Business > Industrial Devices > Automation Controls Top > FA Sensors & Components > Sensors > Photoelectric Sensors / Laser Sensors > Compact Multi-voltage Photoelectric Sensor NX5 > Specifications
Discontinuation plan
|
|
Type | Thru-beam | ||||
---|---|---|---|---|---|
Long sensing range | |||||
Model No. | NX5-M10RA | NX5-M10RB | NX5-M30A | NX5-M30B | |
Regulatory compliance | ・Low Voltage Directive : EN IEC 60947-5-2 ・EMC Directive : EN IEC 60947-5-2 ・RoHS Directive ・GB/T 14048.10 |
||||
Sensing range | 10 m 32.808 ft |
30 m 98.425 ft |
|||
Sensing object | φ20 mm φ0.787 in or more opaque object (Note 2) |
φ20 mm φ0.787 in or more opaque object (Completely beam interrupted object) (Note 2) |
|||
Hysteresis | - | ||||
Repeatability (perpendicular to sensing axis) |
0.1 mm 0.004 in or less | 0.2 mm 0.008 in or less | |||
Supply voltage | 24 to 240 V AC +10–15 % or 12 to 240 V DC +10–15 % Ripple P-P 10 % or less | ||||
Power consumption | Emitter: 1 VA or less Receiver: 2 VA or less |
Emitter: 1.5 VA or less Receiver: 2 VA or less |
|||
Output | Relay contact 1 c • Switching capacity: 250 V AC 1 A (resistive load) 30 V DC 2 A (resistive load) • Electrical life: 500,000 or more switching operations (switching frequency 3,600 operations/hour) 100,000 or more switching operations (switching frequency 3,600 operations/hour) • Mechanical life: 100 million or more switching operations (switching frequency 36,000 operations/hour) |
||||
Output operation | Light-ON | Dark-ON | Light-ON | Dark-ON | |
Response time | 10 ms or less | ||||
Operation indicator | Red LED (lights up when the output is ON) | ||||
Stability indicator | Green LED (lights up under stable light received condition or stable dark condition) |
||||
Power indicator | - | Red LED (lights up when the power is ON) |
|||
Sensitivity adjuster | Continuously variable adjuster | - | |||
Automatic interference prevention function |
(Use optional interference prevention filters) |
- | |||
Pollution degree | 3 (Industrial environment) | ||||
Protection | IP66 (IEC) | ||||
Ambient temperature | –20 to +55 ℃ –4 to +131 ℉ (No dew condensation or icing allowed) (Note 3), Storage: –30 to +70 ℃ –22 to +158 ℉ |
||||
Ambient humidity | 35 to 85 % RH, Storage: 35 to 85 % RH | ||||
Ambient illuminance | Incandescent light: 3,500 Lx or less at the light-receiving face | ||||
Voltage withstandability | 1,500 V AC for one min. between all supply terminals connected together and enclosure, 1,500 V AC for one min. between power supply and output terminals, 1,000 V AC for one min. between relay contact terminals |
||||
Insulation resistance | 20 MΩ, or more, with 500 V DC megger between power supply and output terminals, and between relay contact terminals | ||||
Vibration resistance | 10 to 55 Hz frequency, 1.5 mm 0.059 in double amplitude in X, Y and Z directions two hours each | ||||
Shock resistance | 500 m/s2 (50 G approx.) in X, Y and Z directions three times each | ||||
Emitting element | Red LED (modulated) | Infrared LED (modulated) | |||
Peak emission wavelength |
660 nm 0.026 mil | 880 nm 0.035 mil | |||
Material | Enclosure: Polycarbonate, Lens: Polycarbonate, Cover: Polycarbonate | ||||
Cable | 0.3 mm2 5-core (thru-beam type emitter: 2-core) cabtyre cable, 2 m 6.562 ft long | ||||
Cable extension | Extension up to total 100 m 328.084 ft is possible with 0.3 mm2, or more, cable (thru-beam type: both emitter and receiver). | ||||
Net weight | Emitter: 100 g approx. Receiver: 140 g approx. |
Emitter: 125 g approx. Receiver: 140 g approx. |
|||
Accessories | Adjusting screwdriver: 1 pc. | - |
Notes:
1) | Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +23 ℃ +73.4 ℉. |
