Rating/ Performance

1.Rating

Types of load Resistive
load
(cosø≒1)
Inductive
load
(cosø≒0.4)
Motor or lamp load
N.C.
contact
N.O.
contact
125V AC 15A 10A 4A 2A
250V AC 15A 10A 3A 1.5A
125V DC 0.5A 0.05A - -

2.Characteristics

Contact arrangement 1 Form C
Initial contact resistance, max. 15mΩ (By voltage drop 6 to 8V DC 1A)
Initial insulation resistance (At 500V DC) Min. 100MΩ
Initial breakdown voltage 1,000Vrms for 1 min Between non-consective terminals
1,500Vrms for 1 min Between dead metal parts and each terminal
1,500Vrms for 1 min Between ground and each terminal
Expected life
(Min. operations)
Mechanical 106 (at 60 cpm)
Electrical 105 (at 60 cpm)

3.Operating characteristics

特性 O.F.(N{gf})
max.
R.F.(N{gf})
min.
P.T.
max.
M.D.
max.
O.T.(mm)
min.
Push plunger 9.80{1,000} 2.16{220} 2.0 .079 0.1 .004 5.0 .197
Roller plunger 3.43{350} 1.12{114} 0.5 .020 0.1 .004 3.6 .142
Cross roller plunger 3.43{350} 1.12{114} 0.5 .020 0.1 .004 3.6 .142
Roller lever 6.67{680} 1.67{170} 4.5 .177 0.4 .016 5.5 .217

4.Protective characteristics

Protective
construction
Slitted type
limit switches
IEC
IP60 ○ *
IP64 ○ *
*Except AZ6102,6202,AZ6103,AZ6203

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region




Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)