Business > Industrial Devices > Automation Controls Top > FA Sensors & Components > Sensors > Inductive Proximity Sensors > Compact & Low Price Inductive Proximity Sensor GL(Discontinued Products) > Specifications
We are sorry, the products have been discontinued. Please refer to the details of the discontinued products and the recommended substitutes list below.
|
|
Type | Standard | |||
---|---|---|---|---|
Different frequency | ||||
Model No. | GL-18H | GL-18HI | GL-18HB | |
CE marking directive compliance | EMC Directive, RoHS Directive | |||
Max. operation distance (Note 2) | 5 mm 0.197 in ± 10 % | |||
Stable sensing range (Note 2) |
0 to 4 mm 0 to 0.157 in | |||
Standard sensing object | Iron sheet 25 x 25 x t 1 mm 0.984 x 0.984 x t 0.039 in |
|||
Hysteresis | 15 % or less of operation distance (with standard sensing object) |
|||
Supply voltage | 10 to 30 V DC Ripple P-P 10 % or less | |||
Current consumption | 10 mA or less | |||
Output | NPN open-collector transistor - Maximum sink current: 100 mA - Applied voltage: 30 V DC or less (between output and 0 V) - Residual voltage: 1.5 V or less (at 100 mA sink current) 0.4 V or less (at 16 mA sink current) |
|||
Utilization category | DC-12 or DC-13 | |||
Output operation | Normally open | Normally closed | ||
Max. response frequency | 1kHz | |||
Operation indicator | Red LED (lights up when the output is ON) | |||
Pollution degree | 3 (Industrial environment) | |||
Protection | IP67 (IEC), IP67G (Note 3) | |||
Ambient temperature | -25 to +70 ℃ -13 to +158 ℉, Storage: -25 to +70 ℃ -13 to +158 ℉ |
|||
Ambient humidity | 45 to 85 % RH, Storage: 45 to 85 % RH | |||
Voltage withstandability | 1,000 V AC for one min. between all supply terminals connected together and enclosure | |||
Insulation resistance | 50 MΩ, or more, with 250 V DC megger between all supply terminals connected together and enclosure | |||
Vibration resistance | 10 to 55 Hz frequency, 1.5 mm 0.059 in double amplitude in X, Y and Z directions for two hours each | |||
Shock resistance | 1,000 m/s2 acceleration (100 G approx.) in X, Y and Z directions three times each | |||
Sensing range variation |
Temperature characteristics | Over ambient temperature range -25 to +70 ℃ -13 to +158 ℉ : within ±10 % of sensing range at +20 ℃ +68 ℉ |
||
Voltage characteristics | Within ±2 % for ±10 % fluctuation of the supply voltage | |||
Material | Enclosure: Polyarylate | |||
Cable | 0.3 mm2 3-core oil resistant cabtyre cable, 1 m 3.281 ft long | |||
Cable extension | Extension up to total 100 m 328.084 ft is possible with 0.3 mm2, or more, cable. | |||
Weight | Net weight : 45 g approx. | |||
Accessory | - |
Type | Long sensing range | |||
---|---|---|---|---|
Different frequency | ||||
Model No. | GL-18HL | GL-18HLI | GL-18HLB | |
CE marking directive compliance | EMC Directive, RoHS Directive | |||
Max. operation distance (Note 2) |
12 mm 0.472 in ± 10 % | |||
Stable sensing range (Note 2) |
0 to 10 mm 0 to 0.394 in | |||
Standard sensing object | Iron sheet 40 x 40 x t 1 mm 1.575 x 1.575 x t 0.039 in |
|||
Hysteresis | 15 % or less of operation distance (with standard sensing object) |
|||
Supply voltage | 10 to 30 V DC Ripple P-P 10 % or less | |||
Current consumption | 10 mA or less | |||
Output | NPN open-collector transistor - Maximum sink current: 100 mA - Applied voltage: 30 V DC or less (between output and 0 V) - Residual voltage: 1.5 V or less (at 100 mA sink current) 0.4 V or less (at 16 mA sink current) |
|||
Utilization category | DC-12 or DC-13 | |||
Output operation | Normally open | Normally closed | ||
Max. response frequency | 500Hz | |||
Operation indicator | Red LED (lights up when the output is ON) | |||
Pollution degree | 3 (Industrial environment) | |||
Protection | IP67 (IEC), IP67G (Note 3) | |||
Ambient temperature | -25 to +70 ℃ -13 to +158 ℉, Storage: -25 to +70 ℃ -13 to +158 ℉ |
|||
Ambient humidity | 45 to 85 % RH, Storage: 45 to 85 % RH | |||
Voltage withstandability | 1,000 V AC for one min. between all supply terminals connected together and enclosure | |||
Insulation resistance | 50 MΩ, or more, with 250 V DC megger between all supply terminals connected together and enclosure | |||
Vibration resistance | 10 to 55 Hz frequency, 1.5 mm 0.059 in double amplitude in X, Y and Z directions for two hours each | |||
