AUTOMATION
CONTROLS

Search
Discontinued
Products



HE-R Relays

Coil data

  • Operating characteristics such as 'Operate voltage' and 'Release voltage' are influenced by mounting conditions,
    ambient temperature, etc.
    Therefore, please use the relay within ±5% of rated coil voltage.
  • 'Initial' means the condition of products at the time of delivery.
Rated coil voltage Operate voltage*1
(at 20°C)
Release voltage*1
(at 20°C)
Rated operating
current
(±10%, at 20°C)
Coil resistance
(±10%, at 20°C)
Rated operating power Max. allowable voltage
(at 55°C)
12 V DC Max. 75 % V of
rated coil voltage
(Initial)
Min. 5 % V of
rated coil voltage
(Initial)
333 mA 36.0 Ω 4,000 mW
Holding*2:
490 mW*3
110 % V of
rated coil
voltage
24 V DC 167 mA 144.0 Ω
*1Square, pulse drive
*2When using with the holding voltage, switch to the holding voltage after 200 ms from the application of the coil rated voltage.
*3With 35% V coil holding voltage

Return to top

Specifications

Item Specifications
Contact data Contact arrangement 2 Form A (2a),
2 Form A 1 Form B (2a1b)
4 Form A (4a),
4 Form A 1 Form B (4a1b)
Form A
contact
Contact resistance (initial) Max. 10 mΩ
(by voltage drop 20 A 6 V DC, after 3 min.)
Max. 3 mΩ
(by voltage drop 80 A 6 V DC, reference value)
Max. 10 mΩ
(by voltage drop 20 A 6 V DC after 3 min.)
Max. 3 mΩ
(by voltage drop 50 A 6 V DC, reference value)
Contact material AgNi type AgSnO2 type
Contact rating (resistive) 80 A 277 V AC 40 A 480 V AC
Max. switching power
(resistive)
22,160 VA 19,200 VA
Max. switching voltage 277 V AC 480 V AC
Max. switching current 80 A 50 A
Min. switching load
(reference value)*1
100 mA 24 V DC
Form B
contact
(4a1b type only)
Contact resistance (initial) Max. 100 mΩ (by voltage drop 1 A 6 V DC)
Contact material Au plated AgNi type
Contact rating (resistive) 0.5 A 30 V DC, 1 A 277 V AC
Max. switching power
(resistive)
15 W, 277 VA
Max. switching voltage 30 V DC, 277 V AC
Max. switching current 1 A
Min. switching load
(reference value)*1
10 mA 5 V DC
Insulation resistance (initial) Min. 1,000 MΩ
(at 500 V DC, Measured portion is the same as the case of dielectric strength)
Dielectric
strength
(initial)
Between open Form A contacts 2,000 Vrms for 1 min (detection current: 10 mA)
Between Form A contact and coil 5,000 V rms for 1 min (detection current: 10 mA)
Between Form A contact sets 5,000 V rms for 1 min (detection current: 10 mA)
Between open Form B contacts 1,000 V rms for 1 min (detection current: 10 mA)
Between Form B contact and coil 2,000 V rms for 1 min (detection current: 10 mA)
Between Form A contact and Form B contact 5,000 V rms for 1 min (detection current: 10 mA)
Surge
withstand
voltage
(initial)*2
Between Form A contact and coil 10,000 V
Between Form B contact and coil 2,500 V
Coil holding voltage*3 35 to 110% V
(at -40 to +55°C, Form A contact: 80 A)
35 to 50% V
(at -40 to +85°C, Form A contact: 70 A to 80 A)
35 to 110% V
(at -40 to +55°C, Form A contact: 50 A)
35 to 50% V
(at -40 to +85°C, Form A contact: 40 A to 50 A)
Time
characteristics
(initial)
Operate time Max. 50 ms (at rated coil voltage, at 20°C, without bounce)
Release time*4 Max. 30 ms (at rated coil voltage, at 20°C, without bounce, without diode)
Shock
resistance
Functional 25 m/s2 (half-sine shock pulse: 11 ms, detection time: 10 μs)
Destructive 980 m/s2 (half-sine shock pulse: 6 ms)
Vibration
resistance
Functional 10 to 55 Hz (at double amplitude of 0.3 mm, detection time: 10 μs)
Destructive 10 to 55 Hz (at double amplitude of 1.5 mm)
Expected life Mechanical life Min. 100 x 103 ope. (switching frequency: at 180 times/min)
Conditions Conditions for usage,
transport and storage
Ambient temperature: -40 to +55°C
(When applied coil hold voltage is 35 to 110% V of rated coil voltage)
-40 to +85°C
(When applied coil hold voltage is 35 to 50% V of rated coil voltage or storage)
Humidity: 5 to 85% RH (Avoid icing and condensation)
Unit weight Approx. 180 g
*1This value can change due to the switching frequency, environmental conditions, and desired reliability level, therefore it is recommended to check this with the actual load.
*2Wave is standard shock voltage of ±1.2 x 50 µs according to JEC-212-1981
*3Coil holding voltage is the coil voltage after 200 ms from the applied rated coil voltage.
*4Release time will lengthen if a diode, etc., is connected in parallel to the coil. Be sure to verify operation under actual conditions.

Return to top

Expected electrical life

Conditions: Resistive load, Switching frequency: ON: OFF = 1 s: 9 s

Type Switching capacity Number of operations
2 Form A/
2 Form A 1 Form B
Form A contact 63 A 277 V AC Min. 50 x 103 ope.
70 A 277 V AC Min. 30 x 103 ope.
80 A 277 V AC Min. 10 x 103 ope.
Form B contact
(2 Form A 1 Form B type only)
0.5 A 30 V DC Min. 100 x 103 ope.
1 A 277 V AC Min. 100 x 103 ope.
4 Form A/
4 Form A 1 Form B
Form A contact 32 A 277 V AC Min. 50 x 103 ope.
40 A 480 V AC Min. 30 x 103 ope.
Form B contact
(4 Form A 1 Form B type only)
0.5 A 30 V DC Min. 100 x 103 ope.
1 A 277 V AC Min. 100 x 103 ope.

Return to top

INSULATION CHARACTERISTICS (IEC61810-1)

Item Characteristics
Clearance/Creepage distance Min. 8.0/8.0 mm (Form A contact)
Category of protection RT Ⅱ
Tracking resistance PTⅠ 175
Insulation material group Ⅲ a
Over voltage category
Rated voltage 250 V
Pollution degree 3
Type of insulation (Between contact and coil) Reinforced insulation (Form A contact)
Type of insulation (Between open contacts) Full disconnection (Form A contact)

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region







BY PHONE

Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)