S1DXM-A/M Multi-range Timers

 

RoHS compatible UL CSA Marking CE Marking

Features

1.Multiple functions built in

The operation mode and time range can be switched by using the MODE and RANGE switches on the front panel.

2.Part number consolidation

1.The lineup consists of 64 easy-to-choosemodels.
2.An operation mode fixed type (S1DXM-A) and 4-operation mode switching type (S1DXM-M) are available.

3.Cadmium-free contacts used

To eliminate environmentally harmful chemical substances, relays with cadmium-free contacts are used.

4.Economically priced

1.Prices set to lower costs.
2.Further cost reduction when used with HJ Relay terminal socket.

5.CE marking supporte

UL and C-UL approved.


Operation Mode

1.S1DXM-A multi-range timer

Operation mode
Power ON-delay operation When power is turned on, the output contact operates after the set time.
The output contact remains on until the power is turned off.

2.S1DXM-M multi-range timer

Operation mode
Power ON-delay operation
[MODE] switch 1: OFF, switch 2: OFF
. When power is turned on, the output contact operates after the set time.
The output contact remains on until the power is turned off.
Power Flicker OFF start operation
[MODE] switch 1: OFF, switch 2: ON
When the power is turned on, the output contacts repeatedly operate at the set time.
The output contact begins from the off state.
Power Flicker ON start operation
[MODE] switch 1: ON, switch 2: OFF
When power is turned on, the output contact operates repeatedly at the set time.
The output contact outputs at the same time power turns on.
Power One-shot operation
[MODE] switch 1: ON, switch 2: ON
When power is turned on, the output contact performs the on operation at the same time power turns on, only for the set time.

Time range setting

Type Time scale Time unit Min.scale Max.scale Setting range
S1DXM-A 10M type ×1 ×10 s m 0.05 1 0.05 to 1s 0.5 to 10s 0.05 to 1m 0.5 to 10m
30M type s m 0.2 3 0.2 to 3s 2 to 30s 0.2 to 3m 2 to 30m
60M type s m 0.5 6 0.5 to 6s 5 to 60s 0.5 to 6m 5 to 60m
10H type m h 0.05 1 0.05 to 1m 0.5 to 10m 0.05 to 1h 0.5 to 10h
S1DXM-M 10M type ×1 ×10 s m 0.05 1 0.05 to 1s 0.5 to 10s 0.05 to 1m 0.5 to 10m
30M type s m 0.2 3 0.2 to 3s 2 to 30s 0.2 to 3m 2 to 30m
60M type s m 0.5 6 0.5 to 6s 5 to 60s 0.5 to 6m 5 to 60m
10H type m h 0.05 1 0.05 to 1m 0.5 to 10m 0.05 to 1h 0.5 to 10h
*The time setting range is the combination of the time scale (X1 or X10) on the dial and the time unit (s, m, or h).
Example: When dial reads 1,time scale is X1 and time units is seconds, then it is 1 second.

Operation Mode and Time Range Setting

Operation mode Power ON-delay Power Flicker OFF start Power Flicker ON start Power One-shot
Operation mode switch
Time range switch
The time setting can be switched among 4 ranges each for 4 types
for an interval between 0.05 seconds and 10 hours.
1* The product is factory shipped with all settings on the OFF side (left).
2* Do not operate the switches with a sharp-edged object such as a knife blade.
3* The power must be turned off when setting the time range or operation mode. Operating the switches with the power on is a cause of breakdown and malfunction.
4* Use a force of under 5 N to operate the DIP switches when setting the time range and operation mode.