[Notification of CAD Data Download Issue]
We regret to inform you that we are currently experiencing issues with downloading CAD data for some products.
We are investigating the cause of this problem. We apologize for any inconvenience this may cause and appreciate your understanding.
Business > Industrial Devices > Automation Controls Top > FP0R Intelligent units > AFP0RAD4
*Photo may vary from actual product.
Product Number | AFP0RAD4 |
Part Number | AFP0RAD4 |
Product | FP0R Analog input unit |
Product name | FP0R Intelligent units |
As of May 18, 2024
Specifications and design of the products are subject to change without notice for the product improvement.
Item | Specifications |
---|---|
Product Number | AFP0RAD4 |
Part Number | AFP0RAD4 |
Item | Specifications |
---|---|
Number of input / output channels | 4 / 0 |
Input range (digital input range) : Voltage | -10 to +10 V 14 bits (-8,000 to +8,000) -5 to +5 V 14 bits (-8,000 to +8,000) 0 to +10 V 14 bits (0 to +16,000) 0 to +5 V 14 bits (0 to +16,000) -100 to +100 mV 12 bits (-2,000 to +2,000)(Note) (Note) : It is equipped in the products after Ver.1.2 (12-bit mode only) |
Input range (digital input range) : Current | 0 to 20 mA 14 bits (0 to +16,000) |
Absolute maximum input:Voltage | ±15 V |
Absolute maximum input:Current | ±30 mA |
Input impedance:Voltage | 1 MΩ approx. |
Input impedance:Current | 250 Ω approx. |
Max. resolution | 14 bits (1/16,000) |
Overall accuracy : Voltage : ±100mV | ±0.6 % F.S. or less (at +25 ℃ +77 ℉) ±1.0 % F.S. or less (at 0 to +55 ℃ +32 to +131 ℉) |
Overall accuracy : Voltage : Others | ±0.2 % F.S. or less (at +25 ℃ +77 ℉) ±0.4 % F.S. or less (at 0 to +55 ℃ +32 to +131 ℉) |
Overall accuracy : Current | ±0.3 % F.S. or less (at +25 ℃ +77 ℉) ±0.6 % F.S. or less (at 0 to +55 ℃ +32 to +131 ℉) |
Conversion speed | 2 ms/all channels |
Other functions | Averaging processing (moving, number of times) Compatibility function for existing programs (12 bits) |
Insulation method : Between input terminals and internal circuit | Photocoupler and isolated DC/DC converter |
Insulation method : Between channels | Not insulated |
Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)