Business > Industrial Devices > Automation Controls Top > Components & Devices > Relays / Couplers > Safety Relays > SF Relay Slim type > Rating/Performance
|
Operating characteristics such as "Operate voltage" and "Release voltage" are influenced by mounting conditions or ambient temperature, etc.
Therefore, please use the relay within ±5% of rated coil voltage.
"Initial" means the condition of products at the time of delivery.
Contact arrangement | Rated coil voltage | Operate voltage* (at 20°C) |
Release voltage* (at 20°C) |
Rated operating current [±10%] (at 20°C) |
Coil resistance [±10%] (at 20°C) |
Rated operating power |
Max. allowable voltage (at 20°C) |
|
---|---|---|---|---|---|---|---|---|
4 poles | 2 Form A 2 Form B |
12 V DC | Max. 75% V of rated coil voltage (Initial) | Min. 10% V of rated coil voltage (Initial) | 30 mA | 400 Ω | Approx. 360 mW |
110% V of rated coil voltage |
18 V DC | 20 mA | 900 Ω | ||||||
21 V DC | 17.1 mA | 1,225 Ω | ||||||
24 V DC | 15 mA | 1,600 Ω | ||||||
48 V DC | 7.5 mA | 6,400 Ω | ||||||
3 Form A 1 Form B |
12 V DC | 30 mA | 400 Ω | |||||
18 V DC | 20 mA | 900 Ω | ||||||
21 V DC | 17.1 mA | 1,225 Ω | ||||||
24 V DC | 15 mA | 1,600 Ω | ||||||
48 V DC | 7.5 mA | 6,400 Ω | ||||||
6 poles | 4 Form A 2 Form B |
12 V DC | 41.7 mA | 288 Ω | Approx. 500 mW |
|||
18 V DC | 27.8 mA | 648 Ω | ||||||
21 V DC | 23.8 mA | 882 Ω | ||||||
24 V DC | 20.8 mA | 1,152 Ω | ||||||
48 V DC | 10.4 mA | 4,608 Ω | ||||||
5 Form A 1 Form B |
12 V DC | 41.7 mA | 288 Ω | |||||
18 V DC | 27.8 mA | 648 Ω | ||||||
21 V DC | 23.8 mA | 882 Ω | ||||||
24 V DC | 20.8 mA | 1,152 Ω | ||||||
48 V DC | 10.4 mA | 4,608 Ω | ||||||
3 Form A 3 Form B |
12 V DC | 41.7 mA | 288 Ω | |||||
18 V DC | 27.8 mA | 648 Ω | ||||||
21 V DC | 23.8 mA | 882 Ω | ||||||
24 V DC | 20.8 mA | 1,152 Ω | ||||||
48 V DC | 10.4 mA | 4,608 Ω |
Note) For with LED indication, the rated operating current will increase by approximately 2 mA due to the LED display.
* | square, pulse drive (JIS C 5442) |
---|
Item | Characteristics | |||||
---|---|---|---|---|---|---|
4 poles | 6 poles | |||||
Contact data | Contact arrangement | 2 Form A 2 Form B |
3 Form A 1 Form B |
4 Form A 2 Form B |
5 Form A 1 Form B |
3 Form A 3 Form B |
Contact resistance (initial) | Max. 100 mΩ (by voltage drop 6 V DC 1 A) | |||||
Contact material | Au flashed AgSnO2 type | |||||
Contact rating (resistive) | 6 A 250 V AC, 6 A 30 V DC | |||||
Max. switching power (resistive) | 1,500 VA, 180 W | |||||
Max. switching voltage | 250 V AC, 125 V DC | |||||
Max. switching current | 6 A (Reduce by 0.1 A/°C for temperatures 70 to 85°C) | |||||
Min. switching load (reference value) *1 |
1 mA 5 V DC | |||||
Insulation resistance (initial) | Min. 1,000 MΩ (at 500 V DC, Measured portion is the same as the case of dielectric strength.) | |||||
Dielectric strength (initial) | Between open contacts | 1,500 Vrms for 1 min (detection current: 10 mA) | ||||
Between contact sets | 7-8/9-10 between open contacts 2,500 Vrms for 1 min (detection current: 10 mA) |
7-8/11-12 between open contacts 9-10/13-14 between open contacts 11-12/13-14 between open contacts 2,500 Vrms for 1 min (detection current: 10 mA) |
||||
3-4/5-6 between open contacts 3-4/7-8 between open contacts 5-6/9-10 between open contacts 4,000 Vrms for 1 min (detection current: 10 mA) |
3-4/5-6 between open contacts 3-4/7-8 between open contacts 5-6/9-10 between open contacts 7-8/9-10 between open contacts 4,000 Vrms for 1 min (detection current: 10 mA) |
|||||
Between contact and coil | 4,000 Vrms for 1 min (detection current: 10 mA) | |||||
Time characteristics (initial) | Operate time | Max. 20 ms at rated coil voltage (at 20°C, without bounce) | ||||
Response time*2 | Max. 8 ms at rated coil voltage (at 20°C, without bounce, without diode) *4 | |||||
Release time | Max. 20 ms at rated coil voltage (at 20°C, without bounce) | |||||
Shock resistance | Functional | 200 m/s2 (half-sine shock pulse: 11 ms, detection time: 10 μs) | ||||
Destructive | 1,000 m/s2 (half-sine shock pulse: 6 ms) | |||||
Vibration resistance | Functional | 10 to 55 Hz (at double amplitude of 1.5 mm, detection time: 10 μs) | ||||
Destructive | 10 to 55 Hz (at double amplitude of 1.5 mm) | |||||
Expected life | Mechanical life | Min. 10 x 106 ope. (switching frequency: at 180 times/min) | ||||
Conditions | Conditions for usage, transport and storage*3 | Ambient temperature: -40 to +85°C Humidity: 5 to 85% RH (Avoid icing and condensation) *5 |
||||
Unit weight | Approx. 20 g | Approx. 23 g |
*1 | This value is a rough indication of the lower limit at which switching is possible at micro load level. This value can change due to the switching frequency, environmental conditions, and desired reliability level, therefore it is recommended to check this with the actual load. |
---|---|
*2 | Response time is the time after the coil voltage turns off until the time when form A contact turns off. |
*3 | The upper limit of the ambient temperature is the maximum temperature that can satisfy the coil temperature rise value. Refer to "7.Usage, transport and storage conditions" in SF Relays Cautions For Use. |
*4 | Response time of with diode type is Max. 12 ms (without bounce when rated coil voltage is applied). |
*5 | When the temperature is 70 to 85°C, reduce the max. continuous carrying current by 0.1 A/°C. |
Type | load | Switching capacity | Number of operations |
---|---|---|---|
2 Form A 2 Form B 3 Form A 1 Form B 4 Form A 2 Form B 5 Form A 1 Form B 3 Form A 3 Form B |
Resistive load | 6 A 250 V AC | Min. 100 x 103 ope. (switching frequency at 20 times/min) |
6 A 30 V DC | Min. 100 x 103 ope. (switching frequency at 20 times/min) |
||
1 A 250 V AC | Min. 500 x 103 ope. (switching frequency at 30 times/min) |
||
1 A 30 V DC | Min. 500 x 103 ope. (switching frequency at 30 times/min) |
||
AC 15: inductive load | 2 A 240 V AC | Min. 100 x 103 ope. (switching frequency at 20 times/min, cosΦ = 0.3) |
|
DC 13: inductive load | 1 A 24 V DC | Min. 100 x 103 ope. (switching frequency at 20 times/min, L/R = 48 ms) |
|