AUTOMATION
CONTROLS

Search
Discontinued
Products



LH2H Hour Meters (Discontinued Products)

Rating/ Performance

Panel Mounting Type

Type Standard type Backlight type Standard type
item Non-voltage input Voltage input Voltage input Free voltage type
No. digits 7 digits
External power supply Not required (built-in battery)
Measurement time range 0 to 999999.9h/0 to 3999d23.9h (Switchable by switch)
0 to 999h59m59s/0 to 9999h59.9m (Switchable by switch) Separate product type
>Start
input
>Min. input signal width 200ms
Input method (signal) Non-voltage input using contacts or open collector connection High level: 4.5 to 30 V DC
Low level: 0 to 2 V DC
High level: 24 to 240 V AC/DC
Low level: 0 to 2.4 V AC/DC
Input impedance When shorted: Max. 10 kΩ
When open: Max. 750 kΩ
Approx. 4.7 kΩ -
Residual voltage Max. 0.5 V - -
Reset
input
Min. input signal width 100ms
Input method (signal) Non-voltage input using contacts or open collector connection High level: 4.5 to 30 V DC
Low level: 0 to 2 V DC
Non-voltage input using contacts or open collector connection
Input impedance When shorted: Max. 10 kΩ
When open: Max. 750 kΩ
Appox. 4.7 kΩ When shorted: Max. 10 kΩ
When open: Max. 750 kΩ
Residual voltage Max 0.5 V - Max 0.5 V
Display method 7-segment LCD 7-segment LCD With green/red backlight 7-segment LCD
Breakdown voltage (initial) Between charged and uncharged parts: 1,000 V AC for 1 minute. Between charged and uncharged parts: 2,000 V AC for 1 minute.
Insulation resistance (initial) Min. 100 MΩ (measured at 500 V DC) Measurement location same as for break down voltage.
Backlight power - 24 V DC (±10%) -
Protective construction (Note) IEC Standard IP66 (only panel front: when using rubber gasket)
Accessories (Note) Rubber gasket, mounting bracket
Battery life 10 years (at 25°C/ 77°F)
Note) Only for installation frame type.

PC Board Mounting Type

Type PC board mounting type
Item
Input method Non DC voltage input
No. digits 7 digits
Rated operation voltage 3 V DC
Allowable operation voltage range 2.7 to 3.3 V DC
Current consumption Max. 20 μA (max. 200 μA during reset input)
Measurement time range 0 to 999999.9h 0 to 9999h59.9m
Start
input
Min. input signal width 200ms
Input method Non-voltage input using contacts or open collector connection
Input impedance When shorted: Max. 10 kΩ
When open: Max. 750 kΩ
Residual voltage Max. 0.5 V
Reset
input
Min. input signal width 10ms
Input method Non-voltage input using contacts or open collector connection
Input impedance When shorted: Max. 10 kΩ
When open: Max. 750 kΩ
Residual power Max. 0.5 V
Break down voltage (initial) Between charged and uncharged parts: 1,000 V AC for 1 minute.
Insulation resistance (initial) Min. 100 MΩ (measured at 500 V DC) Measurement location same as for break down voltage.

Common

Type Panel mounting/PC board mounting types
Item
Time accuracy ±100 ppm (25°C/ 77°F)
Vibration resistance Functional 10 to 55 Hz (1 cycle/min.), single amplitude: 0.15 mm (10 min. on 3 axes)
Destructive 10 to 55 Hz (1 cycle/min.), single amplitude: 0.375 mm (1 hr. on 3 axes)
Shock resistance Functional Min. 98 m/s2 (4 times on 3 axes)
Destructive Min. 294 m/s2 (5 times on 3 axes)
Operation temperature --10 to +55°C/ +14 to +131°F (without frost or dew)
Storage temperature --25 to +65°C/ --13 to +149°F (without frost or dew)
Ambient humidity 35 to 85% RH (non-condensing)

Explanation of Operation

1.Time measuring takes place when the start input is ON.

2.When the elapsed (measured) time reaches full scale it returns to "0", and then measuring starts again from "0".

3.When reset input is ON, the display becomes "0". You cannot measure during reset input.

For PC board mounting type the display disappears while the reset input is ON; however, the display reads "0" when the reset input turns OFF.

4.Press the front reset button if you want to perform a manual reset (for panel installation type)

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region




Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)