Shock resistance | 1,000 m/s2 acceleration (100 G approx.) in X, Y and Z directions three times each | |||
Sensing range variation |
Temperature characteristics | Over ambient temperature range -25 to +70 ℃ -13 to +158 ℉ : within ±10 % of sensing range at +20 ℃ +68 ℉ |
||
Voltage characteristics | Within ±2 % for ±10 % fluctuation of the supply voltage | |||
Material | Enclosure: Polyarylate | |||
Cable | 0.3 mm2 3-core oil resistant cabtyre cable, 1 m 3.281 ft long | |||
Cable extension | Extension up to total 100 m 328.084 ft is possible with 0.3 mm2, or more, cable. | |||
Weight | Net weight : 45 g approx. | |||
Accessory | MS-GL18HL (Sensor mounting bracket): 1 set |
Notes:
1) | Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +23 ℃ +73.4 ℉. |
---|---|
2) | The maximum operation distance stands for the maximum distance for which the sensor can detect the standard sensing object. The stable sensing range stands for the sensing range for which the sensor can stably detect the standard sensing object even if there is an ambient temperature drift and/or supply voltage fluctuation. |
3) | If using the sensor in an environment where cutting oil droplets splatter, the sensor may be deteriorated due to added substances in the oil. Please check the resistivity of the sensor against the cutting oil you are using beforehand. |
Type | DC 2-wire type | ||||
---|---|---|---|---|---|
Front sensing | Top sensing | ||||
Model No. | GL- 8FUx10 |
GL- 8FUBx10 |
GL- 8HUx10 |
GL- 8HUBx10 |
|
Different frequency | GL- 8FUIx10 |
GL- 8FUIBx10 |
GL- 8HUIx10 |
GL- 8HUIBx10 |
|
Max. operation distance (Note 2) | 2.5 mm 0.098 in ± 20 % | ||||
Stable sensing range (Note 2) | 0 to 1.8 mm 0 to 0.071 in | ||||
Standard sensing object | Iron sheet 15 x 15 x t 1 mm 0.591 x 0.591 x t 0.039 in |
||||
Hysteresis | 20 % or less of operation distance (with standard sensing object) |
||||
Supply voltage | 12 to 24 V DC ± 10 % Ripple P-P 10 % or less | ||||
Current consumption | 0.8 mA or less (Note 3) | ||||
Output | Non-contact DC 2-wire type - Load current: 3 to 70 mA (Note 4) - Residual voltage: 3 V or less (Note 5) |
||||
Utilization category | DC-12 or DC-13 | ||||
Output operation | Normally open | Normally closed | Normally open | Normally closed | |
Short-circuit protection | Incorporated | ||||
Max. response frequency | 1kHz | ||||
Operation indicator | Orange LED (lights up when the output is ON) | ||||
Pollution degree | 3 (Industrial environment) | ||||
Protection | IP67 (IEC) | ||||
Ambient temperature | -25 to +70 ℃ -13 to +158 ℉, Storage: -30 to +80 ℃ -22 to +176 ℉ |
||||
Ambient humidity | 35 to 95 % RH, Storage: 35 to 95 % RH | ||||
Voltage withstandability | 1,000 V AC for one min. between all supply terminals connected together and enclosure | ||||
Insulation resistance | 50 MΩ, or more, with 250 V DC megger between all supply terminals connected together and enclosure | ||||
Vibration resistance | 10 to 55 Hz frequency, 1.5 mm 0.059 in double amplitude in X, Y and Z directions for two hours each | ||||
Shock resistance | 1,000 m/s2 acceleration (100 G approx.) in X, Y and Z directions three times each | ||||
Sensing range variation |
Temperature characteristics | Over ambient temperature range -25 to +70 ℃ -13 to +158 ℉ : within +10 -15 % of sensing range at +20 ℃ +68 ℉ |
|||
Voltage characteristics | Within ±2 % for ±10 % fluctuation of the supply voltage | ||||
Material | Enclosure: Polyarylate | ||||
Cable | 0.15 mm2 2-core cabtyre cable, 1 m 3.281 ft long | ||||
Cable extension | Extension up to total 50 m 164.042 ft is possible with 0.3 mm2, or more, cable. | ||||
Weight | Net weight : 12 g approx. |
Notes:
1) | Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +23 ℃ +73.4 ℉. |
---|---|
2) | The maximum operation distance stands for the maximum distance for which the sensor can detect the standard sensing object. The stable sensing range stands for the sensing range for which the sensor can stably detect the standard sensing object even if there is an ambient temperature drift and/or supply voltage fluctuation. |
3) | It is the leakage current when the output is in the OFF state. |
4) | The maximum load current varies depending on the ambient temperature. |
5) | When the cable is extended, the residual voltage becomes larger according to the resistance of the cable. |
Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)