Rating/ Performance

Rating And Specifications

Display Specifications
KT7
CE marking directive compliance Low Voltage Directive, EMC Directive, RoHS Directive
Size 22.5×75mm 0.886×2.953 in
Rating Supply voltage (Must be specified) 100 - 240V AC
24V AC/DC
Frequency 50/60Hz
Power consumption Approx. 6VA
Rated scale Input type Input range
Thermocouple K -200 to 1370℃(-320 to 2,500 ℉)
-199.9 to 400.0℃(-199.9 to 750.0 ℉)
J -200 to 1,000℃(-320 to 1,800 ℉)
R 0 to 1,760℃(0 to 3,200 ℉)
S 0 to 1,760℃(0 to 3,200 ℉)
B 0 to 1,820℃(0 to 3,300 ℉)
E -200 to 800℃(-320 to 1,500 ℉)
T -199.9 to 400.0℃(-199.9 to 7,50.0 ℉)
N -200 to 1,300℃(-320 to 2,300 ℉)
PL-II 0 to 1,390℃(0 to 2,500 ℉)
C(W/Re5-26) 0 to 2,315℃(0 to 4,200 ℉)
RTD Pt100 -200 to 850℃(-300 to 1,500 ℉)
-199.9 to 850.0℃(199.9 to 999.9 ℉)
JPt100 -200 to 500℃(-300 to 900 ℉)
-199.9 to 500.0℃(-199.9 to 900.0 ℉)
DC Current 4 to 20mA DC -1,999 to 9,999,
-199.9 to 999.9,
-19.99 to 99.99,
-1.999 to 9.999
0 to 20mA DC
DC Voltage 0 to 1V DC
0 to 10V DC
1 to 5V DC
0 to 5V DC
· Scaling and change to the decimal point position is possible for DC current input and DC voltage input.
· DC current input is supported with an externally connected 50Ω shunt resistor (sold separately).
Sensor input Thermocouple K, J, R, S, B, E, T, N, PL-II, C (W/Re5-26)
External resistor: Max. 100Ω (max. 40Ω external resistor for B input)
RTD Pt100, JPt100 3-conductor system (Allowable input conductor resistance for each conductor: max. 10Ωor less)
DC current 0 to 20 mA DC Input impedance: 50Ω (Connect 50Ω shunt resistor between input terminals.)
Allowable input current: 50 mA or less (When 50Ω shunt resistor is used)
4 to 20 mA DC
DC voltage 0 to 1 V DC Input impedance: min. 1 MΩ, Allowable input voltage: max 5 V, Allowable signal source resistance: max. 2 kΩ
0 to 5 V DC Input impedance: min. 100 kΩ, Allowable input voltage: max 15 V, Allowable signal source resistance: max. 100Ω
1 to 5 V DC
0 to 10 V DC
Control output Relay contact (Must be
specified)
1a
3 A 250 V AC (at resistive load), 1 A 250 V AC (at inductive load cos ø = 0.4), Electrical life: 100,000 times
Non-contact DC voltage 12+20 V DC, Max. load current: 40mA (Short-circuit protected)
DC current 4 to 20mADC Load resistance: Max. 550Ω
Alarm output 1 Open collector, Control capacity: 24V DC 0.1A(Max.)
Alarm output 2 Not available
Control mode PID action (with auto-tuning function), PI action, PD action (with manual reset function), P action (with manual reset function), ON / OFF action
Target temperature setting -
Program control function -
Indication accuracy Thermocouple Within ± (0.2 % + 1 digit) of each input span or within ±2℃ (4℉) whichever is greater However, R or S input; within ±6℃ (12℉) in the range of 0 to 200℃ (32 to 392℉) B input, range of 0 to 300℃ (32 to 572℉): accuracy is not guaranteed K, J, E, T, and N input, less than 0℃ (32℉): within ± (0.4 % ±1 digit) of input span
RTD Within ±(0.1 % + 1 digit) of each input span or ±1℃ (2℉) whichever is greater
DC current and DC voltage Within ±0.2% ±1 digit of each input span
Sampling period 250ms
Hysteresis (ON / OFF) Thermocouple and RTD: 0.1 to 100.0℃ ()
DC current and DC voltage: 1 to 1,000 (The decimal point place follows the selection)
Proportional band For sensor input range and DC current, DC voltage 0.0 to 110.0%
Integral time 0 to 1,000 seconds
Derivative time 0 to 300 seconds
Proportional cycle 1 to 120 seconds
Allowable voltage fluctuation When 100-240 V AC: 85-264 V AC, When 24 V AC/DC: 20-28 V AC/DC
Insulated resistance 500 V DC, Min. 10 MΩ
Breakdown voltage Between input terminal and power terminal
Between output terminal and power terminal
1.5 kV AC for 1 min.
Malfunction vibration 10 to 55 Hz (1 cycle/min.), double amplitude: 0.35 mm 0.014 in (10 min. on 3 axes)
Breakdown vibration 10 to 55 Hz (1 cycle/min.), double amplitude: 0.75 mm 0.030 in (1 hour on 3 axes)
Malfunction shock X, Y and Z each direction for 5 times 98 m/s2
Breakdown shock Same as above, but 294 m/s2
Ambient temperature 0 to +50℃ 32 to +122 ℉
Ambient humidity 35 to 85%RH (No condensation)
Mass 150 g approx.
Waterproof None
Display character height PV: 7.4 mm 0.291in
SV: 7.4 mm 0.291in
(PV / SV switching display)
Option
functions
Heating /
Cooling
control
Relay contact None
Non-contact
voltage
Open collector, Control capacity: 24V DC 0.1A(Max.)
Heater burnout alarm
output
Open collector, Control capacity: 24V DC 0.1A(Max.)
Communication function Please refer below to “Communication Function Overview”.
Accessories Mounting frame / Mounting bracket -
Terminal cover -
Rubber gasket -

Communication Function Overview

Item Specification
Communication method Half-duplex
Communication speed Select 2,400, 4,800, 9,600, or 19,200 bps using key operation.
Synchronization type Asynchronous
Protocol Modbus
Coding ASCII
Error correcting Parity check and check sum
Error detection Parity check, check sum
Data structure Start bit: 1 Data bit: 7 Parity: Even parity Stop bit: 1
Interface EIA RS-485 compliant
No. of nodes 31
Maximum cable length 1,000 m 3,280.840 ft(cable resistance must be within 50Ω

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region







BY PHONE

Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)