Item | Unit | Data display range | |
---|---|---|---|
Integrated electric power (Active)*1 | kWh/MWh | 0.00 to 9999.99 kWh to 9999.99 MWh, 0.00 to 9999999.99 kWh (when 9-digit display) | |
Instantaneous electric power |
Active*2 | kW | −9999.99 to 0.000 to 9999.99 |
Reactive*2 | kvar | −9999.99 to 0.00 to 9999.99 | |
Apparent | kVA | 0.00 to 9999.99 | |
Current | R-current | A | 0.000 to 6000.00 |
N/S-current | A | 0.000 to 6000.00 (calculated value) | |
T-current | A | 0.000 to 6000.00 | |
Voltage | R (RS)-voltage | V | 0.0 to 9999.9 |
S (RT)-voltage | V | 0.0 to 9999.9 (calculated value) | |
T (TS)-voltage | V | 0.0 to 9999.9 | |
Electricity charge*3 | 0.00 to 999999 | ||
Conversion carbon dioxide value |
kg-CO2 | 0.00 to 999999 | |
Power factor*2 | Displayed on the main unit |
−1.00 to 1.00 (without identify leading phase and lagging phase) | |
Frequency | Hz | 47.5 to 63.0 | |
Pulse counter*4 | 0 to 999999 |
*1 | KW2G / KW2G-H can measure regeneration electric power. Integrated electrical power is not integrated (not subtracted) when detecting regeneration electric power. |
---|---|
*2 | While detecting regeneration electric power, minus is displayed on instantaneous active electric power and power factor. |
*3 | Eco-POWER METER is designed chiefly to manage saving energy. It is neither intended nor can it be legally used for billing. |
*4 | Displayed digit of pulse counter differs according to the pre-scale set by pre-scale setting mode. |
Item | Data display range |
---|---|
Pulse counter value* | 0 to 999999 |
* The number of displayed digit of pulse count value differs according to the pre-scale set by pre-scale setting mode.
Item | Data display range |
---|---|
Converted digital value* | −999999 to 9999999 |
* The number of displayed digits of the converted digital values differs according to the preset decimal point position.
Item | Unit | Data display range |
---|---|---|
OFF-time*1 | h(Hour) | 0.0 to 99999.9 |
ON-time1*1 | ||
ON-time2*1 | ||
Maintenance-time*2 | ||
Actual-hours | ||
Rate of ON-time1*1 | % | 0.0 to 100.0 |
Rate of ON-time2*1 |
*1 | Excluding AKW2152G |
---|---|
*2 | Maintenance time by using pulse input cannot be measured with AKW2110GB or AKW2160GB |
*3 | Hour meter function can be used only with main unit and one expansion unit. |
Item | Specifications | |
---|---|---|
Accuracy (without error in CT and VT) |
Instantaneous electric power, Integrated electric power, Electricity charge and Conversion value |
Within ± (2.0 % F.S. + 1 digit) (at +20 ℃ +68 ℉, rated input, rated frequency, power factor 1) *Accuracy coverage: 10 to 100 % of rated current |
Current | Within ± (1.0 % F.S. + 1 digit) (at +20 ℃ +68 ℉, rated input, rated frequency, power factor 1) *Accuracy coverage: 10 to 100 % of rated current |
|
Voltage | Within ± (1.0 % F.S. + 1 digit) (at +20 ℃ +68 ℉, rated input, rated frequency, power factor 1) |
|
Temperature characteristics | Within ± (1.0 % F.S. + 1 digit) (Range of -10 to +50 ℃ +14 to +122℉, rated input, power factor 1) |
|
Hour meter | ±(0.01% +1 digit) Monthly accuracy: ±280 sec. (at +20℃ +68℉) | |
Frequency characteristics | Within ± (1.0 % F.S. + 1 digit) (Frequency change ± 5 % based on rated frequency, rated input, power factor 1) |
Item | Specifications |
---|---|
Rated operating voltage | 100 to 240 V AC (Add to main unit) |
Rated frequency | 50 / 60 Hz common |
Rated power consumption | Main unit: 6 VA, Expansion unit (Power measurement, Power measurement and Pulse output, and Analog input): 0.5 VA / unit, Expansion unit (Pulse input): 1.0 VA /unit (240 V AC at +25 ℃ +77 ℉) |
Allowable operating voltage range | 85 to 264 V AC (85 % to 110 % of rated operating voltage) |
Allowable momentary power-off time | 10 ms |
Ambient temperature | -10 to +50 ℃ +14 to +122 ℉ (-25 to +70 ℃ -13 to +158 ℉ at storage) |
Ambient humidity | 30 to 85 % RH (at +20 ℃ +68 ℉) non-condensing |
Display method | LCD with backlight (green), Upper: 5-digit (7-segment 1-digit + 16-segment 4-digit), Lower: 6-digit (7-segment) |
Number of connectable expansion units | Max. 7 units |
Power failure memory method | EEPROM (more than 1,000,000 overwrite), Memory items: setting value and integral measuring value |
