Safety Liquid Leak Sensor [Control Category 4 PLe SIL3] SQ4

Specifications

Sensors

Type For standard liquid For chemical liquid
Model No. PNP output SQ4-A21-P SQ4-A22-P
NPN output SQ4-A21-N SQ4-A22-N
Sensing object(Note 2) Water (Standard liquid) (Note 3) Sulfuric acid, Hydrochloric acid, Phosphoric acid, Ammonia, Fluorinert™ (Note 4), Galden® (Note 4), Hydrofluoric acid etc. (Note 3)
Supply voltage 12 to 24 V DC ±10 % Ripple P-P 10 % or less
Current consumption 30 mA or less
Utilization category DC-12, DC-13
Detection output
(Leakage detection)
<PNP output type>
PNP open-collector transistor
• Maximum source current: 50 mA
• Applied voltage: Same as the supply voltage (between detection output and +V)
• Residual voltage: 2.5 V or less (at 50 mA source current)

<NPN output type>
NPN open-collector transistor
• Maximum sink current: 50 mA
• Applied voltage: Same as the supply voltage (between detection output and 0 V)
• Residual voltage: 2 V or less (at 50 mA sink current)
  Response time 10 ms or less
Output operation ON when normal condition or initial detection, OFF when detection leakage or wrong installation
Short-circuit protection Incorporated
Detection auxiliary output
(Initial detection)
<PNP output type>
PNP open-collector transistor
• Maximum source current: 50 mA
• Applied voltage: Same as the supply voltage (between detection auxiliary output and +V)
• Residual voltage: 2.5 V or less (at 50 mA source current)

<NPN output type>
NPN open-collector transistor
• Maximum sink current: 50 mA
• Applied voltage: Same as the supply voltage (between detection auxiliary output and 0 V)
• Residual voltage: 2 V or less (at 50 mA sink current)
  Response time 50 ms or less
Output operation ON when normal condition, OFF when initial detection or accidental leakage
Short-circuit protection Incorporated
Protection IP65 / IP67 (IEC)
Ambient temperature -10 to +55 ℃ +14 to +131 (No dew condensation or icing allowed) (Note 5)
Storage: -10 to +55 ℃ +14 to +131
Ambient humidity 35 to 85 % RH, Storage: 35 to 85 % RH
Emitting element Infrared LED (modulated)
Material Enclosure: Polypropylene Enclosure: PFA
Cable 0.18 mm2 4-core PVC cabtyre cable, 2 m 6.562 ft long 0.1 mm2 4-core PFA cabtyre cable, 2 m 6.562 ft long
Weight Net weight: 45 g approx., Gross weight: 110 g approx.

Notes:
1) Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +20 ℃ +68 ℉.
2) Highly viscous liquid may not be stably detected.
3) The agents mentioned above are examples. It may not be detected depending on viscosity the agent.
Before using this device, check the detecting liquid and installation condition.
4) Fluorinert is the world wide trademark of 3M. Galden is the registered trademark of Solvay.
5) Liquid being detected should be also kept within the rated ambient temperature range.

Controller

Model No. SQ4-C11
Applicable
standards
International
standard
ISO 13849-1:2015 (Category 4, PLe), IEC 61508-1 to 7 (SIL3)
Japan JIS B 9705-1 (Category 4), JIS C 0508-1 to 7 (SIL3)
Europe
(Note 2)
EN 55011 Class A, EN 61000-6-2, EN 50178, EN ISO 13849-1:2015 (Category 4, PLe), EN 61508-1 to 7 (SIL3)
North America
(Note 3)
ANSI/UL 508, CAN/CSA C22.2 No.14
South Korea S1-G-1, S2-W-5, KS C IEC 60947-5-2
SEMI Conforming to SEMI-S2-0310a
Power voltage 24 V DC+10-15 % Ripple P-P 10 % or less
Consumption current 200 mA or less
Control output
[OSSD 1(Y1),
OSSD 2(Y2)]
PNP open-collector transistor / NPN open-collector transistor (switch method)

<Selecting PNP output>
• Maximum source current: 200 mA
• Applied voltage: Same as power voltage (between control output to +V)
• Residual voltage: 2.5 V or less (at 200 mA source current)

<Selecting NPN output>
• Maximum sink current: 200 mA
• Applied voltage: Same as power voltage (between control output to 0 V)
• Residual voltage: 2.0 V or less (at 200 mA sink current)
  Response time 20 ms or less (excluding the response time of the sensor)
Operation mode
(Output operation)
ON when normal condition or initial detection, OFF when detection leakage or wrong installation
Protection circuit
(Short-circuit protection)
Incorporated
Utilization category DC-12, DC-13
Sensor monitor output
(AUX1, 2, 3, 4, Non-safety
output)
PNP open-collector transistor / NPN open-collector transistor (switch method)

<Selecting PNP output>
• Maximum source current: 60 mA
• Applied voltage: Same as power voltage(between sensor monitor output to +V)
• Residual voltage: 2.5 V or less (at 60 mA source current)

<Selecting NPN output>
• Maximum sink current: 60 m A
• Applied voltage: Same as power voltage(between sensor monitor output to 0 V)
• Residual voltage: 2.0 V or less (at 60 mA sink current)
  Response time 100 ms or less (excluding the response time of the sensor)
Operation mode
(Output operation)
ON when normal condition, OFF when initial detection or accidental leakage
Protection circuit
(Short-circuit protection)
Incorporated
Utilization category DC-12, DC-13
Lockout output OFF for lockout (Rating: Same as sensor monitor output)
Auxiliary output Negative logic output of control output 1 / 2 (OSSD 1 / 2) (Rating: Same as sensor monitor output)
[Auxiliary output ON when control output 1 / 2 (OSSD 1/2) is OFF]
Functions Interlock / lockout cancel / Test input / External device monitor / Safety input / Control output polarity selection /
Non-safety output polarity selection / Sensor connection number setting
Protection IP20 (IEC) (However, it should be in IP54 protection structure of control panel)
Ambient temperature -10 to +55 ℃ +14 to +131 (No dew condensation or icing allowed), Storage: -20 to +70 ℃ -4 to +158
Ambient humidity 35 to 85 % RH, Storage: 35 to 85 % RH
PFHD When PNP output is selected: 1.89 × 10-9 (when connecting 4 safety liquid leak sensors)
When NPN output is selected: 1.80 × 10-9 (when connecting 4 safety liquid leak sensors)
MTTFD 100 years or more
Material Main unit case: PC+ABS (alloy)
Weight Net weight: 170 g approx., Gross weight: 440 g approx.

Notes:
1) Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +20 ℃ +68 ℉.
PFHD: Probability of dangerous failure per hour, MTTFD: Mean time to dangerous failure (in years)
2) Regarding EU Machinery Directive, a Notified Body, TÜV SÜD, has certified with the type examination certificate.
3) With regards to the standards in the US/Canada, a Notified Body, TÜV SÜD, has certified the CTÜVUS mark.

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region







BY PHONE

Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)