Business > Industrial Devices > Automation Controls Top > AKW2020GB
*Photo may vary from actual product.
Product Number | AKW2020GB |
Part Number | AKW2020GB |
Product | Eco-POWER METER |
Details | Main unit |
Product name | KW2G-H Eco-Power Meter(Discontinued) |
Item | Specifications |
---|---|
Product Number | AKW2020GB |
Part Number | AKW2020GB |
Item | Specifications |
---|---|
Integrated electric power(Active):kWh/MWh | 0.00 to 9999.99 kWh to 9999.99 MWh, 0.00 to 9999999.99 kWh (when 9-digit display) (Note):measure regeneration electric power. Integrated electrical power is not integrated (not subtracted) when detecting regeneration electric power. |
Power measurement:Instantaneous electric power:Active:kW | -9999.99 to 0.000 to 9999.99 (Note):While detecting regeneration electric power, minus is displayed on instantaneous active electric power and power factor. |
Instantaneous electric power:Reactive:kvar | -9999.99 to 0.00 to 9999.99 (Note):While detecting regeneration electric power, minus is displayed on instantaneous active electric power and power factor. |
Instantaneous electric power:Apparent:kVA | 0.00 to 9999.99 |
Current:R-current:A | 0.000 to 6000.00 |
Current:N/S-current:A | 0.000 to 6000.00 (calculated value) |
Current:T-current:A | 0.000 to 6000.00 |
Voltage:R(RS)-voltage:V | 0.0 to 9999.9 |
Voltage:S(RT)-voltage:V | 0.0 to 9999.9 (calculated value) |
Voltage:T(TS)-voltage:V | 0.0 to 9999.9 |
Electricity charge | 0.00 to 999999 |
Conversion carbon dioxide value:kg-CO2 | 0.00 to 999999 |
Power factor:Displayed on the main unit | -1.00 to 1.00 (without identify leading phase and lagging phase) (Note):While detecting regeneration electric power, minus is displayed on instantaneous active electric power and power factor. |
Frequency:Hz | 47.5 to 63.0 |
Pulse count value | 0 to 999999 (Note):Displayed digit of pulse counter differs according to the pre-scale set by pre-scale setting mode. |
Item | Specifications |
---|---|
OFF-time:Hour | 0 to 99999.9 |
ON-time 1:Hour | 0 to 99999.9 |
ON-time 2:Hour | 0 to 99999.9 |
Maintenance time:Hour | 0 to 99999.9 (Note):Maintenance time by using pulse input cannot be measured |
Actual work time:Hour | 0 to 99999.9 |
Ratio of ON-time 1:% | 0.0 to 100.0 |
Ratio of ON-time 2:% | 0.0 to 100.0 |
Item | Specifications |
---|---|
Accuracy (without error in CT and VT) : Integrated electric power and Instantaneous electric power | Within ± (2.0 % F.S. + 1 digit) (at +20 ℃ +68 ℉, rated input, rated frequency, power factor 1) *Accuracy coverage : 10 to 100 % of rated current |
Accuracy (without error in CT and VT) : Current | Within ± (1.0 % F.S. + 1 digit) (at +20 ℃ +68 ℉, rated input, rated frequency, power factor 1) *Accuracy coverage : 10 to 100 % of rated current |
Accuracy (without error in CT and VT) : Voltage | Within ± (1.0 % F.S. + 1 digit) (at +20 ℃ +68 ℉, rated input, rated frequency, power factor 1) |
Accuracy (without error in CT and VT) : Temperature characteristics | Within ± (1.0 % F.S. + 1 digit) (Range of -10 to +50 ℃ +14 to +122℉, rated input, power factor 1) |
Accuracy (without error in CT and VT) : Hour meter | ±(0.01% +1 digit) Monthly accuracy: ±280 sec. (at +20℃ +68℉) |
Accuracy (without error in CT and VT) : Frequency characteristics | Within ± (1.0 % F.S. + 1 digit) (Frequency change ± 5 % based on rated frequency, rated input, power factor 1) |
Item | Specifications |
---|---|
Rated operating voltage | 100-240V AC (Add to main unit) |
Rated frequency | 50 / 60 Hz common |
Rated power consumption | Main unit : 6 VA, Expansion unit (Power measurement, Power measurement and Pulse output, and Analog input) : 0.5 VA / unit, Expansion unit (Pulse input) : 1.0 VA /unit (240 V AC at +25 ℃ +77 ℉) |
Allowable operating voltage range | 85-264 V AC (85 % to 110 % of rated operating voltage) |
Allowable momentary power-off time | 10 ms |
Ambient temperature | -10 to +50 ℃ +14 to +122 ℉ (-25 to +70 ℃ -13 to +158 ℉ at storage) |
Ambient humidity | 30 to 85 % RH (at +20 ℃ +68 ℉) non-condensing |
Display method | LCD with backlight (green), Upper : 5-digit (7-segment 1-digit + 16-segment 4-digit), Lower : 6-digit (7-segment) |
Number of connectable expansion units | Max. 7 units |
Power failure memory method | EEPROM (more than 1,000,000 overwrite), Memory items : setting value and integral measuring value |
Weight | Main unit (Standard type): 180 g approx. Main unit (SD memory card type): 185 g approx. Expansion unit (Power measurement): 80 g approx. Expansion unit (Power measurement and Pulse output, Pulse input and Analog input): 85 g approx. |
