Type | PM5S-A | PM5S-S | PM5S-M | ||
---|---|---|---|---|---|
Item | |||||
Rating | Rated operating voltage | 24 to 240V AC/DC | |||
Rated frequency | 50/60Hz common | ||||
Rated power consumption | 2.6 VA (AC), 1.4 W (DC) | ||||
Rated control capacity | 5A 250V AC (resistive load) | ||||
Operating mode | Pulse ON-delay Pulse Flicker Pulse ON-Flicker Signal OFF-delay Pulse One-shot Pulse One-cycle |
Power ON-delay | Pulse ON-delay Pulse Flicker Pulse ON-flicker Signal OFF-delay Pulse One-shot Pulse One-cycle (with instantaneous contact) |
||
Time range | 1s to 500h (Max.) 16 time ranges switchable | ||||
Time accuracy (Note) |
Operating time fluctuation | ±0.3% (power off time change at the range of 0.1s to 1h) | |||
Setting error | ±10% (Full-scale value) | ||||
Voltage error | ±0.5% (at the operating voltage changes between 85 to 110%) | ||||
Temperature error | ±2% (at 20℃ ambient temp. at the range of –10 to +55℃ +14 to +131℉) | ||||
Contact | Contact arrangement | Timed-out 2 Form C |
Timed-out 1 Form C Instantaneous 1 Form C |
||
Contact resistance (Initial value) | Max. 100mΩ (at 1A 6V DC) | ||||
Contact material | Silver alloy | Au flash on Silver alloy | |||
Life | Mechanical (contact) | 2 x 107 | 1 x 107 | ||
Electrical (contact) | 105 (at rated control capacity) | ||||
Electrical function |
Allowable operating voltage range | 85 to 110% of rated operating voltage (at 20℃ coil temp.) | |||
Insulation resistance (Initial value) | Min. 100MΩ (Between live and dead metal parts, Between input and output, Between contacts of different poles, Between contacts of same pole) (At 500V DC) |
||||
Breakdown voltage (Initial value) | 2,000Vrms for 1 min Between live and dead metal parts 2,000Vrms for 1 min Between input and output 2,000Vrms for 1 min Between contacts of different poles 1,000Vrms for 1 min Between contacts of same pole |
||||
Min. power off time | 100ms | ||||
Max. temperature rise | 55℃ 131℉ | 65℃ 149℉ | |||
Mechanical function |
Shock resistance | Functional | Min. 98m/s2 (4 times on 3 axes) | ||
Destructive | Min. 980m/s2 (5 times on 3 axes) | ||||
Vibration resistance | Functional | 10 to 55Hz: 1 cycle/min Single amplitude of 0.35mm (10min on 3 axes) | |||
Destructive | 10 to 55Hz: 1 cycle/min Single amplitude of 0.75mm (1h on 3 axes) | ||||
Operating condition |
Ambient temperature | –10 to +55℃ +14 to +131℉ | |||
Ambient humidity | Max. 85%RH (non-condensing) | ||||
Atmospheric pressure | 860 to 1,060hPa | ||||
Ripple factor (DC) | 20% | ||||
Others | Protective construction | IP40 | |||
Weight | 120g 4.233 oz |
Note 1 : | Unless otherwise specified, the measurement conditions at the maximum scale time standard are specified to be the rated operating voltage (within 5% ripple factor for DC), 20℃ 68℉ ambient temperature, and 1s power off time. |
---|---|
Note 2 : | For the 1s range, the tolerance for each specification becomes ±10ms. |
|
Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)