Business > Industrial Devices > Automation Controls Top > Components & Devices > Relays / Couplers > Interface Terminal > RT-3 UNIT RELAY (PA-N relay type) /4-POINT TERMINAL (Without relay type) > Rating/Performance
Part No. | Rated input voltage | Input current (at rated input voltage) (at 20°C) |
Allowable variation of rated input voltage (-20 to +55°C) |
---|---|---|---|
AY32001 | 12 V DC | Approx. 10.7 mA (Relay 9.2 mA + LED 1.5 mA) | 12 V DC ± 10% |
AY32002 | 24 V DC | Approx. 7.6 mA (Relay 4.6 mA + LED 3.0 mA) | 24 V DC ± 10% |
Relay part No. |
Operate voltage (at 20°C) | Release voltage (at 20°C) | Coil resistance (±10%) (at 20°C) |
Rated operating power |
---|---|---|---|---|
APAN3112 | Max. 70% V of rated coil voltage (Initial) | Min. 5% V of rated coil voltage (Initial) | 1,309 Ω | 110 mW |
APAN3124 | 5,236 Ω | 110 mW |
Specification | Item | Specifications |
---|---|---|
Contact data | Contact rating (resistive) | 3 A 250 V AC, 3 A 30 V DC |
Max. switching power (resistive) | 750 VA (AC), 90 W (DC) | |
Max. switching voltage | 250 V AC, 30 V DC | |
Max. switching current | 3 A | |
Min. switching load (reference value) | 100 μA 100 mV DC | |
Expected life | Mechanical life | Min. 20 x 106 ope. (at 180 times/min) |
Electrical life (resistive) | 3 A 250 V AC: Min. 30 x 103 ope. 3 A 30 V DC: Min. 30 × 103 ope. 2 A 250 V AC: Min. 100 × 103 ope. 2 A 30 V DC: Min. 100 × 103 ope. |
* | Note: During 4-point simultaneous operation, the rating per point is also as shown above. |
---|
Rated input voltage | Allowable variation of rated input voltage | Allowable input current |
---|---|---|
12 V, 24 V DC | 12 V DC ± 10%, 24 V DC ± 10% | 0.2 A |
* | The input voltage value above is the allowable current when no relay is installed. Please note that input voltage is determined by the type of relay installed. |
---|
Type | Rated input voltage |
Operate voltage (Initial) | Release voltage (Initial) | Input current (during application of rated input voltage) |
---|---|---|---|---|
APAN3112 | 12 V DC | Max. 9.5 V DC (Relay max. 8.4 V + include diode max. 1.1 V) |
Min. 1.0 V DC (Relay min. 0.6 V + include diode min. 0.4 V) |
Approx. 10.7 mA (Relay 9.2 mA + LED 1.5 mA) |
APAN3124 | 24 V DC | Max. 17.9 V DC (Relay max. 16.8 V + include diode max. 1.1 V) |
Min. 1.6 V DC (Relay min. 1.2 V + include diode min. 0.4 V) |
Approx. 7.6 mA (Relay 4.6 mA + LED 3.0 mA) |
Type | Rated input voltage |
Operate voltage (Initial) | Release voltage (Initial) | Input current (during application of rated input voltage) |
---|---|---|---|---|
AQZ∗0∗D | 12 V, 24 V DC | Max. 5.1 V DC (Relay max. 4.0 V + include diode max. 1.1 V) |
Min. 1.2 V DC (Relay min. 0.8 V + include diode min. 0.4 V) |
Approx. 10.0 mA (Relay 7.0 mA + LED 3.0 mA) |
Allowable load voltage | Allowable load current |
---|---|
600 V (DC), 600 V (AC peak value) | 3 A |
* | The value above is the allowable value when no relay is installed. Please note that limitations apply to the load voltage and current depending on the type of relay installed. |
---|
Specification | Item | Specifications |
---|---|---|
Contact data | Contact rating (resistive) | 3 A 250 V AC, 3 A 30 V DC |
Max. switching power (resistive) | 750 VA (AC), 90 W (DC) | |
Max. switching voltage | 250 V AC, 30 V DC | |
Max. switching current | 3 A | |
Min. switching load (reference value) | 100 μA 100 mV DC | |
Expected life | Mechanical life | Min. 20 x 106 ope. (at 180 times/min) |
Electrical life (resistive) | 3 A 250 V AC, 3 A 30 V DC: Min. 30 × 103 ope. 2 A 250 V AC, 2 A 30 V DC: Min. 100 × 103 ope. |
* | During 4-point simultaneous operation, the rating per point is also as shown above. |
---|
Mountable relays | Maximum load voltage (DC, AC peak value) |
Continuous load current (DC, AC peak value) |
Mountable relays | Maximum load voltage (DC, AC peak value) |
Continuous load current (DC, AC peak value) |
||
---|---|---|---|---|---|---|---|
Type | Part No. | Type | Part No. | ||||
DC only | AQZ102D | 60 V | 1.80 A | AC, DC dual use |
AQZ202D | 60 V | 1.350 A |
AQZ105D | 100 V | 1.15 A | AQZ205D | 100 V | 0.900 A | ||
AQZ107D | 200 V | 0.55 A | AQZ207D | 200 V | 0.450 A | ||
AQZ104D | 400 V | 0.30 A | AQZ204D | 400 V | 0.225 A |
* | During 4-point simultaneous operation, the rating per point is also as shown above. Please use a load current that is within the range of the data given below in “REFERENCE DATA Load current vs. ambient temperature characteristics”. |
---|
Item | Specifications | Condition | |
---|---|---|---|
Dielectric strength (Initial) |
Between input and output | 2,000 Vrms | for 1 min |
Between different terminals (between relays, both ways) |
1,500 Vrms | for 1 min | |
Insulation resistance | Min. 100 MΩ (Measured portion is the same as the case of dielectric strength.) | Using 500 V DC megger | |
Shock resistance |
Destructive | Min. 196 m/s2 | In vertical, horizontal and longitudinal directions |
Functional | Min. 98 m/s2 | In vertical, horizontal and longitudinal directions | |
Vibration resistance |
Destructive | 10 to 55 Hz at double amplitude of 1 mm | In vertical, horizontal and longitudinal directions |
Functional | 10 to 55 Hz at double amplitude of 1 mm | In vertical, horizontal and longitudinal directions | |
Use condition | Ambient temperature | -20 to +55°C | Avoid icing and condensation |
Ambient humidity | 35 to 85% RH | Avoid condensation | |
Storage temperature | -30 to +80°C | Avoid icing and condensation | |
Terminal screw fasten torque | 0.3 to 0.5 N·m (3 to 5 kgf·cm) | ||
Coil surge absorber | Diode (1 A, 400 V) | ||
Cross connection protecting diode | 1 A, inverse voltage 400 V | ||
Unit weight | Approx. 100 g |
*1 | Dielectric strength and insulation resistance are initial values. |
---|---|
*2 | Condensing occurs when the unit relay is exposed to sudden temperature change in a high temperature and high humidity atmosphere. This may cause some troubles like insulation failure of the socket or the PC board. Take care under this condition. |
*3 | Below 0°C, condensing water can freeze and cause socket contact failures and other problems. Take care under this condition. |
|
Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])