AUTOMATION
CONTROLS

Search
Discontinued
Products



HE Relays

Coil data

  • Operating characteristics such as 'Operate voltage' and 'Release voltage' are influenced by mounting conditions, ambient temperature, etc.
    Therefore, please use the relay within ±5% of rated coil voltage.
  • 'Initial' means the condition of products at the time of delivery.

1.AC type

Rated coil voltage Operate voltage *
(at 20°C)
Release voltage *
(at 20°C)
Rated operating current
(±10%, at 20°C)
Rated operating power Max. allowable voltage
(at 20°C)
12 V AC Max. 70% V of
rated coil voltage
(Initial)
Min. 15% V of
rated coil voltage
(Initial)
138 mA 1.7 VA 110% V of
rated coil voltage
24 V AC 74 mA 1.8 VA
48 V AC 39 mA 1.9 VA
100/120 V AC Max. 70 V AC
(Initial)
Min. 18 V AC
(Initial)
18.7 to 22.1 mA 1.9 to 2.7 VA
200/240 V AC Max. 140 V AC
(Initial)
Min. 36 V AC
(Initial)
9.1 to 10.8 mA 1.8 to 2.6 VA
*Square, pulse drive

2.DC type

Rated coil voltage Operate voltage *
(at 20°C)
Release voltage *
(at 20°C)
Rated operating current
(±10%, at 20°C)
Coil
resistance
(±10%, at 20°C)
Rated operating power Max. allowable voltage
(at 55°C)
6 V DC Max. 70% V of
rated coil voltage
(Initial)
Min. 10% V of
rated coil voltage
(Initial)
320 mA 18.8 Ω 1,920 mW 110% V of
rated coil voltage
12 V DC 160 mA 75 Ω
24 V DC 80 mA 300 Ω
48 V DC 40 mA 1,200 Ω
100 V DC 19 mA 5,200 Ω
110 V DC 18 mA 6,300 Ω
*Square, pulse drive

Return to top

Specifications

Item Specifications
Contact data Contact arrangement 1 Form A 2 Form A
Contact resistance
(Initial)
Max. 100 mΩ (by voltage drop 6 V DC 1 A)
Contact material AgSnO2 type
Contact rating
(resistive)
30 A 277 V AC 25 A 277 V AC
Max. switching power
(resistive)
8,310 VA 6,925 VA
Max. switching voltage 277 V AC, 30 V DC
Max. switching current 30 A (AC) 25 A (AC)
Min. switching load
(reference value) *1
100 mA 5 V DC
Insulation resistance (Initial) Min. 1,000 MΩ (at 500 V DC, Measured portion is the same as the case of dielectric strength.)
Dielectric
strength
(initial)
Between
open contacts
2,000 Vrms for 1 min (detection current: 10 mA)
Between
contact sets
- 4,000 Vrms for 1 min (detection current: 10 mA)
Between
contact and coil
5,000 Vrms for 1 min (detection current: 10 mA.)
Surge withstand
voltage (initial) *2
Between
contact and coil
10,000 V
Time
characteristics
(initial)
Operate time Max. 30 ms at rated coil voltage (at 20°C, without bounce)
Release time DC: Max. 10 ms at rated coil voltage
(at 20°C, without bounce, without diode)
AC: Max. 30 ms at rated coil voltage
(at 20°C, without bounce)
Shock
resistance
Functional 98 m/s2 (half-sine shock pulse: 11 ms, detection time: 10 μs)
Destructive 980 m/s2 (half-sine shock pulse: 6 ms)
Vibration
resistance
Functional 10 to 55 Hz (at double amplitude of 1 mm, detection time: 10 μs)
Destructive 10 to 55 Hz (at double amplitude of 1.5 mm)
Expected life Mechanical life DC: Min. 10 x 106 ope. (switching frequency: at 180 times/min)
AC: Min. 5 x 106 ope. (switching frequency: at 180 times/min)
Conditions Conditions for usage,
transport and storage *3
Temperature: -50 to +55°C,
Humidity: 5 to 85% RH
(Avoid icing and condensation)
Unit weight PC board type: Approx. 80 g
Plug-in terminal and TM type: Approx. 90 g
Screw terminal: Approx. 120 g
*1This value can change due to the switching frequency, environmental conditions, and desired reliability level, therefore it is recommended to check this with the actual load.
*2Wave is standard shock voltage of ±1.2 x 50 µs according to JEC-212-1981
*3For ambient temperature, please read "Relays Cautions for Use"

Return to top

Expected electrical life

Conditions: Resistive load, switching frequency at 20 times/min

Type Switching capacity Number of operations
1 Form A 30 A 250 V AC Min. 200 x 103 ope.
2 Form A 20 A 250 V AC Min. 200 x 103 ope.
25 A 277 V AC Min. 100 x 103 ope.

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region