【Notification of Manufacturer Change for Panasonic Industrial Devices SUNX Products and Panasonic Industrial Devices SUNX Tatsuno Products】
From April 1, 2024, the terms "Panasonic Industrial Devices SUNX Co., Ltd." and "Panasonic Industrial Devices SUNX Tatsuno Co., Ltd."
in this page and in the manuals and other documents to be downloaded will all be replaced with "Panasonic Industry Co., Ltd." and applied accordingly.

AUTOMATION
CONTROLS

Search
Discontinued
Products



Digital Pressure Controller PAD (Discontinued Products)

Specifications

Model No. PAD-D1 PAD-1 PAD-2 PAD-10 PAD-50
Applicable pressure sensor PLX-D1L PLX-1L PLX-2L PLX-10L PLX-50L
Supply voltage 12 to 24 V DC ± 10 % Ripple P-P 10 % or less
Current consumption 260 mA or less
Power supply for sensor 12 V DC +10 / 0 %, 70 mA or less
Inputs Sensor input Range of input current: 4 to 20 mA (Maximum aliowable current: 50 mA)
Input impedance: 20 Ω approx.
Sampling cycle: 50 ms (20 times/sec.)
Auto-reference input Activating auto-reference function
・Operation: NPN non-contact input, edge trigger at signal falling
・Signal condition
Low level: 1.5 V or less
Low level output current: 0.6 mA or less
Low level input time: 0.5 ms or more
Outputs Comparative outputs
(HI, GO, LO)
NPN open-collector transistor
・Maximum sink current: 100 mA
・Applied voltage: 30 V DC or less (between comparative output and 0 V)
・Residual voltage: 1 V or less (at 100 mA sink current)
0.4 V or less (at 16 mA sink current)
  Output
operation
Response time 100 ms or less (150 ms or less during auto-reference active)
Display Measurement value display 3 1/2 digit LCD display [Sampling cycle: 250 ms (4 times/sec.)]
  Display range +0.0 to +100.0 kPa +0.000 to +1.000 MPa +0.000 to +1.999 MPa +0.00 to +10.00 MPa +0.0 to +50.0 MPa
Setting value display 3 1/2 digit LCD display
  Setting range -199.9 to +199.9 kPa -1.999 to +1.999 MPa -1.999 to +1.999 MPa -19.99 to +19.99 MPa -199.9 to +199.9 MPa
Comparative output display "HI", "GO" or "LO" LCD display
(HI, GO or LO lights up when the corresponding output is activated)
Indication accuracy ± (measurement value x 0.15 % + 1 digit) or less at 23 ± 1 ℃ 73.4 ± 33.8 ℉
Ambient temperature 0 to +50 ℃ +32 to +122 ℉ (No dew condensation), Storage: -10 to +60 ℃ +14 to +140 ℉
Connection method Terminal block
Weight 230 g approx.
Dimensions W72 x H72 x D88.2 mm W2.835 x H2.835 x D3.472 in

(Note) :Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +20 ℃ +68 ℉ .

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region







BY PHONE

Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])