KW2M-X Eco-POWER METER Firmware Detailed Version-Up Information

Version-up Information

Version-Up Information (Ver.1.11 to Ver.1.12) (April 1, 2019 update)

The following points have been upgraded.

[Correct errors]

  • The problem that it doesn't measure TR-voltage (L3-L1) correctly with 1P3W and 3P3W system of Expansion unit (Power measurement), is corrected.

Version-Up Information (Ver.1.10 to Ver.1.11) (May 9, 2018 update)

The following points have been upgraded.

[Correct errors]

  • Improve error in DT register
    The error that when phase and wire system set to "3P3W", the DT register of frequency is "0" is corrected.
    * When it set to other than "3P3W", there is no error.
  • Improve indicator error
    The error that indicator of "OUT1" and "OUT 2" may turn on immediately when the power on, is corrected.
    * Although the indicator may turn on, it doesn't output pulse.
  • Improve error that pulse output setting of main unit was changed when upgrading from Ver.1.01 or less to Ver.1.10 -Main unit's measured target CH of "OUT2" becomes CH1 from CH2. -When main unit's output type is set to "integral power pulse" for "OUT1" and "OUT2", unit for output becomes "0.001kWh". -When main unit's "OUT2" is set to "Under current" or "Over current", the ratio of current used for threshold to judge becomes "0 %".

Version-Up Information (Ver.1.01 to Ver.1.10) (January 9, 2018 update)

The following points have been upgraded.

[Add functions]

  • Support series models
    Expansion unit (Multi analog input), Expansion unit (Digital I/O)
  • Demand totalizing function
  • Select log to save
  • Leakage current measurement (Expansion unit (power measurement))
  • Set power of the expansion unit (power measurement) as a warning threshold with the pulse output function

Version-Up Information (Ver.01.00) (January 2016 update)

The following points have been upgraded.

[Add functions]

  • Power quality log function of KW2M-X for expansion unit (Power meausurement ) added.