Business > Industrial Devices > Automation Controls Top > FA Sensors & Components > Timers / Counters / FA Componets > Timers > PM4H-F Off-Delay Timers(Discontinued Products) > Rating/ Performance
We are sorry, the products have been discontinued. Please refer to the details of the discontinued products and the recommended substitutes list below.
|
|
Type Item |
PM4H-F8 | PM4H-F8R | PM4H-F11R | ||
---|---|---|---|---|---|
Rating | Rated operating voltage | 100 to 120V AC, 200 to 240V AC, 24V AC, 12V DC, 24V DC | |||
Rated frequency | 50/60Hz common (AC operating type) | ||||
Rated power consumption |
Approx. 1.6VA (100 to 120V AC, 200 to 240V AC), Approx. 2.3VA (24V AC) Approx. 1.1W (12V DC, 24V DC) |
||||
Rated control capacity | 3A 250V AC (resistive load) | ||||
Operation mode | Power OFF-delay | Power OFF-delay (with reset) | |||
Time range | 1s to 10s: 3 range switchable 1min to 10 min: 3 range selectable | ||||
Time accuracy *1 | Operation time fluctuation | ±0.3% | |||
Setting error | ±5% (Max. setting time value) | ||||
Voltage error | ±0.5% (at the operating voltage changes between 85 to 110%) | ||||
Temperature error | ±2% (at 20°C ambient temp. at the range of -10 to +50°C +14 to +122°F) | ||||
Contact | Contact arrangement | Timed-out 2 Form C | Timed-out 1 Form C | Timed-out 2 Form C | |
Contact resistance (Initial value) | Max. 100mohm (at 1A 6V DC) | ||||
Contact material | Au flash on Silver alloy | ||||
Life | Mechanical (contact) | 107 | |||
Electrical (contact) | 105 (at rated control capacity) | ||||
Electrical function | Allowable operating voltage range | 85 to 110% of rated operating voltage (at 20°C coil temp.), 90 to 110% (DC Type) | |||
Insulation resistance (Initial value) |
Min. 100Mohm Between live and dead metal parts Between input and output Between contacts of different poles *3 Between contacts of same pole (At 500V DC) |
||||
Breakdown voltage (Initial value) |
1, 500Vrms for 1 min Between live and dead metal parts 1, 500Vrms for 1 min Between input and output 1, 000Vrms for 1 min Between contacts of different poles *3 750Vrms for 1 min Between contacts of same pole |
||||
Min. power supply width |
s range type: 100ms min range type: 2s |
||||
Min. reset time | - | 50ms | |||
Max. temperature rise | 55°C/ 131°F | ||||
Mechanical function | Vibration resistance | Functional | 10 to 55Hz: 1 cycle/min double amplitude of 0.5mm (10min on 3 axes) | ||
Destructive | 10 to 55Hz: 1 cycle/min double amplitude of 0.75mm (1h on 3 axes) | ||||
Shock resistance | Functional | Min. 98m/s2 (4 times on 3 axes) | |||
Destructive | Min. 980m/s2 (5 times on 3 axes) | ||||
Operating condition | Ambient temperature | -10 to +50°C/ +14 to +122°F | |||
Ambient humidity | 30 to 85%RH (non-condensing) | ||||
Atmospheric pressure | 860 to 1, 060hPa | ||||
Ripple factor (DC type) | 20% | ||||
Others | Protective construction |
IP65 on front panel (using rubber gasket ATC 18002) (only for IP65 type) |
|||
Weight | 100g/ 3.527 oz (Pin type), 110g/ 3.880 oz (Screw terminal type) |
*1 Unless otherwise specified, the measurement conditions at the maximum scale time standard are specified to be the rated operating voltage (within 5% ripple factor for DC), 20℃/ 68℉ ambient temperature.
*2 For the 1s range, the tolerance for each specification becomes ±10ms. When the power goes on, in rush current (0.3A) flows. Cautions should be taken. The minimum power supplying time after forced reset input is 2s or more.
*3 Between contacts of different pools for F8, F11R types only.
|
Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)