Weight | Main unit (Standard type): 180 g approx. Main unit (SD card type): 185 g approx. Expansion unit (Power measurement): 80 g approx. Expansion unit (Power measurement and Pulse output, Pulse input and Analog input): 85 g approx. |
Item | Specifications | ||
---|---|---|---|
Logging functions | File type 1 (instantaneous value) *1 |
Save cycle |
15 min (00 hr. 00 min 00 sec after the day) (fixed) |
Saved data |
(Instantaneous value) Integrated electric power (1) (2), Instantaneous active electric power (1) (2), Instantaneous reactive electric power (1) (2), Instantaneous apparent electric power (1) (2), R-current (1), R (T)-current (2), S (N)-current, R/RS-voltage (1), R (T/TS)-voltage (2), RT-voltage, Power factor (1) (2), Frequency, Count value, Converted digital value for CH0, Converted digital value for CH1, Pulse count value for CH0 and Pulse count value for CH1 | ||
Saved data amount |
96 records per file (max. approx. 8 days worth of data) | ||
File type 2 (difference value) *1 |
Save cycle |
15 min (00 hr. 00 min 00 sec after the day) (fixed) | |
Saved data |
(Difference value) Integrated electric power (1) (2), Count value, Pulse count value for CH0 and Pulse count value for CH1 | ||
Saved data amount |
96 records per file (max. approx. 8 days worth of data) | ||
File type 3 (instantaneous value detail) *1 |
Save cycle |
Select among 1 min, 5 min, 10 min, 15 min, 30 min, or 60 min (Saved timing) When 1 min is selected: 00 sec after the minute When 10 min is selected: 00, 10, 20, 30, 40, 50 min after the hour When 60 min is selected: 00 min after the hour When 5 min is selected: 00, 05, 10, 15, 20, 25, 30... min after the hour When 15 min is selected: 00, 15, 30, 45 min after the hour |
|
Saved data |
Integrated electric power (1) (2), Instantaneous active electric power (1) (2), Instantaneous reactive electric power (1) (2), Instantaneous apparent electric power (1) (2), R-current (1), R (T)-current (2), S (N)-current, R/RS-voltage (1), R (T/TS)-voltage (2), RT-voltage, Power factor (1) (2), Frequency, Count value, Converted digital value for CH0, Converted digital value for CH1, Pulse count value for CH0 and Pulse count value for CH1 | ||
Saved data amount |
Max. 720 records, 12 hours approx. worth of data (when the save cycle is set to one minute) | ||
Main unit display | Integrated electric power by day (latest data covering 8 days period) / Integrated electric power by hour (latest data covering 12 hours period) | ||
Calendar timer function | Time accuracy Monthly accuracy: ±30 sec (at +25 ℃ +77 ℉) | ||
Content of battery backup | Time measurement and Log data | ||
Battery life*2 | 2 years approx. (at +25 ℃ +77 ℉, in power-off state) |
*1 | Using the setting mode, you can select whether or not to write to the SD memory card for each of file types 1, 2, and 3. Files can be created for each unit. |
---|---|
*2 | When the battery gets low, the BATT display will start flashing. Please replace the battery in accordance with the battery replacing procedure. Also, battery life will be shortened if the main unit is used in a high temperature environment. |
* | While measuring, data is collected in the memory of main unit. If, while measuring, the memory capacity of main unit is reached, data will be overwritten in succession starting from the oldest data. Initialization of the main unit memory is possible. |
Item | Specifications |
---|---|
Support media | SD memory card*1 |
Supported format standards | SD / SDHC standard conformance |
*1 | Please use the SLC type SD memory card. |
---|---|
* | UHS standard SDHC memory cards are not supported. Log data may not be written to the SD memory card if an SD memory card without operational confirmation is used. |
* | The use of UPS (Uninterruptible Power Supply) is recommended because data damage may occur in case of instant power failure during writing. |
* | Refer to the user manual regarding SD memory card handling. |
<Precautions when handling the SD memory card>
Data saved to the SD memory card may be lost in the following cases. Be aware that Panasonic Industrial Devices SUNX Co., Ltd. assumes no responsibility for any loss or direct / indirect damage of registered data.
