AUTOMATION
CONTROLS

Search
Discontinued
Products



PM4S Multi-range Timers (Discontinued Products)

Application Standard

Safety standard EN61812-1 Pollution Degree 2/Overvoltage Category III
EMC (EMI)EN61000-6-4
Radiation interference electric field strength EN55011 Group 1 ClassA
Noise terminal voltage
(EMS)EN61000-6-2
EN55011 Group 1 ClassA
 
Static discharge immunity EN61000-4-2 4kV contact
8kV air
RF electromagnetic field immunity EN61000-4-3 10V/m AM modulation(80MHz to 1GHz)
10V/m pulse modulation (895MHz to 905MHz)
EFT/B immunity EN61000-4-4 1kV(power line)
Surge immunity EN61000-4-5 1kV(power line)
Conductivity noise immunity EN61000-4-6 10V/m AM modulation(0.15MHz to 80MHz)
Power frequency magnetic field immunity EN61000-4-8 30A/m(50Hz)
Voltage dip/Instantaneous stop/Voltage fluctuation immunity EN61000-4-11 10ms,30%(rated voltage)
100ms,60%(rated voltage)
1,000ms,60%(rated voltage)
500ms,95%(rated voltage)

Return to top