企業專屬首頁 > 電子元件/工業用機器 > 制御機器首頁 > FA 感測器/系統 > 感測器 > 安全光柵‧安全機器 > 安全漏液感測器 [Type4 PLe SIL3] SQ4 > 品名 > SQ4-A21-P
品名 | SQ4-A21-P |
型號 | SQ4-A21-P |
產品 | Safety Liquid Leak Sensor [Control Category 4 PLe SIL3] |
詳細 | Sensor [For standard liquid] |
產品名稱 | 安全漏液感測器 [Type4 PLe SIL3] SQ4 |
截至2024年05月20日
為了改善本產品,會有在未事先通知的情況下變更本產品的規格及設計的情況。
項目 | 內容 |
---|---|
品名 | SQ4-A21-P |
型號 | SQ4-A21-P |
Sensing object | Water (Standard liquid) (Note 1) Highly viscous liquid may not be stably detected. (Note 2) The agents mentioned above are examples. It may not be detected depending on viscosity the agent. Before using this device, check the detecting liquid and installation condition. |
Power voltage | 12 to 24 V DC plus or minus 10 % Ripple P-P 10 % or less |
Current consumption | 30 mA or less |
Utilization category | DC-12, DC-13 |
Detection output(Leakage detection) | PNP open-collector transistor - Maximum source current: 50 mA - Applied voltage: Same as the supply voltage (between detection output and +V) - Residual voltage: 2.5 V or less (at 50 mA source current) |
Detection output(Leakage detection):Response time | 10 ms or less |
Detection output(Leakage detection):Output operation | ON when normal condition or initial detection, OFF when detection leakage or wrong installation |
Detection output(Leakage detection):Short-circuit protection | Incorporated |
Detection auxiliary output(Initial detection) | PNP open-collector transistor - Maximum source current: 50 mA - Applied voltage: Same as the supply voltage (between detection auxiliary output and +V) - Residual voltage: 2.5 V or less (at 50 mA source current) |
Detection auxiliary output(Initial detection):Response time | 50 ms or less |
Detection auxiliary output(Initial detection):Output operation | ON when normal condition, OFF when initial detection or accidental leakage |
Detection auxiliary output(Initial detection):Short-circuit protection | Incorporated |
Protection | IP65 / IP67 (IEC) |
Ambient temperature | -10 to +55 ℃ +14 to +131 ℉ (No dew condensation or icing allowed) (Note) Storage: -10 to +55 ℃ +14 to +131 ℉ (Note) Liquid being detected should be also kept within the rated ambient temperature range. |
Ambient humidity | 35 to 85 % RH, Storage: 35 to 85 % RH |
Emitting element | Infrared LED (modulated) |
Material | Enclosure: Polypropylene |
Cable | 0.18 mm2 4-core PVC cabtyre cable, 2 m 6.562 ft long |
Weight | Net weight: 45 g approx Gross weight: 110 g approx |