1) | If the SD memory card is misused by the customer or a third party |
---|---|
2) | If the SD memory card is effected by electrostatic / electronic noise |
3) | If the card is removed or the main unit is turned OFF while the main unit SD memory card access LED is flashing (reading data). |
* It is recommended to save important data to other media and always perform backup.
Item | Specifications | |
---|---|---|
RS-485 communication | USB communication*5 | |
Protocol | MEWTOCOL / Modbus RTU (selectable with setting mode) | - |
Transmission function | - | Computer link (MEWTOCOL) |
Isolation status | Isolated with the internal circuit | Isolated with the internal circuit |
Number of connected units | 99 units Max.*1*2 | - |
Transmission distance | 1200 m 3.937 ft Max.*3 | - |
Transmission speed | 2,400 / 4,800 / 9,600 / 19,200 / 38,400 / 57,600 / 115,200 bps (selectable with setting mode) |
12 Mbps (Full-speed) |
Transmission format | Data length: 8-bit / 7-bit (selectable with setting mode)*4 Parity: Not available / Odd number / Even number (selectable with setting mode) Stop bit: 1-bit / 2-bit (selectable with setting mode) |
- |
Communication method | Half-duplex | - |
Synchronous system | Synchronous communication method | - |
Ending resistance | 120 Ω approx. (built-in) | - |
*1 | For RS-485 converter on the computer side, we recommend SI-35 and SI-35USB (from LINE EYE Co.,Ltd.). |
---|---|
*2 | When using SI-35, SI-35USB or PLC from our company (which can be connected up to 99 units), up to 99 Eco-POWER METER can be connected. In case using this system with the other devices, up to 31 Eco-POWER METER can be connected. |
*3 | Please check with the actual devices when some commercial devices with RS-485 interface are connected. The number of connected devices, transmission distance, and transmission speed may be different according to using transmission line. |
*4 | With Modbus RTU protocol, it works only with 8-bit. |
*5 | When using the USB port, install the dedicated USB driver. |
Item | Specifications | |
---|---|---|
Input mode | Addition (Fixed) | |
Max. counting speed | 50 kHz / 30 Hz (Select with setting mode) | |
Pulse input (Min. input signal width) |
0.01 ms (When 50 kHz selected) / 16.7 ms (When 30 Hz selected), ON : OFF ratio = 1 : 1 |
|
Input signal | Contact / No contact (open collector) • Impedance when shorted: Max. 1 kΩ • Residual voltage when shorted: Max. 2 V • Impedance when open: Min. 100 kΩ |
|
Output mode | HOLD (Over count) | |
Prescale | Decimal point |
Setting possible up to under 3-digit |
Range | 0.001 to 100.000 (Set with setting mode) |
Item | Specifications | |
---|---|---|
Number of input points | 2 channels | |
Input range (Select with setting mode) | Voltage | 0 to 5 V / 1 to 5 V |
Current | 0 to 20 mA / 4 to 20 mA | |
Converted digital value | 0 to 4000 (decimal number)* | |
Resolution | 1/4000 (12 bits) | |
Overall precision | ±1 % F.S. or less (-10 to 55 ℃ +14 to 131 ℉ ) | |
Input impedance | Voltage | 440 kΩ |
Current | 125 Ω | |
Absolute maximum input | Voltage | - 0.3 to +10 V |
Current | - 2 to + 30 mA | |
Input protection | Diode |
* | Digital conversion value differs according to the scaling conversion value set by setting
mode. If the analog input value exceeds the upper or lower limit, the digital value will preserve the upper or lower limit. |
---|
Item | Specifications |
---|---|
Number of output point | 1 point |
Insulation method | Photo coupler |
Output type / Output capacity |
Open collector / 100 mA 30 V DC |
Pulse width*2 (when pulse output with integrated active electric power selected) |
1 to 100 ms (selectable with setting mode) |