---|---|
2) | If slit masks (optional) are fitted, an object as small as 3 x 6 mm 0.118 x 0.236 in can be detected. |
3) | In case the sensor is to be used at an ambient temperature of –15 ℃ +5 ℉, or less, please contact our office. |
Type | Thru-beam | |||
---|---|---|---|---|
Long sensing range | ||||
Model No. | NX5-M10RA | NX5-M10RB | NX5-M30A | NX5-M30B |
Utilization category | AC-12/DC-12 | |||
Impulse withstand voltage | 2.5kV | |||
Output minimum operational current | DC5V 1mA or more | |||
Turn on time / Turn off time (Note 4) | 10ms / 10ms | |||
Maximum response frequency (Note 5) | 50Hz | |||
Pollution degree | 3 (Industrial environment) | |||
Class of protection against electric shock | Out of classification | |||
Excess gain | 30% (Note 6) | 30% |
Note:
1) | Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +23 ℃ +73.4 ℉. |
---|---|
2) | The output applied voltage should be the same as the supply voltage of the sensor. |
3) | Be sure to add a short-circuit protection (a fuse or a breaker) to the power supply input and the output. In addition, use 3A or less fast blow fuse or breaker. |
4) | Turn-On time and Turn-OFF time are the delay time between reference sensor and measurement sensor in case round plate rotates as below. |
5) | The maximum response frequency is the value calculated below. Maximum response frequency = 1 / (Turn on time+Turn off time) |
6) | Excess gain of NX5-M10□ is the value in case sensitivity aduster is in maximum position. |
Type | Retroreflective | Diffuse reflective | |||||
---|---|---|---|---|---|---|---|
With polarizing filters | Long sensing range | ||||||
Model No. | NX5-PRVM5A | NX5-PRVM5B | NX5-RM7A | NX5-RM7B | NX5-D700A | NX5-D700B | |
Regulatory compliance | ・Low Voltage Directive : EN IEC 60947-5-2 ・EMC Directive : EN IEC 60947-5-2 ・RoHS Directive ・GB/T 14048.10 |
||||||
Sensing range | 0.1 to 5 m 0.328 to 16.404 ft (Note 2) |
0.1 to 7 m 0.328 to 22.966 ft (Note 2) |
700 mm 27.559 in (Note 3) |
||||
Sensing object | φ50 mm φ1.969 in or more opaque, translucent or specular object (Note 2, 4) |
φ50 mm φ1.969 in or more opaque or translucent object (Note 2, 4) |
Opaque, translucent or transparent object (Note 4) |
||||
Hysteresis | - | 15 % or less of operation distance (Note 3) |
|||||
Repeatability (perpendicular to sensing axis) |
0.2 mm 0.008 in or less | 0.3 mm 0.012 in or less | |||||
Supply voltage | 24 to 240 V AC +10–15 % or 12 to 240 V DC +10–15 % Ripple P-P 10 % or less | ||||||
Power consumption | 2 VA or less | ||||||
Output | Relay contact 1 c • Switching capacity: 250 V AC 1 A (resistive load) 30 V DC 2 A (resistive load) • Electrical life: 500,000 or more switching operations (switching frequency 3,600 operations/hour) 100,000 or more switching operations (switching frequency 3,600 operations/hour) • Mechanical life: 100 million or more switching operations (switching frequency 36,000 operations/hour) |
||||||
Output operation | Light-ON | Dark-ON | Light-ON | Dark-ON | Light-ON | Dark-ON | |
Response time | 10 ms or less | ||||||
Operation indicator | Red LED (lights up when the output is ON) | ||||||
Stability indicator | Green LED (lights up under stable light received condition or stable dark condition) |
||||||
Power indicator | - | ||||||
Sensitivity adjuster | Continuously variable adjuster | - | Continuously variable adjuster | ||||
Automatic interference prevention function |
Incorporated (Two units of sensors can be mounted close together.) | ||||||
Pollution degree | 3 (Industrial environment) | ||||||
Protection | IP66 (IEC) | ||||||
Ambient temperature | –20 to +55 ℃ –4 to +131 ℉ (No dew condensation or icing allowed) (Note 5), Storage: –30 to +70 ℃ –22 to +158 ℉ |
