Business > Industrial Devices > Automation Controls Top > Components & Devices > Relays / Couplers > Power Relays (Over 2A) > Power Relays (Over 2A) Lineup > LD-P Relays > Rating/Performance
|
Rated coil voltage |
Operate voltage*1 (at 20°C) |
Release voltage*1 (at 20°C) |
Rated operating current [±10%] (at 20°C) |
Coil resistance [±10%] (at 20°C) |
Rated operating power |
Max. allowable voltage*2 (at 20°C) |
---|---|---|---|---|---|---|
5 V DC | Max. 75% V of rated coil voltage (Initial) |
Min. 5% V of rated coil voltage (Initial) |
40.0 mA | 125 Ω | 200 mW | 180% V of rated voltage |
6 V DC | 33.3 mA | 180 Ω | ||||
9 V DC | 22.2 mA | 405 Ω | ||||
12 V DC | 16.7 mA | 720 Ω | ||||
18 V DC | 11.1 mA | 1,620 Ω | ||||
24 V DC | 8.3 mA | 2,880 Ω |
*1 | Square, pulse drive |
---|---|
*2 | Maximum allowable voltage is the maximum voltage which can satisfy the coil temperature rise value. Please refer to "Max. applied voltage and temperature rise" in GUIDELINES FOR USAGE. |
Item | Specifications | |
---|---|---|
Contact data | Contact arrangement | 1 Form A |
Contact resistance (Initial) | Max. 100 mΩ (by voltage drop 6 V DC 1 A) | |
Contact material | AgNi type | |
Contact rating (resistive) | 5 A 277 V AC, 3 A 30 V DC | |
Max. switching power (resistive) | 1,385 VA, 90 W | |
Max. switching voltage | 277 V AC, 30 V DC | |
Max. switching current | 5 A (AC), 3 A (DC) | |
Min. switching load (reference value)*1 | 100 mA 5 V DC | |
Insulation resistance (initial) | Min. 1,000 MΩ (at 500 V DC, Measured portion is the same as the case of dielectric strength.) | |
Dielectric strength (initial) | Between open contacts | 750 Vrms for 1 min (detection current: 10 mA) |
Between contact and coil | 4,000 Vrms for 1 min (detection current: 10 mA) | |
Surge withstand voltage (initial)*2 | Between contact and coil | 10,000 V |
Time characteristics (initial) | Operate time | Max.10 ms at rated coil voltage (at 20°C, without bounce) |
Release time | Max.10 ms at rated coil voltage (at 20°C, without bounce, with diode) | |
Shock resistance | Functional | 300 m/s2 (half-sine shock pulse: 11 ms, detection time: 10 μs) |
Destructive | 1,000 m/s2 (half-sine shock pulse: 6 ms) | |
Vibration resistance | Functional | 10 to 55 Hz (at double amplitude of 1.5 mm, detection time: 10 μs) |
Destructive | 10 to 55 Hz (at double amplitude of: 1.5 mm) | |
Expected life | Mechanical life | Min. 5×106 ope. (at 180 times/min) |
Conditions | Conditions for usage, transport and storage*3 |
Ambient temperature: -40 to +85°C, Humidity: 5 to 85% RH (Avoid icing and condensation) |
Unit weight | Approx. 4 g |
*1 | This value can change due to the switching frequency, environmental conditions, and desired reliability level, therefore it is recommended to check this with the actual load. |
---|---|
*2 | Wave is standard shock voltage of ±1.2 x 50 µs according to JEC-212-1981 |
*3 | For ambient temperature, please read GUIDELINES FOR USAGE. |
Item | Characteristic | |
---|---|---|
Clearance/Creepage distance (IEC61810-1) | Min. 5.5mm/5.5mm | |
Category of protection (IEC61810-1) | RT III | |
Tracking resistance (IEC60112) | PTI175 | |
Insulation material group | III a | |
Over voltage category | III | |
Rated voltage | 250V | |
Pollution degree | 3 | 2 |
Type of insulation (Between contact and coil) | Basic Insulation | Reinforced Insulation |
Type of insulation (Between open contact) | Micro Disconnection |
* | Note: EN/IEC VDE Certified. |
---|
Conditions: Resistive load, at 20°C, switching frequency at 20 times/min
Type | Switching capacity | Number of operations |
---|---|---|
1 Form A | 5 A 125 V AC | Min. 200 x 103 ope. |
5 A 250 V AC | Min. 100 x 103 ope. | |
3 A 30 V DC | Min. 100 x 103 ope. |
|
Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)