Item | Specifications |
---|---|
Logging functions : File type 1 (instantaneous value) : Save cycle | 15 min (00 hr. 00 min 00 sec after the day)(fixed) (Note): Using the setting mode, you can select whether or not to write to the SD memory card for each of file types 1, 2, and 3. Files can be created for each unit. 'Integrated electric power' is logged with the unit of 0.01kWh.It doesn't log it with the unit of 0.001kWh. |
Logging functions : File type 1 (instantaneous value) : Saved data | (Instantaneous value) Integrated electric power ①②, Instantaneous active electric power ①②, Instantaneous reactive electric power ①②, Instantaneous apparent electric power ①②, R-current ①, R (T)-current ②, S (N)-current, R/RS-voltage ①, R (T/TS)-voltage ②, RT-voltage, Power factor ①②, Frequency, Count value, Converted digital value for CH0, Converted digital value for CH1, Pulse count value for CH0 and Pulse count value for CH1 (Note 1): Using the setting mode, you can select whether or not to write to the SD memory card for each of file types 1, 2, and 3. Files can be created for each unit. 'Integrated electric power' is logged with the unit of 0.01kWh.It doesn't log it with the unit of 0.001kWh. (Note 2): When the battery gets low, the "BATT" display will start flashing. Please replace the battery in accordance with the battery replacing procedure. Also, battery life will be shortened if the main unit is used in a high temperature environment. * While measuring, data is collected in the memory of main unit. If, while measuring, the memory capacity of main unit is reached, data will be overwritten in succession starting from the oldest data. Initialization of the main unit memory is possible. |
Logging functions : File type 1 (instantaneous value) : Saved data amount | 96 records per file (max. approx. 8 days worth of data) (Note): Using the setting mode, you can select whether or not to write to the SD memory card for each of file types 1, 2, and 3. Files can be created for each unit. 'Integrated electric power' is logged with the unit of 0.01kWh.It doesn't log it with the unit of 0.001kWh. |
Logging functions : File type 2 (difference value) : Save cycle | 15 min (00 hr. 00 min 00 sec after the day)(fixed) (Note): Using the setting mode, you can select whether or not to write to the SD memory card for each of file types 1, 2, and 3. Files can be created for each unit. 'Integrated electric power' is logged with the unit of 0.01kWh.It doesn't log it with the unit of 0.001kWh. |
Logging functions : File type 2 (difference value) : Saved data | (Difference value) Integrated electric power (1)(2), Count value, Pulse count value for CH0 and Pulse count value for CH1 (Note 1): Using the setting mode, you can select whether or not to write to the SD memory card for each of file types 1, 2, and 3. Files can be created for each unit. 'Integrated electric power' is logged with the unit of 0.01kWh.It doesn't log it with the unit of 0.001kWh. (Note 2): When the battery gets low, the "BATT" display will start flashing. Please replace the battery in accordance with the battery replacing procedure. Also, battery life will be shortened if the main unit is used in a high temperature environment. * While measuring, data is collected in the memory of main unit. If, while measuring, the memory capacity of main unit is reached, data will be overwritten in succession starting from the oldest data. Initialization of the main unit memory is possible. |
Logging functions : File type 2 (difference value) : Saved data amount | 96 records per file (max. approx. 8 days worth of data) (Note): Using the setting mode, you can select whether or not to write to the SD memory card for each of file types 1, 2, and 3. Files can be created for each unit. 'Integrated electric power' is logged with the unit of 0.01kWh.It doesn't log it with the unit of 0.001kWh. |
Logging functions :File type 3 (instantaneous value detail) : Save cycle | Select among 1 min, 5 min, 10 min, 15 min, 30 min, or 60 min(Saved timing)When 1 min is selected: 00 sec after the minuteWhen 10 min is selected: 00, 10, 20, 30, 40, 50 min after the hourWhen 60 min is selected: 00 min after the hourWhen 5 min is selected: 00, 05, 10, 15, 20, 25, 30... min after the hourWhen 15 min is selected: 00, 15, 30, 45 min after the hour (Note): Using the setting mode, you can select whether or not to write to the SD memory card for each of file types 1, 2, and 3. Files can be created for each unit. 'Integrated electric power' is logged with the unit of 0.01kWh.It doesn't log it with the unit of 0.001kWh. |