||||||
Ambient humidity | 35 to 85 % RH, Storage: 35 to 85 % RH | ||||||
Ambient illuminance | Incandescent light: 3,500 Lx at the light-receiving face | ||||||
Voltage withstandability | 1,500 V AC for one min. between all supply terminals connected together and enclosure, 1,500 V AC for one min. between power supply and output terminals, 1,000 V AC for one min. between relay contact terminals |
||||||
Insulation resistance | 20 MΩ, or more, with 500 V DC megger between power supply and output terminals, and between relay contact terminals | ||||||
Vibration resistance | 10 to 55 Hz frequency, 1.5 mm 0.059 in amplitude in X, Y and Z directions for two hours each | ||||||
Shock resistance | 500 m/s2 (50 G approx.) in X, Y and Z directions for three times each | ||||||
Emitting element | Red LED (modulated) | Infrared LED (modulated) | |||||
Peak emission wavelength |
660 nm 0.026 mil | 880 nm 0.035 mil | |||||
Material | Enclosure: Polycarbonate, Lens: Polycarbonate, Cover: Polycarbonate, Front cover (retroreflective type sensor only) : Acrylic | ||||||
Cable | 0.3 mm2 5-core (thru-beam type emitter: 2-core) cabtyre cable, 2 m 6.562 ft long | ||||||
Cable extension | Extension up to total 100 m 328.084 ft is possible with 0.3 mm2, or more, cable (thru-beam type: both emitter and receiver). | ||||||
Net weight | 140 g approx. | ||||||
Accessories | RF-230 (Reflector): 1 pc. Adjusting screwdriver: 1 pc. |
RF-230 (Reflector): 1 pc. | Adjusting screwdriver: 1 pc. |
Notes:
1) | Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +23 ℃ +73.4 ℉. |
---|---|
2) | The sensing range and the sensing object of the retroreflective type sensor is specified for the RF-230 reflector. Further, the sensing range is the possible setting range for the reflector. The sensor can detect an object less than 0.1 m 0.328 ft away. |
3) | The sensing range and the hysteresis of the diffuse reflective type sensor are specified for white non-glossy paper (200 x 200 mm 7.874 x 7.874 in) as the object. |
4) | Make sure to confirm detection with an actual sensor before use. |
5) | In case the sensor is to be used at an ambient temperature of –15 ℃ +5 ℉, or less, please contact our office. |
Type | Retroreflective | Diffuse reflective | ||||
---|---|---|---|---|---|---|
With polarizing filters | Long sensing range | |||||
Model No. | NX5-PRVM5A | NX5-PRVM5B | NX5-RM7A | NX5-RM7B | NX5-D700A | NX5-D700B |
Utilization category | AC-12/DC-12 | |||||
Impulse withstand voltage | 2.5kV | |||||
Output minimum operational current | DC5V 1mA or more | |||||
Turn on time / Turn off time (Note 4) | 10ms / 10ms | |||||
Maximum response frequency (Note 5) | 50Hz | |||||
Pollution degree | 3 (Industrial environment) | |||||
Class of protection against electric shock | Out of classification | |||||
Excess gain | 10% (Note 6) | 10% | 14% (Note 6) |
Note:
1) | Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +23 ℃ +73.4 ℉. |
---|---|
2) | The output applied voltage should be the same as the supply voltage of the sensor. |
3) | Be sure to add a short-circuit protection (a fuse or a breaker) to the power supply input and the output. In addition, use 3A or less fast blow fuse or breaker. |
4) | Turn-On time and Turn-OFF time are the delay time between reference sensor and measurement sensor in case round plate rotates as below. |
5) | The maximum response frequency is the value calculated below. Maximum response frequency = 1 / (Turn on time+Turn off time) |
6) | Excess gain of NX5-PRVM5□/NX-D700□ is the value in case sensitivity aduster is in maximum position. |
Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)