Business
> Industrial Devices
> Automation Controls Top
> FA Sensors & Components
> Pressure Sensors / Flow Sensors
> Pressure Sensors / Flow Sensors
> Head-separated Dual display Digital Pressure Sensor [For gas & liquid] DPC-L100 / DPH-L100
> Part Number
> DPH-L133
![]() |
*Photo may vary from actual product.
Product Number | DPH-L133 |
Part Number | DPH-L133 |
Product | Head-separated Dual display Digital Pressure Sensor [For gas & liquid] |
Details | Sensor head |
Product name | Head-separated Dual display Digital Pressure Sensor [For gas & liquid] DPC-L100 / DPH-L100 |
As of September 27, 2023
Specifications and design of the products are subject to change without notice for the product improvement.
Item | Specifications |
---|---|
Product Number | DPH-L133 |
Part Number | DPH-L133 |
Applicable regulations | CE Marking (EMC Directive, RoHS Directive), UKCA Marking (EMC Regulations, RoHS Regulations) |
Type of pressure | Sealed gauge pressure (Note): The sensor's internal mechanism is sealed based on an air pressure of 1,013 hPa. |
Rated pressure range | 0 to +3.5 MPa |
Pressure withstandability | 7 MPa |
Applicable fluid | Gases and fluids that do not corrode stainless steel SUS630, SUS304, or SUSXM7 |
Supply voltage | 9 to 36 V DC [9 to 32 V DC when using the attached connector (e-CON)] |
Current consumption | 20 mA or less |
Analog voltage output | Output voltage: 1 to 5 V DC (over rated pressure range) Accuracy: ±1.0 % F.S. (at 23 ±2 ℃ +73.4 ±35 ℉) ±2.0 % F.S. (at -20 to 70 ℃ -4 to +158 ℉) (including linearity, hysteresis and repeatability) |
Response time | 1 ms or less |
Protection | IP67 (IEC) |
Ambient temperature | -20 to +70 ℃ -4 to +158 ℉ (No dew condensation or icing allowed), Storage: -30 to +70℃ -22 to +158 ℉ |
Ambient humidity | 35 to 85 % RH, Storage : 35 to 85 % RH |
Medium temperature range | -20 to +70 ℃ -4 to +158 ℉ |
Voltage withstandability | 150 V AC for one min. between all supply terminals connected together and enclosure |
Insulation resistance | 100 MΩ, or more, with 50 V DC megger between all supply terminals connected together and enclosure |
Vibration resistance | 10 to 2,000 Hz frequency, acceleration 200 m/s2, in X direction for four hours, in Y and Z directions for two hours each (Note): The X, Y, and Z directions are defined as follows : ![]() |
Shock resistance | 1,000 m/s2 acceleration in X, Y and Z directions three times each |
Grounding method | Capacitor earth (Enclosure-supply terminal) |
Pressure port | R1/4 male thread (throttle embeded) |
Material | Diaphragm : Stainless steel (SUS603), Pressure port : Stainless steel (SUS304), Throttle : Stainless steel (SUSXM7) |
Connecting method | Connector |
Cable | 0.2 mm2 3-core heat resistant cabtyre cable 2 m 3.562 ft long |
Cable extension | Extension up to total 10 m 32.808 ft is possible with 0.2 mm2, or more, cable. |
Weight | Net weight : 100 g approx., Gross weight : 150 g approx. |
Accessories | Connector (e-CON) : 1 pc. |
Remark | Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +23 ℃ +73.4 ℉. The sensor head can be used independently. |
Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)