
Stability indicator Green LED (Light-ON mode: lights up under stable light received condition, Dark-ON mode: lights up under stable dark condition)
Emitting indicator -
Sensitivity adjuster Continuously variable adjuster
Protection IP67 (IEC)
Ambient temperature -20 to +60 degrees -4 to +140 degrees Fahrenheit (No dew condensation or icing allowed), Storage: -30 to +70 degrees -22 to +158 degrees Fahrenheit
Ambient humidity 35 to 85 % RH, Storage: 35 to 85 % RH
Ambient illuminance Incandescent light: 3,500 Lx or less at the light-receiving face
Voltage withstandability 1,000 V AC for one min. between all supply terminals connected together and enclosure
Insulation resistance 20 MOhm , or more, with 250 V DC megger between all supply terminals connected together and enclosure
Vibration resistance 10 to 500 Hz frequency, 1.5 mm 0.059 in double amplitude (10 G max.) in X, Y and Z directions for two hours each
Shock resistance 500 m/s2 acceleration (50 G approx.) in X, Y and Z directions three times each
Emitting element Infrared LED (modulated)
Emitting element:Peak emission wavelength 890 nm 0.035 mil
Material Enclosure: Die-cast zinc alloy
Indicator cover: Polyethersulphone
Lens: Polycarbonate
Cable 0.15 mm2 2-core oil, heat and cold resistant cabtyre cable, 5 m 16.404 ft long
Cable extension -
(Note) When extending the cable, the residual voltage will be increased depending on the type of cable used. Verify the residual voltage when extending the cable.
Accessory MS-RX-1 (Sensor mounting bracket): 1 set
Adjusting screwdriver: 1 pc

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region



Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)