Exclusive Control Unit for Safety Light Curtain SF-C10

I/O Circuit and Wiring diagrams

Wiring diagram of SF-C11 and SF4B / SF4B-G series or SF2B series (Control Category 4 or 2)

For PNP output (minus ground)

  • Set the safety light curtain input polarity selection switch to the PNP side and ground the 0 V line.

Wiring diagram of SF-C11 and SF4B / SF4B-G series or SF2B series (Control Category 4 or 2)
Notes: 1) The above diagram is when using manual reset. If automatic reset is used, disconnect the lead from X2 and connect it to X3. In this case, a reset (RESET) button is not needed.
2) Use a momentary-type switch as the reset (RESET) button.
3) Emission halt occurs when the test (TEST) button is open, and emission occurs when the test (TEST) button is short-circuited. If not using the test (TEST) button, short-circuit T1 and T2. However, in case of SF2B series, use a test rod or similar to interrupt the light in order to carry out self-diagnosis separately.

For NPN output (plus ground)

  • In the above diagram, set the safety light curtain input polarity selection switch to the NPN side and ground the + side.

For NPN output (plus ground)
When connecting the SF-C11 to the safety light curtains, make sure to use the 8-core connection cable with a connector. Refer to the SF4B / SF4B-G series and SF2B series pages for details. SFB-CB□, SF2B-CB□, SFB-CCJ10□

Terminal arrangement diagram

SF-C11 Terminal arrangement diagram     
Terminal Function
A1 +24 V DC
A2 0 V
13-14, 23-24, 33-34 Safety output (NO contact × 3)
41-42 Auxiliary output (NC contact × 1)
X1 Reset output terminal
X2 Reset input terminal (Manual)
X3 Reset input terminal (Automatic)
A Not used
B
T1 Test output terminal
T2 Test input terminal
AUX Semiconductor auxiliary output

Pin layout for safety light curtain connectors

SF-C11 Pin layout for light curtain connectors     
Connector pin No. Emitter side connector Receiver side connector
Interlock(Note) OSSD 2
+24 V DC +24 V DC
Emission halt OSSD 1
Auxiliary output EDM (External relay monitor)
Synchronization wire + Synchronization wire +
Synchronization wire – Synchronization wire –
0 V 0 V
Shielded wire Shielded wire

Note: It is not used with the SF2B series.

Wiring diagram of SF-C13 and SF4B / SF4B-G series or SF2B series (Control Category 4 or 2)

For PNP output (minus ground)

  • Connect the safety light curtain control outputs OSSD1 and OSSD2 to S1 and S2 respectively.

Notes: 1) The above diagram is when using manual reset. If automatic reset is used, disconnect the lead from X2 and connect it to X3. In this case, a reset (RESET) button is not needed.
2) Use a momentary-type switch as the reset (RESET) button.
3) This is a test input (pink) for the SF2B series.
4) This is not equipped on the SF2B series.
5) This is a shield for the SF2B series. Output polarity cannot be set.

For NPN output (plus ground)

  • Connect the safety light curtain control outputs OSSD1 and OSSD2 to S4 and S2 respectively and ground the + side.

Notes: 1) The above diagram is when using manual reset. If automatic reset is used, disconnect the lead from X2 and connect it to X3. In this case, a reset (RESET) button is not needed.
2) Use a momentary-type switch as the reset (RESET) button.
3) This is a test input (pink) for the SF2B series.
4) This is not equipped on the SF2B series.
5) This is a shield for the SF2B series. Output polarity cannot be set.
When connecting the SF-C13 to the safety light curtains, make sure to use a discrete wire connection cable. Refer to the SF4B / SF4B-G series and SF2B series pages for details.
SFB-CCB□(-MU), SF2B-CCB□, SFB-CC□(-MU)

Terminal arrangement diagram

SF-C13 Terminal arrangement diagram     
Terminal Function
A1 +24 V DC
A2 0 V
S1 to S4 Safety light curtain control output (OSSD) input terminal
AUX Semiconductor auxiliary output
X1 Reset output terminal
X2 Reset input terminal (Manual)
X3 Reset input terminal (Automatic)
13-14, 23-24, 33-34 Safety output (NO contact × 3)
41-42 Auxiliary output (NC contact × 1)

Use a separate terminal block to carry out wiring for safety light curtains that cannot be connected to the SF-C13.

Discontinued products

For PNP output (minus ground)
Wiring diagram of SF-C12 and SF4B series (Control category 4)

  • Set the two safety light curtain input polarity selection switches to the PNP side and connect the F.G. terminal to the 0 V line.

Note: The above diagram is when using manual reset. If automatic reset is used, connect a normal close-type pushbutton switch between T1 and T2 and leave between X1 and X2 open.

For NPN output (plus ground)

  • In the above diagram, set the two safety light curtain input polarity selection switches to the NPN side and connect the F.G. terminal to the + side.