Logging functions :File type 3 (instantaneous value detail) : Saved data | Integrated electric power ①②, Instantaneous active electric power ①②, Instantaneous reactive electric power ①②, Instantaneous apparent electric power ①②, R-current ①, R (T)-current ②, S (N)-current, R/RS-voltage ①, R (T/TS)-voltage ②, RT-voltage, Power factor ①②, Frequency, Count value, Converted digital value for CH0, Converted digital value for CH1, Pulse count value for CH0 and Pulse count value for CH1 (Note 1): Using the setting mode, you can select whether or not to write to the SD memory card for each of file types 1, 2, and 3. Files can be created for each unit. 'Integrated electric power' is logged with the unit of 0.01kWh.It doesn't log it with the unit of 0.001kWh. (Note 2): When the battery gets low, the "BATT" display will start flashing. Please replace the battery in accordance with the battery replacing procedure. Also, battery life will be shortened if the main unit is used in a high temperature environment. * While measuring, data is collected in the memory of main unit. If, while measuring, the memory capacity of main unit is reached, data will be overwritten in succession starting from the oldest data. Initialization of the main unit memory is possible. |
Logging functions :File type 3 (instantaneous value detail) : Saved data amount | Max. 720 records, 12 hours approx. worth of data (when the save cycle is set to one minute) (Note): Using the setting mode, you can select whether or not to write to the SD memory card for each of file types 1, 2, and 3. Files can be created for each unit. 'Integrated electric power' is logged with the unit of 0.01kWh.It doesn't log it with the unit of 0.001kWh. |
Logging functions : Main unit display | Integrated electric power by day (latest data covering 8 days period) / Integrated electric power by hour (latest data covering 12 hours period) |
Calendar timer function | Time accuracy Monthly accuracy: ±30 sec (at +25 ℃ +77 ℉) |
Content of battery backup | Time measurement and Log data |
Battery life | 2 years approx. (at +25 ℃ +77 ℉, in power-off state) (Note): When the battery gets low, the "BATT" display will start flashing. Please replace the battery in accordance with the battery replacing procedure. Also, battery life will be shortened if the main unit is used in a high temperature environment. * When the battery gets low, the BATT display will start flashing. Please replace the battery in accordance with the battery replacing procedure. Also, battery life will be shortened if the main unit is used in a high temperature environment. |
Item | Specifications |
---|---|
Support media | SD memory card (Note): Panasonic buisiness-use SD memory card is recommended. |
Supported format standards | SD / SDHC standard conformance |
Remark | * UHS standard SDHC memory cards are not supported. Log data may not be written to the SD memory card if an SD memory card without operational confirmation is used. * The use of UPS (Uninterruptible Power Supply) is recommended because data damage may occur in case of instant power failure during writing. * Refer to the user manual regarding US memory card handling. Data saved to the SD memory card may be lost in the following cases. Be aware that Panasonic Industrial Devices SUNX Co., Ltd. assumes no responsibility for any loss or direct / indirect damage of registered data. 1) If the SD memory card is misused by the customer or a third party 2) If the SD memory card is effected by electrostatic / electronic noise 3) If the card is removed or the main unit is turned OFF while the main unit SD memory card access LED is flashing (reading data). * It is recommended to save important data to other media and always perform backup. |
Item | Specifications |
---|---|
Protocol | MEWTOCOL / Modbus RTU(selectable with setting mode) |
Transmission function | - |
Isolation status | Isolated with the internal circuit |
Number of connected units | 99 units max. (Note 1): For RS-485 converter on the computer side, we recommend SI-35 and SI-35USB (from LINE EYE Co.,Ltd.). (Note 2): When using SI-35, SI-35USB or PLC from our company (which can be connected up to 99 units), up to 99 Eco-POWER METER can be connected. In case using this system with the other devices, up to 31 Eco-POWER METER can be connected. |
Transmission distance | 1200 m 3.937 ft max. (Note): Please check with the actual devices when some commercial devices with RS-485 interface are connected. The number of connected devices, transmission distance, and transmission speed may be different according to using transmission line. |
