【Notification of Manufacturer Change for Panasonic Industrial Devices SUNX Products and Panasonic Industrial Devices SUNX Tatsuno Products】
From April 1, 2024, the terms "Panasonic Industrial Devices SUNX Co., Ltd." and "Panasonic Industrial Devices SUNX Tatsuno Co., Ltd."
in this page and in the manuals and other documents to be downloaded will all be replaced with "Panasonic Industry Co., Ltd." and applied accordingly.

AUTOMATION
CONTROLS

Search
Discontinued
Products



Digital Pressure Sensor [For Gas] DP-0

Cautions For Use

  • Never use this product as a sensing device for personnel protection.
  • In case of using sensing devices for personnel protection, use products which meet laws and standards, such as OSHA, ANSI or IEC etc., for personnel protection applicable in each region or country.
  • This product is used for noncorrosive gas. The product shall not be used for liquid or corrosive gas. Never use fluids having inflammability, toxicity, etc., that affect the human body, either.

Part description

Part description

Piping

  • When using this product, connect a joint available in the market to the pressure port. At the time, the tightening torque should be 1.0 N·m or less.

Mounting

  • Use sensor mounting bracket MS‑DP1‑1 prepared independently. When mounting this product with sensor mounting bracket, etc., the tightening torque should be 0.5 N·m or less.

Mounting
  • Panel mounting bracket MS‑DP1‑8 (optional) and front protection cover MS‑DP1‑3 (optional) are available.
  • For the method for mounting panel mounting bracket, refer to the instruction manual that came with the MS‑DP1‑8.

Wiring

  • Make sure that the power supply is OFF while performing the wiring operation.
  • Verify that the supply voltage variation is within the rating.
  • If power is supplied from a commercial switching regulator, ensure that the frame ground (F.G.) terminal of the power supply is connected to an actual ground.
  • In case noise generating equipment (switching regulator, inverter motor, etc.) is used in the vicinity of this product, connect the frame ground (F.G.) terminal of the equipment to an actual ground.
  • When extending the cable, use a cable whose conductor crosssection area is 0.3 mm2 or more. The cable can be extended to up to 10 m 32.808 ft in total length.
  • Do not run the wires together with high-voltage lines or power lines or put them in the same raceway. This can cause malfunction due to induction.
  • Do not apply stress directly to the connection cable leader or to the connector.

Connection

How to connect

  • Insert the cable with connector CN‑14A(‑R)‑C□ into this product's connection connector section as shown in the right figure.
How to disconnect
  • Pressing the release lever of the cable with connector, pull out the connector.
Note: Do not pull by holding the cable without pressing the release lever, as this can cause cable break or connector break.

Connection

Factory setting

Type Low pressure type High pressure type
Operation setting EASY mode
NO / NC setting NC NO
Threshold value -50.0 0.500
Pressure unit kPa MPa
Display color Red when ON, White when OFF
Response speed 2.5ms

Error indication

Error indication Description Remedy
The load is short-circuited causing an overcurrent to flow. Turn OFF the power and
check the load.
Pressure is applied during zero point adjustment. Applied pressure at the pressure port should be brought to atmospheric pressure and zero-point adjustment should be done again.
The applied pressure exceeds the upper limit of the displayed pressure range. Applied pressure range should be brought within the rated pressure range.
The applied pressure exceeds the lower limit (back pressure) of the displayed pressure range.

When other error massage is displayed, contact us.

Others

  • This product has been developed / produced for industrial use only.
  • The product shall be used only within the rated pressure range.
  • Do not apply pressure exceeding the pressure resistance.
    Otherwise, destruction of diaphragm occurs, preventing the product to perform normal operation.
  • Do not use during the initial transient time (0.5 sec.) after the power supply is switched ON.
  • The specification may not be satisfied in a strong magnetic field.
  • This product is suitable for indoor use only.
  • Take care that strong impact such as fall is not given to this product. Otherwise, it may be destroyed.
  • Avoid dust, dirt, and steam.
  • Take care that the product does not come into contact with organic solvents such as thinner.
  • Take care that the product does not come into contact with oil or grease.
  • Take care that the product does not come into contact with strong acid or alkaline.
  • Do not insert wire into the pressure port. Otherwise, destruction of diaphragm occurs, preventing the product to perform normal operation.

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region







BY PHONE

Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)