Safety Liquid Leak Sensor [Control Category 4 PLe SIL3] SQ4

Cautions For Use

  • This product is a sensor for detecting leak of fluids.
  • When this product is used with safety devices, construct the system such that the device itself.
  • Before using this device, check whether the device performs properly with the functions and capabilities as per the design specifications.
  • Avoid using this device in an explosive atmosphere because this product does not have an explosive-proof protective construction.

Installation

  • There is the detection mount difference by directivity of a liquid leakage. When there are a direction from which a liquid leakage happens, and an inclination, please install the nose-of-cam side (opposite side of a cable) of a sensor towards a top.
  • Use the mounting bracket MS-SQ4-□ (optional) which suits the liquid to detect.
  • Periodical checking of operation is recommended with the liquids which are not dangerous (water, alcohol, etc.).
  • The amount of detection may change with the conditions of the installation surface.
  • Be sure to use the mounting bracket MS-SQ4-□ (optional) when installing this device to avoid human error, etc.
    Reliable detection cannot be guaranteed when this sensor is used alone.

Maintenance

  • Before conduct maintenance, be sure that the system is in safety state.
  • When using chemical liquid, use proper protections such as groves, masks, goggles, helmets etc. When using protections, be sure to read manuals of them and use properly.
  • Dispose or reinstall in different environment, flush with DI water.

Mounting

  • Keep enough space for maintenance when mounting this product.
    Keep enough space for maintenance

Leakage detection condition and variation factor

  • Leak detection part of this product properly detects the leakage in the following condition.
1. Detection range: Area except backward of this product (liquid must enter to the detection range)
2. Material of installation surface: Hard vinyl chloride or Stainless steel
3. Surface condition for installation: Glossy surface (surface roughness: corresponding 0.4 μmRa) and clean surface.
4. Installation surface angle: Horizontal

  • This product may not detect properly liquid in following element.
1. Liquid kind, consistency (surface tension) and air bubble incorporation.
2. Material, roughness, angle, dirtiness and liquid absorption of surface of installed surface of sensor.
3. Wrong selection of dedicated mounting bracket.
  • Check the detecting liquid and the installation condition before use.

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region







BY PHONE

Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)