DPC-101-P | Head-separated Dual Display Digital Pressure Sensor [For Gas] DPH-100 / DPC-100


Head-separated Dual Display Digital Pressure Sensor [For Gas] DPH-100 / DPC-100

*Photo may vary from actual product.

  • RoHS Compliant This product has been confirmed that it does not contain the 6 substances specified in EU RoHS Directive 2011/65/EU and the 4 substances specified in 2015/863/EU.  


Product Number DPC-101-P
Part Number DPC-101-P
Product Head-separated Dual Display Digital Pressure Sensor [For gas]
Details Controller
Product name Head-separated Dual Display Digital Pressure Sensor [For Gas] DPH-100 / DPC-100

As of May 18, 2024
Specifications and design of the products are subject to change without notice for the product improvement.

Spec Detail

Item Specifications
Product Number DPC-101-P
Part Number DPC-101-P
CE marking directive compliance EMC Directive, RoHS Directive
Type of pressure Gauge pressure
Rated pressure range DPH-101□(Compound pressure): -100.0 to +100.0 kPa,
DPH-102□(Positive pressure): 0 to +1.000 MPa,
DPH-103□(Vacuum pressure): 0 to -101.0 kPa
(Note) : It changes automatically according to the connected pressure sensor head.
Set pressure range DPH-101□(Compound pressure) : -199.9 to +199.9 kPa (-1.999 to +1.999 kgf/cm2, -19.98 to +19.98 psi, -1.999 to +1.999 bar, -1510 to +1537 mmHg, -59.4 to +60.5 inHg)
DPH-102□(Positive pressure) : -1.050 to +1.050 MPa (-10.71 to +10.71 kgf/cm2, -152.2 to +152.2 psi, -10.50 to +10.50 bar)
DPH-103□(Vacuum pressure) : +101.3 to -101.3 kPa (+1.033 to -1.033 kgf/cm2, +14.70 to -14.70 psi, +1.013 to -1.013 bar, +760 to -760 mmHg, +29.9 to -29.9 inHg)
(Note) : It changes automatically according to the connected pressure sensor head.
Supply voltage 12 to 24 V DC ± 10 % Ripple P-P 10 % or less
Power consumption Normal operation : 960 mW or less (Current consumption 40 mA or less at 24 V supply voltage)
ECO mode (STD) : 720 mW or less (Current consumption 30 mA or less at 24 V supply voltage)
ECO mode (FULL) : 600 mW or less (Current consumption 25 mA or less at 24 V supply voltage)
Excluding the current consumption of sensor head and analog output current
Sensor head supply voltage Same as supply voltage
Comparative output PNP open-collector transistor (2 outputs)
・Maximum source current : 100 mA
・Applied voltage : 30 V DC or less
(between comparative output and +V)
・Residual voltage : 2 V or less (at 100 mA source current)
Comparative output:Output operation NO / NC, selectable by key operation
Comparative output:Output modes EASY mode / Hysteresis mode / Window comparator mode
Comparative output:Hysteresis Minimum 1 digit (variable)(however, 2 digits when using psi unit)
Comparative output:Repeatability With vacuum / positive pressure type connected : within ±0.2 % F.S. (±2 digits)
With compound pressure type connected : within ±0.2 % F.S. (±4 digits)
Comparative output:Response time 0.5 ms, 1 ms, 2.5 ms, 5 ms, 10 ms, 25 ms, 50 ms, 100 ms, 250 ms, 500 ms, 1,000 ms, 5,000 ms, selectable by key operation
Comparative output:Short-circuit protection Incorporated
Analog output <Analog voltage output>
・Output current : 1 to 5 V DC
・Zero point : within 1 V ± 0.5 % F.S.
(vacuum / positive pressure type)
within 3 V ± 0.5 % F.S. (compound pressure type)
・Span : within 4 V ± 0.5 % F.S.
・Linearity : within ±0.1 % F.S.
・Output impedance : 1 kΩ approx.

<Analog current output>
・Output current : 4 to 20 mA
・Zero point : within 4 mA ± 1 % F.S.
(vacuum / positive pressure type)
within 12 mA ± 1.5 % F.S. (compound pressure type)
・Span : within 16 mA ± 1.5 % F.S.
・Linearity : within ±0.1 % F.S.
・Load resistance : 250 Ω (max.).
Inputs : Sensor head input Input voltage range : 1 to 5 V DC (over rated pressure range)
Inputs : External input (Auto-reference function/Remote zero-adjustment function) ON voltage : +5 V to +V DC
OFF voltage : +0.6 V DC or less, or open
Input impedance : 10 kΩ approx.
Input time : 1 ms or more
Display 4 digits + 4 digits 3-color LCD display (Display refresh rate : 250 ms, 500 ms, 1,000 ms, selectable by key operation)
Display : Displayable pressure range Vacuum pressure : +5.1 to -101.3 kPa,
Positive pressure : -0.050 to +1.020 MPa,
Compound pressure : -101.3 to +105.0 kPa
Operation indicator Orange LED (Comparative output 1 operation indicator, comparative output 2 operation indicator : Lights up when each comparative output is ON)
Protection IP40 (IEC)
Ambient temperature -10 to +50 ℃ +14 to +122 ℉ (No dew condensation or icing allowed), Storage : -10 to +60 ℃ +14 to +140 ℉
Ambient humidity 35 to 85 % RH, Storage : 35 to 85 % RH
Voltage withstandability 1,000 V AC for one min. between all supply terminals connected together and enclosure
Insulation resistance 50 MΩ, or more, with 500 V DC megger between all supply terminals connected together and enclosure
Vibration resistance 10 to 500 Hz frequency, double amplitude 3 mm 0.118 in or maximum acceleration 196 m/s2, in X, Y and Z directions for two hours each (when panel mounting bracket is mounted : 10 to 150 Hz frequency, double amplitude 0.75 mm 0.030 in or maximum acceleration 49 m/s2, in X, Y and Z directions for two hours each)
Shock resistance 100 m/s2 acceleration (10 G approx.) in X, Y and Z directions three times each
Temperature characteristics Within ±0.5 % F.S. (ambient temperature range based on +20 ℃ +68 ℉)
Material Enclosure : PBT (glass fiber reinforced), LCD display : Acrylic, Mounting threaded part : Brass (nickel plated), Switch part : Silicone rubber
Connecting method Connector
Cable length Total length up to 100 m 328.084 ft is possible with 0.3 mm2, or more, cable.
Weight Net weight : 25 g approx. (excluding connector attached cable), Gross weight : 140 g approx.
Accessories CN-66A-C2 (Connector attached cable 2 m 6.562 ft), Pressure unit label : 1 set
Remark Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +20 ℃ +68 ℉.
The values specified above are applied only to the controller.

Return to top

Accessories (Option)

no_image
Product Number CN-66A
Part Number CN-66A
Product name Connector
no_image
Product Number CN-66A-C2
Part Number CN-66A-C2
Product name Connector-attached cable
no_image
Product Number CN-66A-C5
Part Number CN-66A-C5
Product name Connector-attached cable


More



Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region







BY PHONE

Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)