AUTOMATION
CONTROLS

Search
Discontinued
Products



AHE32X2N | HE Relays PV Type


HE Relays PV Type

*Photo may vary from actual product.

  • RoHS Compliant This product has been confirmed that it does not contain the 6 substances specified in EU RoHS Directive 2011/65/EU and the 4 substances specified in 2015/863/EU.  
  • Download RoHS Compliance Certificate


Product Number HE1aN-P-DC24V-Y5
Part Number AHE32X2N
Details 48 A
Product name HE Relays PV Type
Features Compact size, 1 Form A 35 A/48 A/90 A Power relays for solar inverter

*“ Product Number ” is ordering part number for non Japanese market. “ Part Number ” is ordering part number for Japanese market.


As of April 18, 2024
Specifications and design of the products are subject to change without notice for the product improvement.

Spec Detail

Item Specifications
Product Number HE1aN-P-DC24V-Y5
Part Number AHE32X2N
Protective construction Flux-resistant
Operating function Single side stable
Terminal shape PC board terminal (blade)
Contact rating type 48 A
Contact gap 2.5mm
Packing style Carton
Standard packing
Carton (pieces)
25
Standard packing
Case (pieces)
100

Coil data

Item Specifications
Rated coil voltage 24 V DC
Operate voltage (at20°C) Max. 70% V of rated coil voltage (Initial)
Release voltage (at20°C) Min. 10% V of rated coil voltage (Initial)
Rated operating current [±10%] (at 20°C) 80 mA
Coil resistance [±10%] (at 20°C) 300 Ω
Rated operating power 1,920 mW
Max. allowable voltage (at 20°C) 110% V of rated coil voltage

Specifications

Item Specifications
Contact arrangement 1 Form A
Contact shape Single
Contact resistance (initial) Max. 100 mΩ (by voltage drop 6 V DC 1 A)
Contact material AgNi type
Contact rating (resistive load) 48 A 490 V AC, 48 A 48 V DC
Max. switching power (resistive load) 23,520 VA (AC), 2,304 W (DC)
Max. switching voltage 490 V AC, 48 V DC
Max. switching current 48 A (AC, DC)
Min. switching load (reference value) 100 mA 5 V DC
Insulation resistance (initial) Min. 1,000 MΩ (at 500 V DC, Measured portion is the same as the case of dielectric strength.)
Dielectric strength (initial) : Between open contacts 2,000 Vrms for 1 min (detection current: 10 mA)
Dielectric strength (initial) : Between contact and coil 5,000 Vrms for 1 min (detection current: 10 mA)
Surge withstand voltage (initial) : Between contact and coil 10,000 V
Coil holding voltage 40 to 100% V (at -50~55°C)
50 to 60% V (at 55~85°C)
Operate time (initial) (at 20°C) Max. 30 ms at rated coil voltage (without bounce)
Release time (initial) (at 20°C) Max. 10 ms at rated coil voltage (without bounce, without diode)
Shock resistance (Functional) 98 m/s2 (half-sine shock pulse: 11 ms, detection time: 10 µs)
Shock resistance (Destructive) 980 m/s2 (half-sine shock pulse: 6 ms)
Vibration resistance (Functional) 10 to 55 Hz (at double amplitude of 1 mm, detection time: 10 µs)
Vibration resistance (Destructive) 10 to 55 Hz (at double amplitude of 1.5 mm)
Mechanical life Min. 10x106 ope. (switching frequency: at 180 times/min)
Conditions Ambient temperature: -50 to +85°C
(When using at 55°C or higher, the coil holding voltage should be 50% V to 60% V)
Humidity: 5 to 85% RH (Avoid icing and condensation)
Unit weight Approx. 80 g

Expected electrical life

Item Specifications
Resistive load [at 85°C, switching frequency ON : OFF = 1 s : 9 s]
Min. 30x103 ope. 48 A 277 V AC
Min. 30x103 ope. 48 A 30 V DC

[room temperature, switching frequency ON : OFF = 1 s : 9 s]
Min. 10x103 ope. 48 A 490 V AC
Min. 10x103 ope. 48 A 48 V DC
Inductive load [at 85°C, switching frequency ON : OFF = 0.1 s : 10 s]
Min. 30x103 ope. 48 A 250 V AC (cosΦ = 0.8)
Min. 50 ope. 72 A 250 V AC (cosΦ = 0.8)

Return to top

Information on Compliance with Standards

Standard Name Status Information on Compliance
UL/C-UL

Approval

File No. E43028
Rating 48A 277V AC General use, at 85°C 30,000 cycles
60A 277V AC General use, at 60°C 10,000 cycles
Remarks -
Last update April 11, 2023
CSA

N/A

File No. -
Rating -
Remarks CSA standard certified by C-UL
Last update November 22, 2021
VDE

Approval

File No. 40006681
Rating 48A 250V AC (cosφ=0.8) at 85°C 30,000 cycles
72A 250V AC (cosφ=0.8) at 85°C 50 cycles
60A 250V AC (cosφ=0.8) at 85°C 10,000 cycles
50A 20V DC (0ms) at 85°C 30000 cycles
Remarks -
Last update March 19, 2024
Mark on products* UL C-UL Recognaized VDE HOUSE MARK

* The "Mark on products" field shows the standards' certificate type marked to products. Note that not all certified products have a certificate mark affixed to them.


Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region







BY PHONE

Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)