Limitation of combination of units
1.Up to 3 expansion or intelligent units can be connected to each base control unit.
2.There is no restriction on the type and the order in which expansion units are installed.
3.The relay output type and transistor type can be used in conjunction with each other.
Expansion method
No special expansion cables are required as the expansion unit employs a stacking system that uses expansion connectors and lock levers on the unit.
Controllable I/O points when expansion units are added
Type of control unit | Control unit only | When the expansion unit is the same output type as the control unit | When the expansion unit is a transistor output type |
---|---|---|---|
C10 | 10 points | Max. 58 points | Max. 106 points |
C14 | 14 points | Max. 62 points | Max. 110 points |
C16 | 16 points | Max. 112 points | Max. 112 points |
C32 T32 F32 |
32 points | Max. 128 points | Max. 128 points |
Type of units | Control unit | Expansion unit | Input circuit | Output circuit | |
---|---|---|---|---|---|
The current consumed by the control unit power supply connector. If expansion units or intelligent units are added, the current is increased by the value indicated below. | The current consumed by the expansion unit power supply connector. If a unit is not listed below, it means that it has no power supply connector. | The current consumed by the input circuits of the various units. The value indicates the current that flows into the input circuit. "n" indicates the number of points that are on. | The current consumed by the output circuits of the various units. The value indicates the current used to drive the output circuit. "n" indicates the number of points that are on. The value does not include the load current value. | ||
FP0R control units |
C10 | 100mA or less | - | 15.9mA | - |
C14 | 120 mA or less | - | 21.1mA | - | |
C16 | 70mA or less | - | 21.1mA | 20mA | |
C32 T32 F32 |
90mA or less | - | 42.2mA | 40mA | |
FP0 expansion units |
FP0-E8X | 10mA or less | - | 34.4mA or less | - |
FP0-E8R | 15mA or less | 50mA or less | 17.2mA or less | - | |
FP0-E8YR | 10mA or less | 100mA or less | - | - | |
FP0-E8YT/P | 15mA or less | - | - | 24mA or less | |
FP0-E16X | 20mA or less | - | 68.8mA or less | - | |
FP0-E16R | 20mA or less | 100mA or less | 34.4mA or less | - | |
FP0-E16T/P | 25mA or less | - | 34.4mA or less | 24mA or less | |
FP0-E16YT/P | 25mA or less | - | - | 48mA or less | |
FP0-E32T/P | 40mA or less | - | 68.8mA or less | 48mA or less | |
FP0 intelligent unit |
FP0-A21 | 20mA or less | 100mA or less | - | - |
FP0-A80 | 20mA or less | 60mA or less | - | - | |
FP0-A04V | 20mA or less | 100mA or less | - | - | |
FP0-A04I | 20mA or less | 130mA or less | - | - | |
FP0-TC4 FP0-TC8 |
25mA or less | - | - | - | |
FP0-IOL | 30mA or less | 40mA or less | - | - | |
FP0-CCLS | 40mA or less | 40mA or less | - | - |
|