Transmission speed | 2,400 / 4,800 / 9,600 / 19,200 / 38,400 / 57,600 / 115,200 bps (selectable with setting mode) |
Transmission format | Data length: 8-bit / 7-bit (selectable with setting mode)(Note) Parity: Not available / Odd number / Even number (selectable with setting mode) Stop bit: 1-bit / 2-bit (selectable with setting mode) (Note):With Modbus RTU protocol, it works only with 8-bit. |
Communication method | Half-duplex |
Synchronous system | Synchronous communication method |
Ending resistance | 120 Ω approx. (built-in) |
Item | Specifications |
---|---|
Protocol | - |
Transmission function | Computer link (MEWTOCOL) |
Isolation status | Isolated with the internal circuit |
Number of connected units | - |
Transmission distance | - |
Transmission speed | 12 Mbps (Full-speed) |
Transmission format | - |
Communication method | - |
Synchronous system | - |
Ending resistance | - |
Remark | When using the USB port, install the dedicated USB driver. |
Item | Specifications |
---|---|
Input mode | Addition (Fixed) |
Max. counting speed | 50 kHz / 30 Hz (Select with setting mode) |
Pulse input (Min. input signal width) | 0.01 ms (When 50 kHz selected) / 16.7 ms (When 30 Hz selected), ON : OFF ratio = 1 : 1 |
Input signal | Contact / No contact (open collector) ・Impedance when shorted : Max. 1 kΩ ・Residual voltage when shorted : Max. 2 V ・Impedance when open : Min. 100 kΩ |
Output mode | HOLD (Over count) |
Prescale : Decimal point | Setting possible up to under 3-digit |
Prescale : Range | 0.001 to 100.000 (Set with setting mode) |
Item | Specifications |
---|---|
Number of input points | 2 channels |
Input range (Select with setting mode) : Voltage | 0 to 5 V / 1 to 5 V (selectable with setting mode) |
Input range (Select with setting mode) : Current | 0 to 20 mA / 4 to 20 mA (selectable with setting mode) |
Converted digital value | 0 to 4,000 (decimal number) (Note):Digital conversion value differs according to the scaling conversion value set by setting mode. If the analog input value exceeds the upper or lower limit, the digital value will preserve the upper or lower limit. |
Resolution | 1/4,000 (12 bits) |
Overall precision | ±1 % F.S. or less (-10 to +55℃ +14 to 131℉) |
Input impedance : Voltage | 440 kΩ |
Input impedance : Current | 125 Ω |
Absolute maximum input : Voltage | - 0.3 to +10 V |
Absolute maximum input : Current | - 2 to + 30 mA |
Input protection | Diode |
Item | Specifications |
---|---|
Number of output point | 1 point |
Insulation method | Optical coupler |
Output type / Output capacity | Open collector / 100 mA 30 V DC |
Pulse width (when pulse output with integrated active electric power selected) | 1 to 100 ms (selectable with setting mode) (Note) : The min. pulse output cycle is 25ms in order to work correctly and output 1 to 10ms pulse output. |
ON state voltage drop | 1.5 V or less |
OFF state leakage current | 100 μA or less |
Pulse output unit | 0.001 kWh, 0.01 kWh, 0.1 kWh, 1 kWh, 10 kWh, 100 kWh / Power alarm(AL-P) / Current alarm(AL-C) / Stand-by power alarm(AL-S) / Counter(Cnt)(Note 3) / General purpose output(OUT) / Error alarm(Error) (Note 1) : General-purpose output (OUT) and Error alarm (Error) are possible using main unit software AKW2010GB Ver. 1.05 or later and AKW2020GB Ver. 1.02 or later and expansion unit software AKW2160GB Ver.1.01 or later. (Note 2) : The min. pulse output cycle is 25ms in order to work correctly and output 1 to 10ms pulse output. (Note 3) : These count output specifications are only for the main unit and expansion unit AKW2160GB. |
General purpose output | Level output / Repeat cycle output / One-shot output (Selectable with setting mode) (Note): In order to use the general purpose output, it is necessary to set the output status ON or OFF via communications. In addition it doesn't work with the on-time and off-time set to under 0.1s. |
Output ON-time, Output OFF-time | 0.1 to 10.0s (Selectable with setting mode) |
To Be Discontinued
Product Number | AKW2110GB |
Part Number | AKW2110GB |
Product | Eco-POWER METER |
Details | Expansion unit |
Product name | KW2G Expansion unit |
To Be Discontinued
Product Number | AKW2160GB |
Part Number | AKW2160GB |
Product | Eco-POWER METER |
Details | Expansion unit |
Product name | KW2G Expansion unit |
To Be Discontinued
Product Number | AKW4801B |
Part Number | AKW4801B |
Product name | Clamp-on type Current Transformer (CT) |
Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)