Tank Level Sensor UA-11 (Discontinued Products)

Specifications

Type Amplifier built-inzultrasonic
Model No. UA-11
Applicable tank
(Note 1)
Tank diameter (Note 2) ø300 to ø3,000mm
Wall thickness (Note 2) 6mm or less
Material (Note 3) Metal (stainless steel, iron etc.)
Contents Water or similar viscosity liquid (without bubbles)
Supply voltage

12 to 24V DC510% Ripple P-P 10% or less

Current consumption 60mA or less
Repeatability ±3mm (with water)
Output
(Output 1, Output 2)
NPN open-collector transistor
・Maximum sink current: 100mA
・Applied voltage: 30V DC or less (between output and 0V)
・Residual voltage:
1.5V or less (at 100mA sink current)
1V or less (at 40mA sink current)
  Utilization category DC-12 or DC-13
Output operation Output 1: ON when liquid is detected, Output 2: OFF when liquid is detected
Short-circuit protection Incorporated
Response time (Note 4) 5ms approx. (for 3,000mm tank diameter with water inside)
Operation indicator Red LED (lights up when Output 1 is ON)
Stability indicator Green LED (lights up under stable operation)
Sound emission lock function Incorporated
Interference prevention function Incorporated
Environmental resistance Pollution degree 3 (Industrial environment)
Protection IP67 (IEC)
Ambient temperature

-10 to +80℃ (No dew condensation or icing allowed), Storage: -20 to +90℃

Ambient humidity 35 to 85% RH, Storage: 35 to 85% RH
EMC Emission: EN50081-2, Immunity: EN50082-2
Voltage withstandability 1,000V AC for one min. between all supply terminals connected together and enclosure
Insulation resistance 20MΩ, or more, with 250V DC megger between all supply terminals connected together and enclosure
Vibration resistance 10 to 500Hz frequency, 1.5mm amplitude in X, Y and Z directions for two hours each
Shock resistance 500m/s2 acceleration (50G approx.) in X, Y and Z directions for three times each
Enclosure earthing Capacitor earth
Material Enclosure: Stainless steel (SUS304), Indicating part: PFA, Skirt: EPR, Adjuster: PPS

Cable

0.2mm2 6-core cabtyre cable, 5m long
Cable extension Extension up to total 100m is possible with 0.5mm2, or more, cable.
Weight 310g approx.
Accessories MS-UA11-2 (Sensor-side mounting bracket): 1 No., UA-G1 (Paste): 1 No., Adjusting screwdriver: 1 No.

(Note 1) :It cannot be used for multi-layered tanks, such as, a tank having thermal insulating jacket for refrigeration, heat-retaining, etc.
(Note 2) :The allowable tank diameter and the wall thickness may vary from the above due to the contents and/or the tank shape. Please enquire for details.
(Note 3) :It cannot be used for tanks made of resin.
(Note 4) :The response time varies with the tank diameter and the type of liquid. Please enquire for details.

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region







BY PHONE

Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)