ON state voltage drop | 1.5 V or less |
OFF state leakage current | 100 μA or less |
Pulse output unit*1*2*3 | 0.001 kWh, 0.01 kWh, 0.1 kWh, 1 kWh, 10 kWh, 100 kWh / Power alarm(AL-P) / Current alarm(AL-C) / Stand-by power alarm(AL-S) / Counter(Cnt)*3 / General purpose output(OUT) / Error alarm(Error) |
General purpose output | Level output / Repeat cycle output / One-shot output (selectable with setting mode) |
Output ON-time, Output OFF-time |
0.1 to 10.0 sec. (selectable with setting mode) |
*1 | General-purpose output (OUT) and Error alarm (Error) are possible using main unit software AKW2010GB Ver. 1.05 or later and AKW2020GB Ver. 1.02 or later and expansion unit software AKW2160GB Ver.1.01 or later. |
---|---|
*2 | The min. pulse output cycle is 25ms in order to work correctly and output 1 to 10ms pulse output. |
*3 | These count output specifications are only for the main unit and expansion unit AKW2160GB. |
The pulse output unit should be set as that it output 40 pulses or less in 1 second.
[How to calculate]
Unit for pulse output: PL-P > Max. measurement power (kW) / 3,600 sec × 40 pulse/sec
When the pulse output unit is 0.001, the maximum power that can be properly measured by pulse output is 144 kW (3,600 sec × 40 pulse/sec × 0.001).
Note:
(1) Count errors may occur if the pulse output is set to 40 pulses or more per 1 second. |
(2) If the pulse output OFF time is set too short, count errors by connected counters, PLCs (Programmable Logic Controllers) may occur. |
<SD memory card handling precautions>
To format SD memory cards, please download and use the formatting software available on the Panasonic website.
The file system on a SD memory card that was formatted using standard PC software does not comply with the SD memory card standard.
Data saved on an SD memory card may be lost in the following cases. Please note that Panasonic Industrial Devices SUNX is not responsible for any losses of recorded data and other direct and indirect damages.
1) When a customer or a third party incorrectly uses the SD memory card
2) When the SD memory card is affected by static electricity or electrical noise
3) When the SD memory card is taken out or the power is turned off while the SD memory card access LED of the unit is flashing (during data writing)
* It is recommended that you constantly back up important data to another medium.
We recommend using this Eco-POWER METER with inserting SD memory card.
If it is not inserted, log data for 8 days will be saved in the internal memory.
We recommend that move or delete logging data in the folder created by KW2G-H regularly (every 1-month). When inserting SD memory card, delete the logging data in the folder created by KW2G-H.
When you turn off the Eco-POWER METER, remove the SD memory card first. If not, it might damage the Eco-POWER METER and SD memory card.
When you turn on the power again, it may access to SD memory card for 25 minutes according to the log data in the internal memory.
Item | Clamp-on typ | ||||
---|---|---|---|---|---|
AKW4801B AKW4801C |
AKW4802B AKW4802C |
AKW4803B AKW4803C |
AKW4804B AKW4804C |
AKW4808B AKW4808C |
|
CE marking directive compliance | Low Voltage Directive, RoHS Directive | ||||
Primary side rated current | 5A/50A | 100A | 250A | 400A | 600A |
Secondary side rated current | 1.67mA/16.7mA | 33.3mA | 125mA | 200mA | 200mA |
Winding (Turn) | 3000 | 3000 | 2000 | 2000 | 3000 |
Ratio error | ±2.0%F.S. | ||||
Through hole | ø10 ø0.39 | ø16 ø0.63 | ø24 ø0.94 | ø36 ø1.42 | ø36 ø1.42 |
Breakdown voltage (initial) | 1000V AC/1min (Between through hole and output lead wire) |
2000V AC/1min (Between through hole and output lead wire) |