When connecting the SF-C12 to the safety light curtains, make sure to use the 12-core connection cable with a connector.
Refer to the SF4B / SF4B-G series pages for details.
SFB-CB05-MU (Cable length: 0.5 m 1.640 ft)
SFB-CCJ10E-MU (Extension cable for emitter, cable length: 10 m 32.808 ft)
SFB-CCJ10D-MU (Extension cable for receiver, cable length: 10 m 32.808 ft)

Terminal arrangement diagram

Terminal Function
FG Frame ground (F.G.) terminal
A2 0 V
A1 +24 V DC
13-14, 23-24 Safety output (NO contact × 2)
31-32 Auxiliary output (NC contact × 1)
FB4 External relay monitor terminal 2
FB3
FB2 External relay monitor terminal 1
FB1
   
Terminal Function
R+ Interference prevention wire – (Receiver side)
R– Interference prevention wire + (Receiver side)
E+ Interference prevention wire – (Emitter side)
E– Interference prevention wire + (Emitter side)
T2 Emission halt input terminal
T1
X2 Automatic reset / manual reset selection terminal
Manual reset: X1 – X2 short-circuited
X1

Pin layout for safety light curtain connectors

SF-C12 Pin layout for light curtain connectors
Note: Input and output for pin Nos.
⑪ and ⑫ are not used by this product.
    
Connector pin No. Emitter side connector Receiver side connector
Interlock OSSD 2
+24 V DC +24 V DC
Emission halt OSSD 1
Auxiliary output EDM (External relay monitor)
Synchronization wire + Synchronization wire +
Synchronization wire – Synchronization wire –
0 V 0 V
Shielded wire Shielded wire
Interference prevention wire + Interference prevention wire +
Interference prevention wire – Interference prevention wire –
(Override input) (Muting input 1)
(Muting lamp output) (Muting input 2)

Wiring diagram of SF-C14EX(-01) and SF4B / SF4B-G series (Control Category 4)

For PNP output (minus ground)

  • Set the output polarity selection switch to the PNP side and ground the 0 V line.

Notes: 1) The above diagram is when using manual reset. If automatic reset is used, disconnect the lead from X12 and X22, and connect them to X13 and X23 as shown by the dotted lines. In this case, a reset (RESET) button is not needed. Terminals X31 to X32 are for manual reset only.
2) Use a momentary-type switch for the reset (RESET) button.

For NPN output (plus ground)

  • Set the output polarity selection switch to the NPN side and ground the + side of the power supply input.

Notes: 1) The left diagram is when using manual reset. If automatic reset is used, disconnect the lead from X12 and X22, and connect them to X13 and X23 as shown by the dotted lines. In this case, a reset (RESET) button is not needed. Terminals X31 to X32 are for manual reset only.
2) Use a momentary-type switch for the reset (RESET) button.
When connecting the SF-C14EX to the safety light curtains, make sure to use the following connecting cable.
SFB-CB05-EX (Cable length: 0.5 m 1.640 ft)
SFB-CB5-EX (Cable length: 5 m 16.404 ft)
SFB-CB10-EX (Cable length: 10 m 32.808 ft)
If the NO (Normally Open) contact switch is used as a muting sensor,wire it as shown in the figure below.
If the emergency stop switch is not used, short-circuit between the terminals S11 to S12 and S21 to S22 directly.

Terminal arrangement diagram

SF-C14EX(-01) Terminal arrangement diagram     
Terminal Function Terminal Function
14 Safety output 1, Light received
/ Light interrupted output of the safety light curtain
S11 Emergency stop contact input
2 NC input
Between S11 and S12
Between S21 and S22
24 S12
34 Safety output 2, Safety light curtain output including the muting function S21
44 S22
54 Safety output 3 Emergency stop output X11 Safety output 1 reset input
X11 - X12: Manual reset
X11 - X13: Auto-reset
64 X12
S3+ Muting sensor input 1 (PNP output type)
S3+, S3–: Power supply
S3: Sensor output
X13
S3 X21 Safety output 2 reset input
X21 - X22: Manual reset
X21 - X23: Auto-reset
S3– X22
S4+ Muting sensor input 2(NPN output type)
S4+, S4–: Power supply
S4: Sensor output
X23
S4 X31 Safety output 3 reset input
X31 - X32: Manual reset
S4– X32
T1 Test input terminal
Open: Test mode
Short-circuit: Normal operation
AUX1 Auxiliary output 1, Muting output
T2 AUX2 Auxiliary output 2, Override output
O1 Override input terminal
Open: Invalid
Short-circuit: Valid
AUX3 Auxiliary output 3, Blown lamp output
O2 AUX4 Auxiliary output 4, Safety light curtain auxiliary output
L1+ Muting lamp output 1 IE+ Interference prevention terminal, Emitter side +
L1– IE– Interference prevention terminal, Emitter side –
L2+ Muting lamp output 2 IR+ Interference prevention terminal, Receiver side +
L2– IR– Interference prevention terminal, Receiver side –
A1 +24 V DC -
A2 0 V -

Pin layout for light curtain connectors

SF-C14EX(-01) Terminal arrangement diagram Pin layout for light curtain connectors     
Connector pin No. Emitter side connector Receiver side connector
Interference prevention wire + Interference prevention wire +
+24 V DC +24 V DC
Interference prevention wire – Interference prevention wire –
Auxiliary output Not used
Synchronization wire + Synchronization wire +
Synchronization wire – Synchronization wire –
0 V 0 V
Shielded wire Shielded wire

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region







BY PHONE

Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)