Business > Industrial Devices > Automation Controls Top > Components & Devices > Relays / Couplers > Power Relays (Over 2A) > Power Relays (Over 2A) Lineup > HE-R Relays > Rating/Performance
|
Rated coil voltage | Operate voltage*1 (at 20°C) |
Release voltage*1 (at 20°C) |
Rated operating current (±10%, at 20°C) |
Coil resistance (±10%, at 20°C) |
Rated operating power | Max. allowable voltage (at 55°C) |
---|---|---|---|---|---|---|
12 V DC | Max. 75 % V of rated coil voltage (Initial) |
Min. 5 % V of rated coil voltage (Initial) |
333 mA | 36.0 Ω | 4,000 mW Holding*2: 490 mW*3 |
110 % V of rated coil voltage |
24 V DC | 167 mA | 144.0 Ω |
*1 | Square, pulse drive |
---|---|
*2 | When using with the holding voltage, switch to the holding voltage after 200 ms from the application of the coil rated voltage. |
*3 | With 35% V coil holding voltage |
Item | Specifications | |||||||||
---|---|---|---|---|---|---|---|---|---|---|
Contact data | Contact arrangement | 2 Form A (2a), 2 Form A 1 Form B (2a1b) |
4 Form A (4a), 4 Form A 1 Form B (4a1b) |
|||||||
Form A contact |
Contact resistance (initial) | Max. 10 mΩ (by voltage drop 20 A 6 V DC, after 3 min.) Max. 3 mΩ (by voltage drop 80 A 6 V DC, reference value) |
Max. 10 mΩ (by voltage drop 20 A 6 V DC after 3 min.) Max. 3 mΩ (by voltage drop 50 A 6 V DC, reference value) |
|||||||
Contact material | AgNi type | AgSnO2 type | Contact rating (resistive) | 80 A 277 V AC | 40 A 480 V AC | |||||
Max. switching power (resistive) |
22,160 VA | 19,200 VA | ||||||||
Max. switching voltage | 277 V AC | 480 V AC | ||||||||
Max. switching current | 80 A | 50 A | ||||||||
Min. switching load (reference value)*1 |
100 mA 24 V DC | |||||||||
Form B contact (4a1b type only) |
Contact resistance (initial) | Max. 100 mΩ (by voltage drop 1 A 6 V DC) | ||||||||
Contact material | Au plated AgNi type | Contact rating (resistive) | 0.5 A 30 V DC, 1 A 277 V AC | |||||||
Max. switching power (resistive) |
15 W, 277 VA | |||||||||
Max. switching voltage | 30 V DC, 277 V AC | |||||||||
Max. switching current | 1 A | |||||||||
Min. switching load (reference value)*1 |
10 mA 5 V DC | |||||||||
Insulation resistance (initial) | Min. 1,000 MΩ (at 500 V DC, Measured portion is the same as the case of dielectric strength) |
|||||||||
Dielectric strength (initial) |
Between open Form A contacts | 2,000 Vrms for 1 min (detection current: 10 mA) | ||||||||
Between Form A contact and coil | 5,000 V rms for 1 min (detection current: 10 mA) | |||||||||
Between Form A contact sets | 5,000 V rms for 1 min (detection current: 10 mA) | |||||||||
Between open Form B contacts | 1,000 V rms for 1 min (detection current: 10 mA) | |||||||||
Between Form B contact and coil | 2,000 V rms for 1 min (detection current: 10 mA) | |||||||||
Between Form A contact and Form B contact | 5,000 V rms for 1 min (detection current: 10 mA) | |||||||||
Surge withstand voltage (initial)*2 |
Between Form A contact and coil | 10,000 V | ||||||||
Between Form B contact and coil | 2,500 V | |||||||||
Coil holding voltage*3 | 35 to 110% V (at -40 to +55°C, Form A contact: 80 A) 35 to 50% V (at -40 to +85°C, Form A contact: 70 A to 80 A) |
35 to 110% V (at -40 to +55°C, Form A contact: 50 A) 35 to 50% V (at -40 to +85°C, Form A contact: 40 A to 50 A) |
||||||||
Time characteristics (initial) |
Operate time | Max. 50 ms (at rated coil voltage, at 20°C, without bounce) | ||||||||
Release time*4 | Max. 30 ms (at rated coil voltage, at 20°C, without bounce, without diode) | |||||||||
Shock resistance |
Functional | 25 m/s2 (half-sine shock pulse: 11 ms, detection time: 10 μs) | ||||||||
Destructive | 980 m/s2 (half-sine shock pulse: 6 ms) | |||||||||
Vibration resistance |
Functional | 10 to 55 Hz (at double amplitude of 0.3 mm, detection time: 10 μs) | ||||||||
Destructive | 10 to 55 Hz (at double amplitude of 1.5 mm) | |||||||||
Expected life | Mechanical life | Min. 100 x 103 ope. (switching frequency: at 180 times/min) | ||||||||
Conditions | Conditions for usage, transport and storage |
|
||||||||
Unit weight | Approx. 180 g |
*1 | This value can change due to the switching frequency, environmental conditions, and desired reliability level, therefore it is recommended to check this with the actual load. |
---|---|
*2 | Wave is standard shock voltage of ±1.2 x 50 µs according to JEC-212-1981 |
*3 | Coil holding voltage is the coil voltage after 200 ms from the applied rated coil voltage. |
*4 | Release time will lengthen if a diode, etc., is connected in parallel to the coil. Be sure to verify operation under actual conditions. |
Conditions: Resistive load, Switching frequency: ON: OFF = 1 s: 9 s
Type | Switching capacity | Number of operations | |
---|---|---|---|
2 Form A/ 2 Form A 1 Form B |
Form A contact | 63 A 277 V AC | Min. 50 x 103 ope. |
70 A 277 V AC | Min. 30 x 103 ope. | ||
80 A 277 V AC | Min. 10 x 103 ope. | ||
Form B contact (2 Form A 1 Form B type only) |
0.5 A 30 V DC | Min. 100 x 103 ope. | |
1 A 277 V AC | Min. 100 x 103 ope. | ||
4 Form A/ 4 Form A 1 Form B |
Form A contact | 32 A 277 V AC | Min. 50 x 103 ope. |
40 A 480 V AC | Min. 30 x 103 ope. | ||
Form B contact (4 Form A 1 Form B type only) |
0.5 A 30 V DC | Min. 100 x 103 ope. | |
1 A 277 V AC | Min. 100 x 103 ope. |
Item | Characteristics |
---|---|
Clearance/Creepage distance | Min. 8.0/8.0 mm (Form A contact) |
Category of protection | RT Ⅱ |
Tracking resistance | PTⅠ 175 |
Insulation material group | Ⅲ a |
Over voltage category | Ⅲ |
Rated voltage | 250 V |
Pollution degree | 3 |
Type of insulation (Between contact and coil) | Reinforced insulation (Form A contact) |
Type of insulation (Between open contacts) | Full disconnection (Form A contact) |
|
Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)