Business > Industrial Devices > Automation Controls Top > KW2G Expansion unit > AKW2160GB
*Photo may vary from actual product.
Product Number | AKW2160GB |
Part Number | AKW2160GB |
Product | Eco-POWER METER |
Details | Expansion unit |
Product name | KW2G Expansion unit |
As of April 29, 2024
Specifications and design of the products are subject to change without notice for the product improvement.
Item | Specifications |
---|---|
Product Number | AKW2160GB |
Part Number | AKW2160GB |
[[Accuracy]Accuracy (without error in CT and VT) : Integrated electric power and Instantaneous electric power | Within ± (2.0 % F.S. + 1 digit) (at 20 ℃ 68 ℉, rated input, rated frequency, power factor 1) *Accuracy coverage : 10 to 100 % of rated current |
Item | Specifications |
---|---|
Integrated electric power(Active):kWh/MWh | 0.00 to 9999.99 kWh to 9999.99 MWh, 0.00 to 9999999.99 kWh (when 9-digit display) (Note):measure regeneration electric power. Integrated electrical power is not integrated (not subtracted) when detecting regeneration electric power. |
Instantaneous electric power:Active:kW | -9999.99 to 0.000 to 9999.99 (Note):While detecting regeneration electric power, minus is displayed on instantaneous active electric power and power factor. |
Current:T-current:A | 0.000 to 6000.00 |
Voltage:R(RS)-voltage:V | 0.0 to 9999.9 |
Voltage:S(RT)-voltage:V | 0.0 to 9999.9 (calculated value) |
Voltage:T(TS)-voltage:V | 0.0 to 9999.9 |
Electricity charge | 0.00 to 999999 |
Conversion carbon dioxide value:kg-CO2 | 0.00 to 999999 |
Power factor:Displayed on the main unit | -1.00 to 1.00 (without identify leading phase and lagging phase) (Note):While detecting regeneration electric power, minus is displayed on instantaneous active electric power and power factor. |
Frequency:Hz | 47.5 to 63.0 |
Pulse count value | 0 to 999999 (Note):Displayed digit of pulse counter differs according to the pre-scale set by pre-scale setting mode. |
Item | Specifications |
---|---|
OFF-time:Hour | 0 to 99999.9 |
ON-time 1:Hour | 0 to 99999.9 |
ON-time 2:Hour | 0 to 99999.9 |
Maintenance time:Hour | 0 to 99999.9 (Note):Maintenance time by using pulse input cannot be measured |
Actual work time:Hour | 0 to 99999.9 |
Ratio of ON-time 1:% | 0.0 to 100.0 |
Ratio of ON-time 2:% | 0.0 to 100.0 |
Item | Specifications |
---|---|
Accuracy (without error in CT and VT) : Current | Within ± (1.0 % F.S. + 1 digit) (at 20 ℃ 68 ℉, rated input, rated frequency, power factor 1) *Accuracy coverage : 10 to 100 % of rated current |
Accuracy (without error in CT and VT) : Voltage | Within ± (1.0 % F.S. + 1 digit) (at 20 ℃ 68 ℉, rated input, rated frequency, power factor 1) |
Accuracy (without error in CT and VT) : Temperature characteristics | Within ± (1.0 % F.S. + 1 digit) (Range of -10 to 50 ℃ 14 to 122℉, rated input, power factor 1) |
Accuracy (without error in CT and VT) : Hour meter | Within ±(0.01% +1 digit)(at20℃ 68℉) ±280sec.per month (for reference) |
Accuracy (without error in CT and VT) : Frequency characteristics | Within ± (1.0 % F.S. + 1 digit) (Frequency change ± 5 % based on rated frequency, rated input, power factor 1) |
Item | Specifications |
---|---|
Rated operating voltage | 100 to 240 V AC (Add to main unit) |
Rated frequency | 50 / 60 Hz common |
Rated power consumption | Main unit : 6 VA, Expansion unit (Power measurement, Power measurement and Pulse output, and Analog input) : 0.5 VA / unit, Expansion unit (Pulse input) : 1.0 VA /unit (240 V AC at 25 ℃ 77 ℉) |
Allowable operating voltage range | 85 to 264 V AC (85 % to 110 % of rated operating voltage) |
Allowable momentary power-off time | 10 ms |
Ambient temperature | -10 to +50 ℃ +14 to +122 ℉ (-25 to +70 ℃ -13 to +158 ℉ at storage) |
Ambient humidity | 30 to 85 % RH (at 20 ℃ 68 ℉) non-condensing |
Display method | LCD with backlight (green), Upper : 5-digit (7-segment 1-digit + 16-segment 4-digit), Lower : 6-digit (7-segment) |
Number of connectable expansion units | Max. 7 units |
Power failure memory method | EEPROM (more than 1,000,000 overwrite), Memory items : setting value and integral measuring value |
Weight | Main unit : 180 g, Expansion unit (Power measurement) : 80 g, Expansion unit (Power measurement and Pulse output, Pulse input, and Analog input) : 85 g |
Item | Specifications |
---|---|
Number of output point | 1 point |
Insulation method | Optical coupler |
Output type / Output capacity | Open collector / 100 mA 30 V DC |
Pulse width (when pulse output with integrated active electric power selected) | 1-100 ms (Select with setting mode) (Note1): The function of setting pulse output width is available with AKW2010G(B) ver. 1.04 or later. (Note2): The max. pulse output cycle is 25ms in order to work correctly and output 1 to 10ms pulse output. Therefore the pulse output unit should be set as that it output 40 pulses or less in 1 second. |
ON state voltage drop | 1.5 V or less |
OFF state leakage current | 100 μA or less |
Pulse output unit | 0.001 kWh, 0.01 kWh, 0.1 kWh, 1 kWh, 10 kWh, 100 kWh / Power alarm(AL-P) / Current alarm(AL-C) / Stand-by power alarm(AL-S) / General purpose output(OUT)(Note) / Error alarm(Error) (Selectable with setting mode) (Note): In order to use the general purpose output, it is necessary to set the output status ON or OFF via communications. In addition it doesn't work with the on-time and off-time set to under 0.1s. |
General purpose output | Level output / Repeat cycle output / One-shot output (Selectable with setting mode) (Note): In order to use the general purpose output, it is necessary to set the output status ON or OFF via communications. In addition it doesn't work with the on-time and off-time set to under 0.1s. |
Output ON-time, Output OFF-time | 0.1 to 10.0s (Selectable with setting mode) |
To Be Discontinued
Product Number | AKW4801B |
Part Number | AKW4801B |
Product name | Clamp-on type Current Transformer (CT) |
To Be Discontinued
Product Number | AKW4802B |
Part Number | AKW4802B |
Product name | Clamp-on type Current Transformer (CT) |
To Be Discontinued
Product Number | AKW4803B |
Part Number | AKW4803B |
Product name | Clamp-on type Current Transformer (CT) |
Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)