Safety standard | EN61812-1 | Pollution Degree 2/Overvoltage Category II (2 Form C type); Pollution Degree 1/Overvoltage Category II (4 Form C type) |
|
---|---|---|---|
EMC | (EMI)EN61000-6-4 | ||
Radiation interference electric field strength | EN55011 Group1 ClassA | ||
Noise terminal voltage | EN55011 Group1 ClassA | ||
(EMS)EN61000-6-2 | |||
Static discharge immunity | EN61000-4-2 | 4 kV contact | |
8 kV air | |||
RF electromagnetic field immunity | EN61000-4-3 | 10 V/m AM modulation (80 MHz to 1 GHz) | |
10 V/m pulse modulation (895 MHz to 905 MHz) | |||
EFT/B immunity | EN61000-4-4 | 2 kV (power supply line) | |
1 kV (signal line) | |||
Surge immunity | EN61000-4-5 | 1 kV (power line) | |
Conductivity noise immunity | EN61000-4-6 | 10 V/m AM modulation (0.15 MHz to 80 MHz) | |
Power frequency magnetic field immunity | EN61000-4-8 | 0 A/m (50 Hz) | |
Voltage dip/Instantaneous stop/Voltage fluctuation immunity | EN61000-4-11 | 10 ms, 30% (rated voltage) | |
100 ms, 60% (rated voltage) | |||
1,000 ms, 60% (rated voltage) | |||
5,000 ms, 95% (rated voltage) |