|||
Insulation resistance (initial) | Min. 100 M Ω (at 500 V DC) (Between through hole and output lead wire) | ||||
Functional vibration resistance | 10 to 55 Hz (1 cycle / min), single amplitude: 0.15 mm 0.01 in (10 min on 3 axes) | ||||
Vibration resistance | 10 to 55 Hz (1 cycle / min), single amplitude: 0.375 mm 0.01 in (1 hour on 3 axes) | ||||
Functional shock resistance | Min. 98m/s2(4 times on 3 axes) | ||||
Shock resistance | Min. 294m/s2(5 times on 3 axes) | ||||
Output protection level | ±7.5 V with clamp element | ±3.0V with clamp element | |||
Permissible clamping frequency | 100 times approx. | ||||
Ambient temperature range | -10 to +50℃ +14 to +122 ℉ (without frost and non-condensing) | ||||
Storage temperature | -20 to +60℃ -4 to +140 ℉ (without frost and non-condensing) | ||||
Ambient humidity | 35 to 85%RH(at +20℃ +68 ℉ non-condensing) | ||||
Dimensions (mm in) (W x H x D) |
23 x 40 x 26.5 0.08 x 0.13 x 0.09 |
30 x46.5 x 32 0.10 x 0.15 x 0.11 |
45 x65 x 34 0.15 x 0.21 x 0.11 |
57 x81 x 38 0.19 x 0.27 x 0.12 |
62.6 x93.3 x 40 0.21 x 0.31 x 0.13 |
Weight (Relay cable included) |
60 g approx. | 90 g approx. | 200 g approx. | 295 g approx. | 450 g approx. |
Item | Through type | |||
---|---|---|---|---|
AKW4506B AKW4506C |
AKW4507B AKW4507C |
AKW4508B AKW4508C |
||
CE marking directive compliance | Low Voltage Directive, RoHS Directive | |||
Primary side rated current | 50A/100A | 250A/400A | 600A | |
Secondary side rated current | 16.7mA/33.3mA | 125mA/200mA | 200mA | |
Winding (Turn) | 3000 | 2000 | 3000 | |
Ratio error | ±1.0%F.S. | |||
Through hole | ø17mm ø0.67 in | ø36mm ø1.42 in | ||
Breakdown voltage (initial) | 1000V AC/1min (Between through hole and output lead wire)) |
2000V AC/1min (Between through hole and output lead wire) |
||
Insulation resistance (initial) | Min. 100 MΩ (at 500 V DC megger) (Between through hole and output lead wire) | |||
Functional vibration resistance | 10 to 55 Hz (1 cycle / min), single amplitude: 0.15 mm 0.01 in (10 min on 3 axes) | |||
Vibration resistance | 10 to 55 Hz (1 cycle / min), single amplitude: 0.375 mm 0.01 in (1 hour on 3 axes) | |||
Functional shock resistance | Min. 98 m/s2 (4 times on 3 axes) | |||
Shock resistance | Min. 294 m/s2 (5 times on 3 axes) | |||
Output protection level | ±7.5 V with clamp element | ±3.0 V with clamp element | ||
Permissible clamping frequency | - | |||
Ambient temperature range | –10 to +50 ℃ +14 to +122 ℉ (without frost and non-condensing) | |||
Storage temperature | –20 to +60 ℃ –4 to +140 ℉ (without frost and non-condensing) | |||
Ambient humidity | 35 to 80 % RH (at +20 ℃ +68 ℉non-condensing) | |||
Dimensions (mm in) (W x H x D) |
ø42 x 15 1.65 x 0.05 |
ø70 x19 2.76 x 0.06 |
ø70 x19 2.76 x 0.06 |
|
Weight (Relay cable included) |
70 g approx. | 200 g approx. | 215 g approx. |
Notes :
1) | Dedicated CT are dedicated for low voltage under 440 V AC system. They can not be used for high voltage circuit. |
---|---|
2) | In each type of Eco-POWER METER excluding AKW8115, KW9M and KW2M, a combination of commercially secondary side 5 A CTs and dedicated CTs for 5 A is used for measuring high voltage circuits; For details, confirm with each respective user's manual. |
3) | Since dedicated CTs cannot be used when measuring with AKW8115, KW9M and KW2M, please be careful and do not purchase a dedicated CT by mistake. |
4) | For the AKW8115, KW9M and KW2M, CT with a secondary side current 1 A or 5 A is recommended. Please confirm the specification beforehand. |
5) | Dedicated CT are not included with Eco-POWER METERs. |
6) | Each dedicated CT includes a 1 m 3.281 ft relay cable, respectively. |