Limitation of use (Please read before using FP-X Add-on cassettes)

The version of the control unit to be used for the application cassettes released in July 2007 is specified. Confirm the version you use before using those cassettes.

Application cassettes that the version of the FP-X control unit is specified

FP-X Application cassette Version of control unit
FP-X Analog output cassette AFPX-DA2 Ver. 2.40 or later
FP-X Analog I/O cassette AFPX-A21
FP-X Thermocouple cassette AFPX-TC2

Application cassettes that have restrictions when more than one units are used simultaneously

Current output

FP-X Application cassette Quantity used Control unit
C14 C30 C60
AFPX-DA2 1 A A A
2 - A *1 A *1
AFPX-A21 1 A A A
2 - A A
AFPX-DA2 + AFPX-A21 Each 1 - A *1 A *1
AFPX-DA2 + AFPX-COM5 Each 1 N/A *2 N/A *2 N/A *2
AFPX-A21 + AFPX-COM5 Each 1 N/A *2 N/A *2 N/A *2
AFPX-DA2 + AFPX-A21 + AFPX-COM5 Each 1 - N/A *2 N/A *2
AFPX-DA2 1unit + AFPX-COM5 1unit - N/A *2 N/A *2
AFPX-A21 2units + AFPX-COM5 1unit - N/A *2 N/A *2
*1 Up to 2 channels can be used for the current output. (When using two units, it is possible to use the 2-ch current output and 2-ch voltage output.)
*2The AFPX-DA2 and AFPX-A21 both cannot be used with the AFP-COM5 (Ethernet).

Voltage output: When sing with the output current of 1 mA or below

FP-X Application cassette Quantity used Control unit
C14 C30 C60
AFPX-DA2 1 A A A
2 - A A
AFPX-A21 1 A A A
2 - A A
AFPX-DA2 + AFPX-A21 Each 1 - A A
AFPX-DA2 + AFPX-COM5 Each 1 A A A
AFPX-A21 + AFPX-COM5 Each 1 A A A
AFPX-DA2 + AFPX-A21 + AFPX-COM5 Each 1 - A A
AFPX-DA2 1unit + AFPX-COM5 1unit - A A
AFPX-A21 2units + AFPX-COM5 1unit - A A
* When the output current is in the range of 1 mA to 10 mA, the condition is the same as the condition of the current output.
Limitations on number of simultaneous input/output points differs depending on Add-on cassettes used.
For more details, please refer to the "FP-X User's Manual".
 