Model No. | SC-LG2-CEF-P | |||
---|---|---|---|---|
Regulatory compliance | CE Marking (EMC Regulations, RoHS Regulations)、UKCA Marking (EMC Regulations, RoHS Regulations) | |||
Supply voltage | 24 V DC+10 -15 %, Ripple P-P 10 % or less | |||
CC-Link IE Field specifications |
Current consumption | 200 mA or less | ||
Communication method | CC-Link IE Field | |||
Remote station type | Intelligent device station | |||
Network number setting | 1 to 239 (decimal) [1 to EF (hex)] (0 and 240 or more: Error) | |||
Cyclic transmission[Maximum number of link points per station] | RX/RY: Maximum 112 points (112 bits) / Maximum 112 points (112 bits) RWr/RWw: Maximum 132 points (132 words) / Maximum 132 points (132 words) |
|||
Transient transmission | For server function only, message size: 2 kbytes (maximum) | |||
Number of ports | 1000BASE-T Ethernet port (RJ45) × 2 | |||
Station number setting | 1 to 120 (decimal)(0 and 121 or more: Error) | |||
Communication speed | 1 Gbps | |||
Communication cable | Category 5e or higher Ethernet cables that satisfy the 1000BASE-T standard (Double shielded twisted pair cable or straight cable)(Note 1) |
|||
Transmission line type | Line type, star type (line/star mixed type also possible), ring type | |||
Maximum distance between stations |
100 m 328.084 ft | |||
Maximum number of stations that can be connected | 121 (1 master station, 120 slave stations) | |||
Maximum number of stages of cascade connection | 20 | |||
IO-Link specifications |
Current consumption | 150 mA or less (excluding the current consumption of connected IO-Link devices) | ||
Allowable passing current | 3 A or less (Note 2) | |||
Communication method | IO-Link V1.0 / V1.1 | |||
Number of ports | e-CON compliant connector port for IO-Link × 8 | |||
Communication speed | COM1 (4.8 kbps), COM2 (38.4 kbps), COM3 (230.4 kbps) Automatically set by IO-Link device |
|||
Current supplied to device (L+, L-) | Maximum 200 mA per port (Note 2) | |||
Digital I/O (C/Q) (Note 2)(Note 3) |
IO-Link mode | Compliance with the IO-Link standard | ||
SIO mode | During input setting | PNP input (Sink current: Max. 15 mA) | ||
During output setting | Push-pull output (Drive capacity: Max.100 mA) | |||
Digital input (DI) (Note 2)(Note 3) |
PNP input (Sink current: Max. 15 mA) | |||
Communication cable | Unshielded | |||
Maximum cable length | 20 m 65.617 ft | |||
IO-Link connector | e-CON compliant connector (4-pin type)(Note 4) | |||
Environmental resistance |
Ambient temperature | -10 to +55 ℃ +14 to +131 ℉ (No dew condensation or icing allowed), Storage: -20 to +70 ℃ -4 to +158 ℉ | ||
Ambient humidity | 35 to 85 % RH, Storage: 35 to 85 % RH | |||
Voltage withstandability | 1,000 V AC for one min. between all supply terminals connected together and enclosure | |||
Insulation resistance | 20 MΩ or more with 250 V DC megger between all supply terminals connected together and enclosure | |||
Vibration resistance | 10 to 150 Hz frequency, 0.75 mm 0.03 in double amplitude (10 to 58 Hz), maximum acceleration 49 m/s2, (58 to 150 Hz) in X, Y, and Z directions for two hours each | |||
Shock resistance | 98 m/s2 (10 G approx.) in X, Y, and Z directions three times each | |||
Grounding method | Power supply connector is equipped with a frame ground (F.G.) RJ45 connector shield: Directly connected to ground terminal Internal circuit: C coupling, Casing: Floating type |
|||
Limit to the number of flash memory save operations | 100,000 (Note 5) | |||
Material | Case: Polycarbonate | |||
Weight | Net weight: 210 g approx., Gross weight: 270 g approx. | |||
Accessory | Power supply connector: 1 pc. |
Notes:
1) | Use a cable recommended by CC-Link Partner Association. |
---|---|
2) | Take care that the total consumption current of connected devices and the unit on
the IO-Link side does not exceed the allowable passing current. Power to devices (L+, L-), digital I/O (C/Q), and digital input (DI) are supplied from IO-Link (+V, -V) on the power supply connector. |
3) | Operation settings for digital I/O (C/Q) and digital input (DI) must be configured with CC-Link IE Field. If operation settings are not configured, they will not operate. |
4) | For the connectors for connecting devices to this product, purchase simple wire-press connector (e-CON) CN-EP2 (5 pcs. set) or CN-EP3 (5 pcs. set) or the recommended product. |
5) | This product saves settings in internal flash memory. |
Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])