Business > Industrial Devices > Automation Controls Top > FA Sensors & Components > Timers / Counters / FA Componets > Timers > PM4H-A/S/M Multi-Range Timers(Discontinued Products) > Rating/ Performance
We are sorry, the products have been discontinued. Please refer to the details of the discontinued products and the recommended substitutes list below.
|
|
Type Item | PM4H-A | PM4H-S | PM4H-M | ||
---|---|---|---|---|---|
Rating | Rated operating voltage | 100 to 240V AC, 48 to 125V DC, 12V DC, 24V AC/DC | |||
Rated frequency | 50/60Hz common (AC operating type) | ||||
Rated power consumption | Approx. 10VA (100 to 240V AC)
Approx. 2.5VA (24V AC) Approx. 2W (12V DC, 24V DC, 48 to 125V DC) |
||||
Output rating | 5A 250V AC (resistive load) | ||||
Operating mode | Pulse ON-delay Pulse Flicker Pulse ON-flicker Differential ON/OFF-delay (1) (2) Signal OFF-delay Pulse One-shot Pulse One-cycle |
Power ON-delay | Power ON-delay Power Flicker Power ON-flicker Power One-shot Power One-cycle (with instantaneous contact) |
||
Time range | 1s to 500h (Max.) 16 time ranges switchable | ||||
Time accuracy Note:) | Operating time fluctuation | ±0.3% (power off time change at the range of 0.1s to 1h) | |||
Setting error | ±5% (Full-scale value) | ||||
Voltage error | ±0.5% (at the operating voltage changes between 85 to 110%) | ||||
Temperature error | ±2% (at 20°C ambient temp. at the range of -10 to +50°C/ +14 to +122°F) | ||||
Contact | Contact arrangement | Timed-out 2 Form C | Timed-out 1 Form C Instantaneous 1 Form C | ||
Contact resistance (Initial value) | Max. 100mΩ (at 1A 6V DC) | ||||
Contact material | Silver alloy | Au flash on Silver alloy | |||
Life | Mechanical (contact) | 2×107 | |||
Electrical (contact) | 105(at rated control capacity) | ||||
Electrical function | Allowable operating voltage range | 85 to 110% of rated operating voltage (at 20°C coil temp.) | |||
Insulation resistance (Initial value) | Min. 100MΩ Between live and dead metal parts Between input and output Between contacts of different poles Between contacts of same pole (At 500V DC) |
||||
Breakdown voltage (Initial value) | 2, 000Vrms for 1 min Between live and dead metal parts 2, 000Vrms for 1 min Between input and output 2, 000Vrms for 1 min Between contacts of different poles 1, 000Vrms for 1 min Between contacts of same pole |
||||
Min. power off time | 100ms | ||||
Max. temperature rise | 55°C/ 131°F | 65°C/ 149° F | |||
Mechanical function | Shock resistance | Functional | Min. 98m/s2(4 times on 3 axes) | ||
Destructive | Min. 980m/s2(5 times on 3 axes) | ||||
Vibration resistance | Functional | 10 to 55Hz: 1 cycle/min double amplitude of 0.5mm (10min on 3 axes) | |||
Destructive | 10 to 55Hz: 1 cycle/min double amplitude of 0.75mm (1h on 3 axes) | ||||
Operating condition | Ambient temperature | -10 to +50°C/ +14 to +122 °F | |||
Ambient humidity | 30 to 85%RH (at 20°C/ 68°F, non-condensing) | ||||
Atmospheric pressure | 860 to 1, 060hPa | ||||
Ripple factor (DC type) | 20% | ||||
Others | Protective construction | IP65 on front panel (using rubber gasket ATC18002) (only for IP65 type) | |||
Weight | 100g/ 3.527oz (Pin type) | ||||
110g/ 3.880oz (Screw terminal type) |
*1 Unless otherwise specified, the measurement conditions at the maximum scale time standard are specified to be the rated operating voltage (within 5% ripple factor for DC), 20℃/ 68℉ ambient temperature, and 1s power off time.
*2 For the 1s range, the tolerance for each specification becomes ±10ms.
|
Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)