Type Item PM4H-W
Rating Rated operating voltage 100 to 240V AC, 12V DC, 24V AC/DC, 48 to 125V
Rated frequency 50/60Hz common (AC operating type)
Rated power consumption Approx. 10VA (100 to 240V AC) Approx. 2.5VA (24V AC) Approx. 2W (12V DC, 24V DC, 48 to 125V DC)
Output rating 5A 250V AC (resistive load)
Operation mode Cyclic (OFF-start/Twin operation)
Time range 1s to 500h 16 time ranges switchable (T1, T2time setting individually)
Time accuracy Note:) Operation time fluctuation ±0.3% (power off time change at the range of 0.1s to 1h)
Setting error ±5% (Max. setting time value)
Voltage error ±0.5% (at the operating voltage changes between 85 to 110%)
Temperature error ±2% (at 20°C ambient temp. at the range of -10 to +50°C/ +14 to +122 °F)
Contact Contact arrangement Timed-out 2 Form C
Contact resistance (Initial value) Max. 100mohm (at 1A 6V DC)
Contact material Silver alloy
Life Mechanical 2×107
Electrical 105(at rated control capacity)
Electrical function Allowable operating voltage range 85 to 110% of rated operating voltage (at 20°C coil temp.)
Insulation resistance (Initial value) Min. 100Mohm Between live and dead metal parts Between input and output Between contacts of different poles Between contacts of same pole (At 500V DC)
Breakdown voltage (Initial value) 2, 000Vrms for 1 min Between live and metal parts 2, 000Vrms for 1 min Between input and output 2, 000Vrms for 1 min Between contacts of different poles 1, 000Vrms for 1 min Between contacts of same pole
Min. power off time 300ms
Max. temperature rise 55°C/ 131 °F
Mechanical function Shock resistance Functional Min. 98m/s2(4 times on 3 axes)
Destructive Min. 980m/s2(5 times on 3 axes)
Vibration resistance Functional 10 to 55Hz: 1 cycle/min double amplitude of 0.5mm (10min on 3 axes)
Destructive 10 to 55Hz: 1 cycle/min double amplitude of 0.75mm (1h on 3 axes)
Operating condition Ambient temperature -10 to +50°C/ +14 to +122 °F
Ambient humidity Max. 85%RH
Atmospheric pressure 860 to 1, 060hPa
Ripple factor (DC type) 20%
Others Protective construction IP65 on front panel (using rubber gasket ATC 18002) (only for IP65 type)
Weight 120g/ 4.233 oz (Pin type), 130g/ 4.586 oz(Screw terminal type)

*1 Unless otherwise specified, the measurement conditions at the maximum scale time standard are specified to be the rated operating voltage (within 5% ripple factor for DC), 20℃/ 68℉ ambient temperature, and 1s power off time.
*2 For the 1s range, the tolerance for each specification becomes ±10ms.

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region







BY PHONE

Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)