AUTOMATION
CONTROLS

Search
Discontinued
Products



PA-N Relays

Coil data

  • Operating characteristics such as ‘Operate voltage’ and ‘Release voltage’ are influenced by mounting conditions, ambient temperature, etc.
    Therefore, please use the relay within ± 5% of rated coil voltage.
  • ‘Initial’ means the condition of products at the time of delivery.
Rated coil
voltage
Operate voltage*
(at 20°C)
Release voltage*
(at 20°C)
Rated operating
current
(±10%, at 20°C)
Coil resistance
(±10%, at 20°C)
Rated operating
power
Max. allowable
voltage
(at 20°C)
3 V DC Max. 70% V of
rated coil voltage
(Initial)
Min. 5% V of
rated coil voltage
(Initial)
36.7 mA 82 Ω 110 mW 120% V of
rated voltage
4.5V DC 24.4 mA 184 Ω
5 V DC 22 mA 227 Ω
6 V DC 18.3 mA 327 Ω
9 V DC 12.2 mA 736 Ω
12 V DC 9.2 mA 1,309 Ω
18 V DC 6.1 mA 2,945 Ω
24 V DC 4.6 mA 5,236 Ω
*square, pulse drive

Return to top

Specifications

Item Specifications
Contact data Contact arrangement 1 Form A (Bifurcated)
Contact resistance
(initial)
Max. 30 mΩ (by voltage drop 6 V DC 1 A)
Contact material AgNi type + Au
Contact rating
(resistive)
5 A 250 V AC, 5 A 30 V DC
Max. switching power
(resistive)
1,250 VA, 150 W
Max. switching voltage 250 V AC, 110 V DC (0.4 A)
Max. switching current 5 A (AC, DC)
Min. switching load
(reference value) *1
100 µA 100 mV DC
Insulation resistance (initial) Min. 1,000 MΩ
(at 500 V DC, Measured portion is the same as the case of dielectric strength.)
Dielectric
strength
(initial)
Between
open contacts
1,000 Vrms for 1 min (detection current: 10 mA)
Between
contact and coil
3,000 Vrms for 1 min (detection current: 10 mA)
Surge withstand
voltage
(initial) *2
Between
contact and coil
6,000 V
Time
characteristics
(initial)
Operate time Max. 10 ms at rated coil voltage (at 20°C, without bounce)
Release time Max. 5 ms at rated coil voltage (at 20°C, without bounce, without diode)
Shock resistance Functional 147 m/s2 (half-sine shock pulse: 11 ms, detection time: 10 μs)
Destructive 980 m/s2 (half-sine shock pulse: 6 ms)
Vibration
resistance
Functional 10 to 55 Hz (at double amplitude of 2.5 mm, detection time: 10µs)
Destructive 10 to 55 Hz (at double amplitude of 3.5 mm)
Expected life Mechanical life Min. 20 x 106 ope. (switching frequency: at 180 times/min)
Conditions Condition for usage,
transport and storage
*3
Ambient temperature: -40 to +90°C
(-40 to +60°C at our standard packing condition)
Humidity: 5 to 85% RH (Avoid icing and condensation)
Unit weight Approx. 3 g
*1This value can change due to the switching frequency, environmental conditions, and desired reliability level, therefore it is recommended to check this with the actual load.
*2Wave is standard shock voltage of ±1.2 x 50 µs according to JEC-212-1981.
*3For ambient temperature, please read “GUIDELINES FOR RELAY USAGE”.

Return to top

Expected electrical life

Type Load Switching capacity Number of operations
1 Form A Resistive load 3 A 250 V AC Min. 100 x 103 ope.
(Switching frequency at 20 times/min)
3 A 30 V DC Min. 100 x 103 ope.
(Switching frequency at 20 times/min)
5 A 250 V AC Min. 50 x 103 ope.
(Switching frequency at 6 times/min, ON : OFF = 1 s : 9 s)
5 A 30 V AC Min. 50 x 103 ope.
(Switching frequency at 20 times/min)
Inductive load 2 A 250 V AC
(cosφ=0.4)
Min. 100 x 103 ope.
(Switching frequency at 6 times/min, ON : OFF = 1 s : 9 s)

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region







BY PHONE

Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)