AUTOMATION
CONTROLS

Search
Discontinued
Products



Electrostatic Sensor EF-S1

Specifications

Sensor head

Model No. EF-S1HS
Applicable controller EF-S1C
Measurement range
(Measurement range) (Note 2, 3, 4)
8.0 to 20.5 mm 0.315 to 0.807 in (±1 kV range mode)
21.0 to 100 mm 0.827 to 3.937 in (±2 kV range mode)
Power indicator Green LED
Ambient temperature 0 to +40 ℃ +0 to +104 (No dew condensation),
Storage: -20 to +60 ℃ -4 to +140
Ambient humidity 35 to 65 % RH, Storage: 35 to 85 % RH
Vibration resistance 10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude in X, Y and Z directions for two hours each
Shock resistance 98 m/s2 acceleration (10 G approx.) in X, Y and Z directions five times each
Material Enclosure: Heat resistant ABS, Measuring part cover: Stainless steel (SUS304)
Cable 0.09 mm2, 3-core shielded cable, 5 m 16.404 ft long
(with controller connector) (Note 5)
Weight Net weight: 90 g approx., Gross weight: 130 g approx.

Notes:
1) Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +20 ℃ +68 .
2) Set the distance between the sensor head and the sensing object by using the controller before use.
3) The measurement range mode is switched automatically when the measurement range setting is changed at the controller.
4) Measurement areas will vary depending on the measurement distances.
5) Cable cannot be extended.

Controller

Model No. EF-S1C
Applicable sensor head EF-S1HS
Supply voltage 24V DC ± 10%
Current consumption Normal operation: 50 mA or less, ECO mode: 40 mA or less
Display range
(Measurement range) (Note 2)
-1,000 to 1,000 (±1 kV range mode)
-1,999 to 1,999 (±2 kV range mode)
Repeatability ±0.3 % F.S.(Note 3)
Linearity ±0.5 % F.S. (Note 3, 4, 6)
Temperature characteristics 0.05 % F.S./℃ (Note 3, 5)
Judgment outputs
(OUT 1, OUT 2)
NPN open-collector transistor
・Maximum sink current: 100 mA
・Applied voltage: 30 V DC or less (between judgment output and 0 V)
・Residual voltage: 1.5 V or less (at 100 mA sink current)
  Response time 10 ms, 20 ms (STD), 100 ms, 200 ms, 400 ms, 800 ms switching method
Output operation OUT1: +potential measurement output or window comparator output
OUT2: -potential measurement output or error output
Short-circuit protection Incorporated
Analog output (Note 6) Analog voltage
・Output voltage: 1 to 5 V
・Output impedance: 100 Ω approx.
  Response time 20 ms, 30 ms (STD), 110 ms, 210 ms, 410 ms, 810 ms switching method
Timing input / 0-adjust input NPN non-contact input
・Signal condition
High: +V or open,
Low: 0 to +2 V (source current 0.5 mA or less)
・Input impedance: 10 kΩ approx.
Ambient temperature -10 to +55 ℃ +14 to +131 (No dew condensation or icing allowed),
Storage: -20 to +70 ℃ - 4 to +158
Ambient humidity 35 to 85 % RH, Storage: 35 to 85 % RH
Material Enclosure: Heat-resistant ABS, Case cover: Polycarbonate, Mode key: Acrylic, Jog switch: Heat-resistant ABS
Cable 0.2 mm2 6-core cabtyre cable, 2 m 6.562 ft long
Cable extension (Note 7) Extension up to total 10 m 32.808 ft is possible with 0.3 mm2, or more, cable.
Weight Net weight: 65 g approx., Gross weight: 110 g approx.

Notes:
1) Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +20 ℃ +68 .
2) The display range (measurement range) is switched automatically when the measurement distance setting is changed at the controller.
3) F.S. is 2,000 V (-1,000 V to 1,000 V) for the ±1 kV range mode and 4,000 V (-2,000 V to 2,000 V) for the ±2 kV range mode.
4) The values given are for when the measured potential is ±200 V or less in the ±1 kV range mode and ±400 V or less in the ±2 kV range mode. If the measured potentials are outside these values, the values will be equal to the displayed values ±5 %.
5) The values given are for when the measured potential is ±200 V or less in the ±1 kV range mode and ±400 V or less in the ±2 kV range mode. If the measured potentials are outside these values, the values will be 0.5 %/℃ of the displayed values.
6) In order to satisfy the linearity specifications for the analog output, do not use the judgment output.
7) This product is CE compliant and complies with EMC directives. EN 61000-6-2 is the applicable standard that covers immunities relating to use of this product, but in order to comply with this standard, the following conditions must be satisfied.
- The controller must be connected to the power supply at a distance of less than 10 m 32.808 ft.
- Install the ferrite core (accessory) to the cable approximately 30 mm 1.181 in away from the sensor head (EF-S1HS).

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region







BY PHONE

Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)