Cautions For Use

Limitation of combination

Limitation of combination of units
1.Up to 3 expansion or intelligent units can be connected to each base control unit.
2.There is no restriction on the type and the order in which expansion units are installed.
3. The relay output type and transistor type can be used in conjunction with each other.

Expansion method
No special expansion cables are required as the expansion unit employs a stacking system that uses expansion connectors and lock levers on the unit.

Controllable I/O points when expansion units are added

Type of control unit Control unit only When the expansion unit is the same output type as the control unit When the expansion unit is a transistor output type
C10 10 points Max. 58 points Max. 106 points
C14 14 points Max. 62 points Max. 110 points
C16 16 points Max. 112 points Max. 112 points
C32/T32 32 points Max. 128 points Max. 128 points

Controllable I/O points of S-LINK control unit

When expansion units are added, control of up to 224 points is possible by using the S-LINK section and expansion section in combination.

  • Controllable I/O points of S-LINK section : Max. 128 points
  • Controllable I/O points of expansion section : Max. 96 points

Unit's current consumption table

Type of units Control unit Expansion unit Input circuit Output circuit
The current consumed by the control unit power supply connector. If expansion units or intelligent units are added, the current is increased by the value indicated below. The current consumed by the expansion unit power supply connector. If a unit is not listed below, it means that it has no power supply connector. The current consumed by the input circuits of the various units. The value indicates the current that flows into the input circuit. "n" indicates the number of points that are on. The current consumed by the output circuits of the various units. The value indicates the current used to drive the output circuit. "n" indicates the number of points that are on. The value does not include the load current value.
FP0 control units FP0-C10 100mA or less - 25.8mA or less -
FP0-C14 100mA or less - 34.4mA or less -
FP0-C16 40mA or less - 34.4mA or less 28mA or less
FP0-C32 FP0-T32 60mA or less - 68.8mA or less 52mA or less
S-LINK control units FP0-SL1 150mA or less - - -
FP0 expansion units FP0-E8X 10mA or less - 34.4mA or less -
FP0-E8R 15mA or less 50mA or less 17.2mA or less -
FP0-E8YR 10mA or less 100mA or less - -
FP0-E8YT/P 15mA or less - - 24mA or less
FP0-E16X 20mA or less - 68.8mA or less -
FP0-E16R 20mA or less 100mA or less 34.4mA or less -
FP0-E16T/P 25mA or less - 34.4mA or less 24mA or less
FP0-E16YT/P 25mA or less - - 48mA or less
FP0-E32T/P 40mA or less - 68.8mA or less 48mA or less
FP0 intelligent unit FP0-A21 20mA or less 100mA or less - -
FP0-A80 20mA or less 60mA or less - -
FP0-A04V 20mA or less 100mA or less - -
FP0-A04I 20mA or less 130mA or less - -
FP0-TC4 FP0-TC8 25mA or less - - -
FP0-IOL 30mA or less 40mA or less - -
FP0-CCLS 40mA or less 40mA or less - -

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region







BY PHONE

Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)